Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB E3N3200PR122/P-LSI is a 3200 A three-pole withdrawable SACE Emax air circuit breaker moving part with a PR122/P-LSI R3200 electronic trip unit providing long-time, short-time and instantaneous overcurrent protection.
£21,024.28
The ABB E3N3200PR122/P-LSI is a high-performance 3200 A three-pole air circuit breaker moving part designed for reliable switching and overcurrent protection in demanding low-voltage power distribution systems. As part of the established ABB SACE Emax New Emax series, this E3N configuration combines a robust high-current breaker frame with the advanced PR122/P-LSI electronic overcurrent release.
The PR122/P-LSI trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. These LSI protection functions help safeguard cables, busbars, switchboards and connected electrical equipment against sustained overloads and short-circuit faults while supporting selective protection and coordination within complex electrical distribution networks.
With a rated uninterrupted current of 3200 A, a three-pole withdrawable moving-part configuration and a PR122/P-LSI R3200 release, ABB order code 1SDA056164R1 is designed for integration into compatible SACE Emax withdrawable switchgear. The moving part is fitted with four auxiliary contacts and circuit-breaker open/closed position indication for effective monitoring and control integration.
Air circuit breakers such as the ABB E3N3200 provide switching and overcurrent protection for high-current low-voltage distribution circuits. The electronic trip release monitors circuit conditions and initiates breaker operation when configured protection thresholds are exceeded, helping protect cables, busbars, switchboards and connected electrical equipment against damaging overload and short-circuit currents.
The PR122/P-LSI release combines long-time, short-time and instantaneous protection functions in an electronic trip system. Together with the E3N frame's 65 kA short-circuit performance, 3200 A current rating and service-friendly withdrawable construction, this moving part is well suited to critical main distribution and high-current feeder applications.
| Series | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA056164R1 |
| Extended product type | E3N3200PR122/P-LSIIn=3200A3pWMP |
| Product type | Air circuit breaker moving part |
| Frame | E3N |
| Short-circuit performance level | N |
| Rated current | 3200 A |
| Rated operational current | 3200 A |
| Rated uninterrupted current | 3200 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Rated ultimate short-circuit breaking capacity | 65 kA |
| Rated service short-circuit breaking capacity | 65 kA |
| Rated short-time withstand current | 65 kA for 1 s / 3 s |
| Execution | Withdrawable moving part (W MP) |
| Trip unit | PR122/P-LSI |
| Release type | Electronic |
| Overcurrent release rating | R3200 |
| Protection functions | L, S and I |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 570 W |
| Electrical durability | 6000 cycles at Ue ≤ 440 V; 5000 cycles at Ue 500–690 V |
| Maximum electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 432 × 461 × 396.5 mm |
| Net weight | 64 kg |
| EAN | 8015644575045 |
| Customs tariff number | 85362090 |
| Standard | IEC |
It is a 3200 A three-pole air circuit breaker moving part designed for switching and protecting high-current low-voltage AC power distribution circuits in compatible ABB SACE Emax withdrawable switchgear.
The PR122/P-LSI electronic trip unit provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
The E3N3200 has a rated ultimate and service short-circuit breaking capacity of 65 kA throughout its specified operational-voltage range up to 690 V AC, together with a rated short-time withstand current of 65 kA.
ABB order code 1SDA056164R1 is a three-pole withdrawable moving part for a compatible SACE Emax E3N circuit-breaker installation.
Yes. This configuration is fitted with four auxiliary contacts together with circuit-breaker open/closed position indication for signalling and control applications.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial low-voltage distribution systems, combining robust high-current switching technology with configurable electronic protection and service-friendly withdrawable configurations for demanding electrical installations.