ABB E3N3200PR122/P-LSI is a 3200 A three-pole fixed SACE Emax air circuit breaker with rear horizontal terminals and a PR122/P-LSI R3200 electronic trip unit providing long-time, short-time and instantaneous overcurrent protection.
£17,219.48
The ABB E3N3200PR122/P-LSI is a high-performance 3200 A three-pole air circuit breaker designed for reliable switching and overcurrent protection in demanding low-voltage power distribution systems. As part of the established ABB SACE Emax New Emax series, this E3N breaker combines a robust high-current frame with the advanced PR122/P-LSI electronic overcurrent release.
The PR122/P-LSI trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection. These LSI protection functions help safeguard cables, busbars, switchboards and connected electrical equipment against sustained overloads and short-circuit faults while supporting selective coordination within complex electrical distribution networks.
With a rated current of 3200 A, a three-pole fixed configuration and rear horizontal terminals, ABB order code 1SDA056148R1 is designed for integration into high-current low-voltage switchboards. The breaker is equipped with a PR122/P-LSI R3200 overcurrent release, four auxiliary contacts and open/closed circuit-breaker position indication for monitoring and control integration.
Air circuit breakers such as the ABB E3N3200 provide switching and overcurrent protection for high-current low-voltage distribution circuits. The electronic trip release monitors current conditions and initiates breaker operation when configured protection thresholds are exceeded, helping protect cables, busbars, switchboards and connected electrical equipment against damaging overload and short-circuit currents.
The PR122/P-LSI release combines long-time, short-time and instantaneous protection functions in an electronic trip system. Together with the E3N frame's 65 kA short-circuit performance, 3200 A current rating and fixed rear-horizontal-terminal construction, this makes the breaker well suited to critical main distribution and high-current feeder applications.
| Series | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA056148R1 |
| Extended product type | E3N3200PR122/P-LSIIn=3200A3pFHR |
| Product type | Air circuit breaker |
| Frame | E3N |
| Short-circuit performance level | N |
| Rated current | 3200 A |
| Rated operational current | 3200 A |
| Rated uninterrupted current | 3200 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Rated ultimate short-circuit breaking capacity | 65 kA |
| Rated service short-circuit breaking capacity | 65 kA |
| Rated short-time withstand current | 65 kA for 1 s / 3 s |
| Execution | Fixed |
| Terminal arrangement | Rear horizontal terminals (HR) |
| Trip unit | PR122/P-LSI |
| Release type | Electronic |
| Overcurrent release rating | R3200 |
| Protection functions | L, S and I |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 330 W |
| Electrical durability | 6000 cycles at Ue ≤ 440 V; 5000 cycles at Ue 500–690 V |
| Maximum electrical operating frequency | 20 cycles per hour |
| Mechanical durability | 20,000 cycles |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 404 × 418 × 302 mm |
| Net weight | 60 kg |
| EAN | 8015644574888 |
| Customs tariff number | 85362090 |
| Standard | IEC |
It is a 3200 A three-pole air circuit breaker designed for switching and protecting high-current low-voltage AC power distribution circuits.
The PR122/P-LSI electronic trip unit provides long-time overload (L), short-time short-circuit (S) and instantaneous short-circuit (I) protection.
The E3N3200 has a rated ultimate and service short-circuit breaking capacity of 65 kA across its specified operating-voltage range up to 690 V AC.
ABB order code 1SDA056148R1 is a fixed three-pole circuit breaker equipped with rear horizontal terminals.
The breaker uses rear horizontal terminals and is fitted with four auxiliary contacts together with circuit-breaker open/closed position indication.
ABB SACE Emax air circuit breakers are widely used in industrial and commercial low-voltage distribution systems, combining robust high-current switching technology with configurable electronic protection for dependable operation in demanding electrical installations.