Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056108R1 E2L1600 four-pole withdrawable air circuit breaker moving part rated at 1600 A with a PR122/P-LSI R1600 electronic release providing long-time, short-time and instantaneous overcurrent protection.
£13,664.84
The ABB E2L1600 PR122/P-LSI, order code 1SDA056108R1, is a high-performance four-pole withdrawable air circuit breaker moving part designed for demanding low-voltage power distribution systems. Part of the ABB SACE Emax E2 series, it combines a rated current of 1600 A with the advanced PR122/P-LSI R1600 electronic overcurrent release.
The PR122/P-LSI release provides long-time, short-time and instantaneous protection, helping protect conductors, switchgear and connected equipment against sustained overloads and short-circuit conditions. Adjustable electronic protection settings support effective selectivity and coordination within industrial, commercial and infrastructure electrical distribution networks.
This version is supplied as the moving part of a withdrawable E2L1600 circuit breaker and is intended for use with the appropriate ABB SACE Emax fixed part. It features four auxiliary contacts and circuit-breaker open/closed position indication, while the E2L performance level provides an ultimate short-circuit breaking capacity of 130 kA at 400/415 V AC for demanding high-fault-level installations.
The ABB SACE Emax E2L1600 is designed for low-voltage installations where substantial prospective short-circuit currents require high interruption performance. Its E2L execution provides an ultimate and service short-circuit breaking capacity of 130 kA at 400/415 V AC, making it particularly suitable for main distribution boards, transformer-fed systems and demanding industrial switchgear.
The PR122/P-LSI electronic release combines long-time overload protection, short-time protection for selective fault coordination and instantaneous protection against severe short circuits. Together with the withdrawable moving-part design, four auxiliary contacts and open/closed position indication, the E2L1600 provides robust protection and practical serviceability in compatible ABB SACE Emax switchgear.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA056108R1 |
| Product type | Air circuit breaker moving part |
| Frame / performance level | E2L |
| Number of poles | 4 |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | PR122/P-LSI R1600 |
| Release type | Electronic |
| Protection functions | LSI – Long-time, Short-time and Instantaneous |
| Overload release current setting | 640–1600 A |
| Short-time delayed short-circuit release setting | 960 A |
| Instantaneous short-circuit release adjustment range | 2400–24000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 130 kA |
| Service short-circuit breaking capacity (Ics) at 400/415 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 110 kA |
| Service short-circuit breaking capacity (Ics) at 440 V AC | 110 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 10 kA |
| Installation | Withdrawable |
| Component | Moving part |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Integrated earth-fault protection | No |
| Motor operating mechanism | Optional |
| Electrical durability at ≤440 V | 3,000 cycles |
| Electrical durability at 500–690 V | 2,000 cycles |
| Mechanical durability | 20,000 cycles |
| Power loss | 265 W |
| Product dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Net weight | 61 kg |
| Standard | IEC |
| EAN | 8015644574482 |
| Customs tariff number | 85362090 |
The ABB 1SDA056108R1 is the moving part of a four-pole SACE Emax E2L1600 withdrawable air circuit breaker rated at 1600 A and fitted with a PR122/P-LSI R1600 electronic overcurrent release.
The PR122/P-LSI provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The E2L1600 moving part has a rated uninterrupted current of 1600 A and uses a four-pole configuration.
ABB 1SDA056108R1 is the moving part of a withdrawable air circuit breaker and is designed for use with the appropriate ABB SACE Emax fixed part.
This E2L1600 configuration provides an ultimate short-circuit breaking capacity of 130 kA at 400/415 V AC, 110 kA at 440 V AC and 85 kA at 690 V AC.
ABB SACE Emax air circuit breakers combine advanced electronic protection, high short-circuit performance and serviceable withdrawable construction to provide dependable switching and protection for demanding low-voltage power distribution systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.