ABB 1SDA056137R1 SACE Emax E3N2500 four-pole withdrawable air circuit breaker moving part with a 2500 A rating, PR121/P-LSI electronic protection and 65 kA breaking capacity for demanding low-voltage power distribution.
£19,632.66
The ABB 1SDA056137R1 is a high-performance SACE Emax E3N air circuit breaker (ACB) moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product group, this four-pole withdrawable circuit breaker combines a 2500 A rated uninterrupted current with the PR121/P-LSI R2500 electronic overcurrent release for dependable protection of industrial, commercial and infrastructure power networks.
The E3N2500 provides long-time, short-time and instantaneous protection through its LSI trip functionality. The PR121/P electronic release provides overload, delayed short-circuit and instantaneous short-circuit protection, supporting effective coordination and selectivity between protective devices. As an LSI configuration, this breaker does not include integrated earth-fault protection.
With a rated uninterrupted current of 2500 A, a 690 V AC rated operational voltage and an ultimate short-circuit breaking capacity of 65 kA at 415 V AC, the E3N2500 provides robust protection for high-current distribution systems. This version is a four-pole withdrawable moving part, allowing removal from a compatible ABB SACE Emax fixed part for inspection, testing, servicing or replacement.
Air circuit breakers such as the ABB SACE Emax E3N2500 provide switching, isolation and overcurrent protection at critical points within high-current low-voltage distribution systems. The E3 frame accommodates substantial continuous currents, while the N performance level provides dependable short-circuit interruption and short-time withstand capability for industrial switchboards, transformer-fed networks and other high-capacity distribution applications.
The PR121/P-LSI electronic trip unit provides long-time overload, short-time overcurrent and instantaneous short-circuit protection. Combined with the withdrawable Emax construction and 65 kA short-circuit performance, this configuration provides dependable electrical protection while allowing the circuit-breaker moving part to be removed from compatible switchgear for inspection, testing, maintenance or replacement.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB order code | 1SDA056137R1 |
| EAN | 8015644574772 |
| Customs tariff number | 85362090 |
| Product type | Air circuit breaker moving part |
| Frame / size | E3 |
| Short-circuit performance level | N |
| Rated current (In) | 2500 A |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated operational current (Ie) | 2500 A |
| Current type | AC |
| Number of poles | 4 |
| Version | Withdrawable moving part (W MP) |
| Trip unit | PR121/P-LSI R2500 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Integrated earth-fault protection | No |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–690 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open/closed |
| Mechanical durability | 20,000 operating cycles |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Electrical durability at ≤440 V | 8,000 operating cycles |
| Electrical durability at 500–690 V | 7,000 operating cycles |
| Maximum electrical operating frequency | 20 cycles per hour |
| Power loss | 350 W |
| Dimensions (W × H × D) | 558 × 461 × 396.5 mm |
| Net weight | 81 kg |
| Standard | IEC |
The ABB 1SDA056137R1 is an E3N2500 withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems against overload and short-circuit conditions.
This circuit breaker has a rated uninterrupted current of 2500 A, making it suitable for high-current industrial, commercial and infrastructure power distribution applications.
The PR121/P-LSI electronic overcurrent release provides long-time overload, short-time overcurrent and instantaneous short-circuit protection. This LSI configuration does not include integrated earth-fault protection.
The E3N2500 has a rated ultimate and service short-circuit breaking capacity of 65 kA across the specified 220–690 V AC operating range, with a rated short-time withstand current of 65 kA for 1 s and 3 s.
The 1SDA056137R1 is a four-pole withdrawable circuit breaker moving part designed for use with a compatible ABB SACE Emax fixed part. The moving part and matching fixed part together form the complete withdrawable circuit-breaker assembly.
ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high continuous-current capability, robust short-circuit performance and service-friendly withdrawable construction for industrial, commercial and infrastructure applications.