Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056188R1 SACE Emax E3S1250 four-pole fixed air circuit breaker with a 1250 A rating, PR122/P-LSI R1250 electronic protection and rear horizontal terminals for demanding low-voltage power distribution.
£11,094.21
The ABB 1SDA056188R1 is a high-performance SACE Emax E3S air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product group, this four-pole fixed circuit breaker combines a 1250 A rated current with the advanced PR122/P-LSI R1250 electronic overcurrent release for dependable protection of industrial, commercial and infrastructure power networks.
The E3S1250 provides long-time, short-time and instantaneous protection through its LSI trip functionality. The PR122/P electronic release protects against overload, delayed short-circuit and instantaneous short-circuit conditions while providing the enhanced measurement, signalling and accessory capabilities associated with ABB's PR122/P platform. This LSI configuration does not include integrated earth-fault protection.
The E3S performance level is designed for applications requiring high short-circuit performance within the SACE Emax range. This version features a four-pole fixed configuration with rear horizontal terminals, a PR122/P-LSI R1250 release, four auxiliary contacts and circuit-breaker open/closed position indication for permanent integration into low-voltage switchgear.
Air circuit breakers such as the ABB SACE Emax E3S1250 provide switching, isolation and electronic overcurrent protection at critical points within low-voltage distribution systems. The E3 frame combines substantial current-carrying capability with the S performance level, making it suitable for switchboards and distribution networks where higher prospective short-circuit currents require robust interruption capability.
The PR122/P-LSI electronic trip unit provides long-time overload, short-time delayed overcurrent and instantaneous short-circuit protection. Combined with the fixed Emax construction and high short-circuit performance of the E3S platform, this configuration provides dependable protection and flexible electronic adjustment for industrial, commercial and infrastructure power distribution applications.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB order code | 1SDA056188R1 |
| EAN / GTIN | 8015644575281 |
| Customs tariff / HS code | 85362090 |
| Product type | Air circuit breaker |
| Frame / size | E3 |
| Short-circuit performance level | S |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Current type | AC |
| Number of poles | 4 |
| Installation | Fixed |
| Version | F |
| Terminal position | Rear |
| Terminal connection | Rear horizontal (HR) |
| Trip unit | PR122/P-LSI R1250 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Integrated earth-fault protection | No |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 415 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 75 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Net weight | 90 kg |
| Standard | IEC |
The ABB 1SDA056188R1 is an E3S1250 air circuit breaker designed for switching and protecting low-voltage electrical distribution systems against overload and short-circuit conditions.
The 1SDA056188R1 has a rated current of 1250 A, making it suitable for substantial industrial, commercial and infrastructure power distribution applications.
The PR122/P-LSI R1250 electronic overcurrent release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.
E3 identifies the SACE Emax frame size, while S identifies the breaker's short-circuit performance level. The E3S configuration is intended for installations requiring higher fault-interruption performance than lower E3 performance classes.
The 1SDA056188R1 is a four-pole fixed air circuit breaker with rear horizontal terminals. It is designed for permanent installation within a suitable low-voltage switchboard or power distribution assembly.
ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining robust short-circuit performance, advanced electronic protection and flexible installation options for industrial, commercial and infrastructure applications.