1SDA056304R1 ABB E3S 3200 PR121/P-LI 3200A 3P Fixed Air Circuit Breaker

1SDA056304R1 ABB E3S 3200 PR121/P-LI 3200A 3P Fixed Air Circuit Breaker

ABB 1SDA056304R1 E3S 3200 three-pole fixed air circuit breaker rated at 3200 A with rear horizontal terminals and a PR121/P-LI electronic trip unit providing overload and instantaneous short-circuit protection for low-voltage power distribution.

SKU: 1SDA056304R1MPN: 1SDA056304R1
Price
List Price £22,749.02 ex VAT
Your Price (ex VAT) Save 25%
£17,061.77 25% OFF
You save £5,687.26 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £17,061.77
Trade pricing is personalised to your account

Manufacturer Lead Time

£17,061.77

Why Choose the ABB E3S 3200 PR121/P-LI 3200A 3P Fixed Air Circuit Breaker?

The ABB 1SDA056304R1 is a high-performance SACE Emax E3S air circuit breaker designed for switching and protection in high-current low-voltage electrical distribution systems. Rated at 3200 A, this three-pole fixed circuit breaker incorporates an ABB PR121/P-LI electronic overcurrent release for dependable overload and instantaneous short-circuit protection.

Part of the proven ABB SACE Emax E3 series, the E3S 3200 combines substantial current-handling capability with strong short-circuit performance. The S performance level provides rated ultimate and service short-circuit breaking capacities of 75 kA at 400 V AC, while the breaker is suitable for low-voltage AC distribution systems with rated operational voltage up to 690 V AC.

The PR121/P-LI release provides long-time overload (L) and instantaneous short-circuit (I) protection. This version features a three-pole fixed configuration with rear flat horizontal terminals and is equipped with four auxiliary contacts plus circuit-breaker open/closed position indication for integration into industrial switchboards and power distribution assemblies.

Key Advantages

  • High-current 3200 A air circuit breaker for demanding power distribution systems.
  • Three-pole fixed configuration for permanent switchboard installations.
  • PR121/P-LI electronic trip unit provides overload and instantaneous short-circuit protection.
  • 75 kA ultimate and service short-circuit breaking capacity at 400 V AC.
  • Suitable for AC distribution systems operating up to 690 V AC.
  • Rear flat horizontal terminals support practical busbar connection within switchboards.
  • Four auxiliary contacts and open/closed indication support status monitoring and control.

Key Features

  • ABB SACE Emax E3S 3200 air circuit breaker.
  • 3200 A rated uninterrupted current.
  • Three-pole configuration.
  • PR121/P-LI electronic overcurrent release.
  • LI protection: long-time overload and instantaneous short-circuit functions.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 75 kA rated ultimate short-circuit breaking capacity at 400 V AC.
  • 75 kA rated service short-circuit breaking capacity at 400 V AC.
  • 75 kA short-time withstand current for 1 s.
  • Fixed construction with rear flat horizontal terminal connections.

Reliable LI Protection for High-Current Distribution

Air circuit breakers such as the ABB E3S 3200 provide switching, isolation and automatic protection for high-current low-voltage distribution circuits. The electronic release monitors circuit current and commands the breaker to open when configured overload or short-circuit thresholds are exceeded, helping protect conductors, switchgear and connected electrical equipment.

The PR121/P-LI release combines long-time overload protection with instantaneous short-circuit protection for straightforward and dependable circuit protection. Together with the E3S breaker's 75 kA short-circuit performance and fixed rear horizontal connection arrangement, the 1SDA056304R1 is well suited to permanent switchboard installations requiring reliable high-current protection.

Typical Applications

  • Main incoming protection in low-voltage switchboards.
  • Industrial power distribution systems.
  • High-current feeder and distribution circuits.
  • Manufacturing and process plant electrical systems.
  • Commercial and infrastructure power distribution.
  • Transformer and generator distribution switchboards.
  • Fixed switchgear installations requiring high short-circuit performance.

Technical Specifications

Series SACE Emax E3
ABB order code 1SDA056304R1
Product type Air circuit breaker
Frame E3
Short-circuit performance level S
Rated current (In) 3200 A
Rated uninterrupted current (Iu) 3200 A
Rated operational current (Ie) 3200 A
Number of poles 3
Current type AC
Trip unit PR121/P-LI
Release type Electronic
Protection functions LI – long-time overload and instantaneous short-circuit
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 75 kA
Rated service short-circuit breaking capacity (Ics) at 400 V AC 75 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 65 kA
Power loss 330 W
Installation Fixed
Terminal connection Rear flat horizontal
Auxiliary contacts 4
Position indication Open / closed
Electrical durability at ≤440 V 6000 cycles
Electrical durability at 500–690 V 5000 cycles
Mechanical durability 20,000 cycles
Dimensions (W × H × D) 404 × 418 × 302 mm
Net weight 60 kg
Standard IEC
EAN 8015644576448
Product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA056304R1?

The ABB 1SDA056304R1 is a SACE Emax E3S 3200 three-pole fixed air circuit breaker rated at 3200 A and equipped with a PR121/P-LI electronic overcurrent release.

What protection functions does the PR121/P-LI provide?

The PR121/P-LI provides long-time overload (L) and instantaneous short-circuit (I) protection functions.

What is the current rating of the ABB E3S 3200 1SDA056304R1?

The circuit breaker has a rated current and rated uninterrupted current of 3200 A.

What is the breaking capacity of the ABB E3S 3200?

The E3S 3200 has a rated ultimate and service short-circuit breaking capacity of 75 kA at 400 V AC.

What installation and terminal arrangement does the ABB 1SDA056304R1 use?

The 1SDA056304R1 is a fixed three-pole circuit breaker with rear flat horizontal terminals, designed for permanent installation within compatible low-voltage switchboards.

Trusted ABB Protection for Critical Power Systems

ABB SACE Emax air circuit breakers provide dependable high-current switching and protection for demanding low-voltage power distribution systems, combining electronic protection, high short-circuit performance and robust switchboard construction.