ABB 1SDA056124R1 E3N2500 four-pole fixed air circuit breaker rated at 2500 A with rear horizontal terminals and a PR122/P-LSI R2500 electronic release providing long-time, short-time and instantaneous overcurrent protection.
£17,502.19
The ABB E3N2500 PR122/P-LSI, order code 1SDA056124R1, is a four-pole fixed air circuit breaker (ACB) designed for high-current low-voltage power distribution and protection. Part of the ABB SACE Emax E3 series, it combines a rated uninterrupted current of 2500 A with the advanced PR122/P-LSI R2500 electronic overcurrent release.
The PR122/P-LSI release provides long-time, short-time and instantaneous protection, helping protect conductors, switchgear and connected equipment against sustained overloads and short-circuit conditions. Its adjustable electronic protection functions support selective coordination and dependable fault clearing in industrial, commercial and infrastructure electrical distribution systems.
This E3N2500 configuration uses fixed construction with rear flat horizontal terminals and is fitted with four change-over auxiliary contacts plus circuit-breaker open/closed position indication. With a rated operational voltage of 690 V AC and rated ultimate and service short-circuit breaking capacities of 65 kA, it provides robust protection for high-capacity switchboards and distribution networks.
The ABB SACE Emax E3N2500 is engineered for high-capacity low-voltage distribution systems requiring dependable switching, isolation and fault protection. Its 2500 A current rating, 65 kA short-circuit breaking capability and fixed rear-horizontal-terminal arrangement make it well suited to main switchboards, transformer-fed networks and large industrial distribution systems.
The PR122/P-LSI electronic release combines long-time overload protection, short-time protection for selective fault coordination and instantaneous protection against severe short circuits. Together with four change-over auxiliary contacts, open/closed position indication and a 65 kA short-time withstand capability, the E3N2500 provides robust protection and practical integration into critical low-voltage switchgear.
| Series | SACE Emax E3 |
|---|---|
| ABB order code | 1SDA056124R1 |
| Product type | Air circuit breaker |
| Frame / performance level | E3N |
| Number of poles | 4 |
| Rated current (In) | 2500 A |
| Rated uninterrupted current (Iu) | 2500 A |
| Rated operational current (Ie) | 2500 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | PR122/P-LSI R2500 |
| Release type | Electronic |
| Protection functions | LSI – Long-time, Short-time and Instantaneous |
| Instantaneous short-circuit release adjustment | 3750–37500 A |
| Short-time delayed short-circuit release setting | 1500 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 440 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 65 kA |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Integrated ground-fault protection | No |
| Power loss | 205 W |
| Mechanical durability | 20,000 cycles |
| Standard | IEC |
| Net weight | 90 kg |
| EAN | 8015644574642 |
| HS code | 85362090 |
The ABB 1SDA056124R1 is a four-pole fixed SACE Emax E3N2500 air circuit breaker rated at 2500 A, equipped with rear horizontal terminals and a PR122/P-LSI R2500 electronic overcurrent release.
The PR122/P-LSI provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The E3N2500 has a rated uninterrupted current of 2500 A and uses a four-pole configuration.
ABB 1SDA056124R1 is a fixed air circuit breaker with rear flat horizontal main terminals for integration into suitable low-voltage switchgear.
This E3N2500 configuration provides rated ultimate and service short-circuit breaking capacities of 65 kA, including at 400/415 V AC and 690 V AC.
ABB SACE Emax air circuit breakers combine advanced electronic protection, robust short-circuit performance and practical switchgear integration to provide dependable switching and protection for high-current low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.