Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056152R1 SACE Emax E3N3200 four-pole fixed air circuit breaker with a 3200 A rating, PR121/P-LI electronic protection, rear horizontal terminals and 65 kA breaking capacity for demanding low-voltage power distribution.
£21,607.61
The ABB 1SDA056152R1 is a high-performance SACE Emax E3N air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product group, this four-pole fixed circuit breaker combines a 3200 A rated uninterrupted current with the PR121/P-LI R3200 electronic overcurrent release for dependable protection of industrial, commercial and infrastructure power networks.
The E3N3200 provides long-time and instantaneous protection through its LI trip functionality. The PR121/P electronic release protects against overload and instantaneous short-circuit conditions, with an overload adjustment range of 1280–3200 A and an instantaneous short-circuit release adjustment range of 4800–48000 A. This LI configuration does not include short-time delayed or integrated earth-fault protection.
With a rated uninterrupted current of 3200 A, a 690 V AC rated operational voltage and an ultimate short-circuit breaking capacity of 65 kA at 415 V AC, the E3N3200 provides robust protection for high-current distribution systems. This version features a four-pole fixed configuration with rear flat horizontal terminals, four auxiliary contacts and circuit-breaker open/closed position indication for permanent integration into low-voltage switchgear.
Air circuit breakers such as the ABB SACE Emax E3N3200 provide switching, isolation and overcurrent protection at critical points within high-current low-voltage distribution systems. The E3 frame accommodates substantial continuous currents, while the N performance level provides dependable short-circuit interruption and short-time withstand capability for industrial switchboards, transformer-fed networks and other high-capacity distribution applications.
The PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. Combined with the fixed Emax construction and 65 kA short-circuit performance, this configuration provides a robust solution for installations requiring high continuous-current capability, dependable fault interruption and straightforward electronic overcurrent protection.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB order code | 1SDA056152R1 |
| EAN | 8015644574925 |
| Customs tariff number | 85362090 |
| Product type | Air circuit breaker |
| Frame / size | E3 |
| Short-circuit performance level | N |
| Rated current (In) | 3200 A |
| Rated uninterrupted current (Iu) | 3200 A |
| Rated operational current (Ie) | 3200 A |
| Current type | AC |
| Number of poles | 4 |
| Installation | Fixed |
| Version | F |
| Terminal position | Rear |
| Terminal connection | Rear flat horizontal (HR) |
| Trip unit | PR121/P-LI R3200 |
| Release type | Electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Integrated earth-fault protection | No |
| Overload release adjustment range | 1280–3200 A |
| Instantaneous short-circuit release adjustment range | 4800–48000 A |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–690 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Motor drive | Optional |
| Degree of protection | IP2X |
| Mechanical durability | 20,000 operating cycles |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Electrical durability at ≤440 V | 6,000 operating cycles |
| Electrical durability at 500–690 V | 5,000 operating cycles |
| Maximum electrical operating frequency | 20 cycles per hour |
| Power loss | 330 W |
| Dimensions (W × H × D) | 530 × 418 × 302 mm |
| Net weight | 76 kg |
| Standard | IEC |
The ABB 1SDA056152R1 is an E3N3200 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems against overload and short-circuit conditions.
This circuit breaker has a rated uninterrupted current of 3200 A, making it suitable for high-current industrial, commercial and infrastructure power distribution applications.
The PR121/P-LI electronic overcurrent release provides long-time overload and instantaneous short-circuit protection. This LI configuration does not include short-time delayed or integrated earth-fault protection.
The E3N3200 has a rated ultimate and service short-circuit breaking capacity of 65 kA across the specified 220–690 V AC operating range, with a rated short-time withstand current of 65 kA for 1 s and 3 s.
The 1SDA056152R1 is a four-pole fixed air circuit breaker with rear flat horizontal terminals, designed for permanent installation within a suitable low-voltage switchboard or power distribution assembly.
ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high continuous-current capability, robust short-circuit performance and electronic overcurrent protection for industrial, commercial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.