ABB 1SDA056153R1 SACE Emax E3N3200 four-pole fixed air circuit breaker with a 3200 A rating, PR121/P-LSI electronic protection, rear horizontal terminals and 65 kA breaking capacity for demanding low-voltage power distribution.
£22,155.11
The ABB 1SDA056153R1 is a high-performance SACE Emax E3N air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product group, this four-pole fixed circuit breaker combines a 3200 A rated uninterrupted current with the PR121/P-LSI R3200 electronic overcurrent release for dependable protection of industrial, commercial and infrastructure power networks.
The E3N3200 provides long-time, short-time and instantaneous protection through its LSI trip functionality. The PR121/P electronic release protects against overload, short-time delayed short-circuit and instantaneous short-circuit conditions, with adjustable protection characteristics that support coordination and selectivity with other protective devices. This LSI configuration does not include integrated earth-fault protection.
With a rated uninterrupted current of 3200 A, operation on low-voltage systems up to 690 V AC and an ultimate short-circuit breaking capacity of 65 kA at 415 V AC, the E3N3200 provides robust protection for high-current distribution systems. This version features a four-pole fixed configuration with rear flat horizontal terminals, four auxiliary contacts and circuit-breaker open/closed position indication for permanent integration into low-voltage switchgear.
Air circuit breakers such as the ABB SACE Emax E3N3200 provide switching, isolation and overcurrent protection at critical points within high-current low-voltage distribution systems. The E3 frame accommodates substantial continuous currents, while the N performance level provides dependable short-circuit interruption and short-time withstand capability for industrial switchboards, transformer-fed networks and other high-capacity distribution applications.
The PR121/P-LSI electronic trip unit provides long-time overload, short-time delayed overcurrent and instantaneous short-circuit protection. Combined with the fixed Emax construction and 65 kA short-circuit performance, this configuration provides a robust solution for installations requiring high continuous-current capability, protection selectivity and dependable fault interruption.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB order code | 1SDA056153R1 |
| EAN | 8015644574932 |
| Customs tariff number | 85362090 |
| Product type | Air circuit breaker |
| Frame / size | E3 |
| Short-circuit performance level | N |
| Rated current (In) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Current type | AC |
| Number of poles | 4 |
| Installation | Fixed |
| Version | F |
| Terminal position | Rear |
| Terminal connection | Rear flat horizontal (HR) |
| Trip unit | PR121/P-LSI R3200 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Integrated earth-fault protection | No |
| Overload release adjustment range | 400–3200 A |
| Short-time delayed short-circuit release adjustment range | 3200–32000 A |
| Instantaneous short-circuit release adjustment range | 4800–48000 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 220 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 230 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 380 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 660 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Motor drive | Optional |
| Standard | IEC |
The ABB 1SDA056153R1 is an E3N3200 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems against overload and short-circuit conditions.
This circuit breaker has a rated uninterrupted current of 3200 A, making it suitable for high-current industrial, commercial and infrastructure power distribution applications.
The PR121/P-LSI electronic overcurrent release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.
The E3N3200 has a rated ultimate and service short-circuit breaking capacity of 65 kA across the specified 220–690 V AC range, together with a rated short-time withstand current of 65 kA for 1 s and 3 s.
The 1SDA056153R1 is a four-pole fixed air circuit breaker with rear flat horizontal terminals, designed for permanent installation within a suitable low-voltage switchboard or power distribution assembly.
ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high continuous-current capability, robust short-circuit performance and electronic overcurrent protection for industrial, commercial and infrastructure applications.
We use cookies