1SDA056284R1 ABB E3S2500 PR122/P-LSI 2500A 4P Fixed Air Circuit Breaker

1SDA056284R1 ABB E3S2500 PR122/P-LSI 2500A 4P Fixed Air Circuit Breaker

ABB 1SDA056284R1 SACE Emax E3S2500 four-pole fixed air circuit breaker with a 2500 A rating, PR122/P-LSI R2500 electronic protection, rear horizontal terminals and 75 kA breaking capacity for demanding low-voltage power distribution.

SKU: 1SDA056284R1MPN: 1SDA056284R1
Price
List Price £24,010.11 ex VAT
Your Price (ex VAT) Save 25%
£18,007.58 25% OFF
You save £6,002.53 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £18,007.58
Trade pricing is personalised to your account

Manufacturer Lead Time

£18,007.58

Why Choose the ABB E3S2500 PR122/P-LSI 2500A 4P Fixed Air Circuit Breaker?

The ABB 1SDA056284R1 is a high-performance SACE Emax E3S air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product group, this four-pole fixed circuit breaker combines a 2500 A rated uninterrupted current with the advanced PR122/P-LSI R2500 electronic overcurrent release for dependable protection of industrial, commercial and infrastructure power networks.

The E3S2500 provides long-time, short-time and instantaneous protection through its LSI trip functionality. The PR122/P electronic release protects against overload, short-time delayed short-circuit and instantaneous short-circuit conditions while providing the enhanced measurement, signalling and accessory capabilities associated with ABB's PR122/P platform. This LSI configuration does not include integrated earth-fault protection.

With a rated uninterrupted current of 2500 A, a 690 V AC rated operational voltage and an ultimate short-circuit breaking capacity of 75 kA across the specified 220–690 V AC range, the E3S2500 provides robust protection for high-capacity distribution systems. This version features a four-pole fixed configuration with rear flat horizontal terminals, four auxiliary contacts and circuit-breaker open/closed position indication for permanent integration into low-voltage switchgear.

Key Advantages

  • High-performance ABB SACE Emax E3S air circuit breaker for demanding low-voltage power distribution.
  • 2500 A rated uninterrupted current for substantial industrial and infrastructure electrical systems.
  • Four-pole fixed configuration suitable for three-phase systems requiring neutral switching.
  • PR122/P-LSI R2500 electronic overcurrent release for overload and short-circuit protection.
  • LSI functionality provides long-time, short-time and instantaneous protection.
  • 75 kA Icu and Ics across the specified 220–690 V AC operating range.
  • 75 kA Icw for 1 s and 65 kA Icw for 3 s provide robust short-time withstand performance.
  • Rear flat horizontal terminals provide a practical connection arrangement for fixed switchboard installations.

Key Features

  • ABB SACE Emax E3S2500 air circuit breaker.
  • 2500 A rated uninterrupted current.
  • Four-pole construction.
  • Fixed circuit-breaker configuration.
  • PR122/P-LSI R2500 electronic overcurrent release.
  • Long-time, short-time and instantaneous (LSI) protection functions.
  • No integrated earth-fault protection in this LSI configuration.
  • 690 V AC rated operational voltage.
  • 75 kA Icu at 220–690 V AC.
  • 75 kA Ics at 220–690 V AC.
  • 75 kA Icw for 1 s and 65 kA Icw for 3 s.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Rear flat horizontal terminals.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Reliable High-Performance Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E3S2500 provide switching, isolation and electronic overcurrent protection at critical points within high-current low-voltage distribution systems. The E3 frame combines substantial continuous-current capability with the S short-circuit performance level, making it suitable for switchboards and distribution networks where robust fault interruption and short-time withstand capability are required.

The PR122/P-LSI electronic trip unit provides long-time overload, short-time delayed overcurrent and instantaneous short-circuit protection while offering the advanced electronic functionality of ABB's PR122/P platform. Combined with the fixed Emax construction, 75 kA breaking capacity and high short-time withstand capability, this configuration provides dependable protection and coordination for demanding industrial, commercial and infrastructure installations.

Typical Applications

  • Main incoming circuit breakers in high-current low-voltage switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Manufacturing and process plants.
  • Transformer-fed distribution systems.
  • Generator distribution and protection systems.
  • High-current distribution feeder protection.
  • Four-pole distribution systems requiring neutral switching.
  • Fixed low-voltage switchgear and power distribution assemblies.

Technical Specifications

Series SACE Emax
Product group 310513-New Emax
ABB order code 1SDA056284R1
EAN / GTIN 8015644576240
Customs tariff / HS code 85362090
Product type Air circuit breaker
Frame / size E3
Short-circuit performance level S
Rated current (In) 2500 A
Rated uninterrupted current (Iu) 2500 A
Rated operational current (Ie) 2500 A
Current type AC
Number of poles 4
Installation Fixed
Version F
Terminal position Rear
Terminal connection Rear flat horizontal (HR)
Trip unit PR122/P-LSI R2500
Release type Electronic
Protection functions Long-time, short-time and instantaneous (LSI)
Integrated earth-fault protection No
Rated operational voltage 690 V AC
Rated voltage (Ur) 690 V
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 220–690 V AC 75 kA
Rated service short-circuit breaking capacity (Ics) at 220–690 V AC 75 kA
Rated short-time withstand current (Icw), 1 s 75 kA
Rated short-time withstand current (Icw), 3 s 65 kA
Auxiliary contacts 4
Position indication Circuit breaker open/closed
Mechanical durability 20,000 operating cycles
Maximum mechanical operating frequency 60 cycles per hour
Electrical durability at ≤440 V 8,000 operating cycles
Electrical durability at 500–690 V 7,000 operating cycles
Maximum electrical operating frequency 20 cycles per hour
Power loss 205 W
Dimensions (W × H × D) 530 × 418 × 302 mm
Net weight 76 kg
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA056284R1 used for?

The ABB 1SDA056284R1 is an E3S2500 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems against overload and short-circuit conditions.

What is the rated current of the ABB E3S2500 1SDA056284R1?

The 1SDA056284R1 has a rated uninterrupted current of 2500 A, making it suitable for substantial industrial, commercial and infrastructure power distribution applications.

What protection does the PR122/P-LSI trip unit provide?

The PR122/P-LSI R2500 electronic overcurrent release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.

What is the breaking capacity of the ABB E3S2500?

The E3S2500 has a rated ultimate and service short-circuit breaking capacity of 75 kA across the specified 220–690 V AC range, together with a rated short-time withstand current of 75 kA for 1 s and 65 kA for 3 s.

Is the ABB 1SDA056284R1 fixed or withdrawable?

The 1SDA056284R1 is a four-pole fixed air circuit breaker with rear flat horizontal terminals, designed for permanent installation within a suitable low-voltage switchboard or power distribution assembly.

Trusted Protection from ABB

ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high continuous-current capability, robust short-circuit performance and advanced electronic protection for industrial, commercial and infrastructure applications.