Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056284R1 SACE Emax E3S2500 four-pole fixed air circuit breaker with a 2500 A rating, PR122/P-LSI R2500 electronic protection, rear horizontal terminals and 75 kA breaking capacity for demanding low-voltage power distribution.
£18,007.58
The ABB 1SDA056284R1 is a high-performance SACE Emax E3S air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product group, this four-pole fixed circuit breaker combines a 2500 A rated uninterrupted current with the advanced PR122/P-LSI R2500 electronic overcurrent release for dependable protection of industrial, commercial and infrastructure power networks.
The E3S2500 provides long-time, short-time and instantaneous protection through its LSI trip functionality. The PR122/P electronic release protects against overload, short-time delayed short-circuit and instantaneous short-circuit conditions while providing the enhanced measurement, signalling and accessory capabilities associated with ABB's PR122/P platform. This LSI configuration does not include integrated earth-fault protection.
With a rated uninterrupted current of 2500 A, a 690 V AC rated operational voltage and an ultimate short-circuit breaking capacity of 75 kA across the specified 220–690 V AC range, the E3S2500 provides robust protection for high-capacity distribution systems. This version features a four-pole fixed configuration with rear flat horizontal terminals, four auxiliary contacts and circuit-breaker open/closed position indication for permanent integration into low-voltage switchgear.
Air circuit breakers such as the ABB SACE Emax E3S2500 provide switching, isolation and electronic overcurrent protection at critical points within high-current low-voltage distribution systems. The E3 frame combines substantial continuous-current capability with the S short-circuit performance level, making it suitable for switchboards and distribution networks where robust fault interruption and short-time withstand capability are required.
The PR122/P-LSI electronic trip unit provides long-time overload, short-time delayed overcurrent and instantaneous short-circuit protection while offering the advanced electronic functionality of ABB's PR122/P platform. Combined with the fixed Emax construction, 75 kA breaking capacity and high short-time withstand capability, this configuration provides dependable protection and coordination for demanding industrial, commercial and infrastructure installations.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB order code | 1SDA056284R1 |
| EAN / GTIN | 8015644576240 |
| Customs tariff / HS code | 85362090 |
| Product type | Air circuit breaker |
| Frame / size | E3 |
| Short-circuit performance level | S |
| Rated current (In) | 2500 A |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated operational current (Ie) | 2500 A |
| Current type | AC |
| Number of poles | 4 |
| Installation | Fixed |
| Version | F |
| Terminal position | Rear |
| Terminal connection | Rear flat horizontal (HR) |
| Trip unit | PR122/P-LSI R2500 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Integrated earth-fault protection | No |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–690 V AC | 75 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–690 V AC | 75 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Mechanical durability | 20,000 operating cycles |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Electrical durability at ≤440 V | 8,000 operating cycles |
| Electrical durability at 500–690 V | 7,000 operating cycles |
| Maximum electrical operating frequency | 20 cycles per hour |
| Power loss | 205 W |
| Dimensions (W × H × D) | 530 × 418 × 302 mm |
| Net weight | 76 kg |
| Standard | IEC |
The ABB 1SDA056284R1 is an E3S2500 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems against overload and short-circuit conditions.
The 1SDA056284R1 has a rated uninterrupted current of 2500 A, making it suitable for substantial industrial, commercial and infrastructure power distribution applications.
The PR122/P-LSI R2500 electronic overcurrent release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.
The E3S2500 has a rated ultimate and service short-circuit breaking capacity of 75 kA across the specified 220–690 V AC range, together with a rated short-time withstand current of 75 kA for 1 s and 65 kA for 3 s.
The 1SDA056284R1 is a four-pole fixed air circuit breaker with rear flat horizontal terminals, designed for permanent installation within a suitable low-voltage switchboard or power distribution assembly.
ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high continuous-current capability, robust short-circuit performance and advanced electronic protection for industrial, commercial and infrastructure applications.