ABB E2L1600 1SDA056098R1 is a 1600 A three-pole withdrawable SACE Emax air circuit breaker moving part with a PR121/P-LSIG electronic trip unit for overload, short-circuit and earth-fault protection.
£10,801.21
The ABB E2L1600 1SDA056098R1 is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for protection and switching in demanding high-current low-voltage electrical distribution systems. Part of the proven ABB SACE Emax E2 series, this three-pole withdrawable breaker combines a 1600 A rated current with the PR121/P-LSIG electronic trip unit for comprehensive overload, short-time, instantaneous and earth-fault protection.
Designed for industrial, infrastructure and commercial power distribution applications, the E2L1600 provides exceptionally high short-circuit interruption performance. The PR121/P-LSIG electronic overcurrent release provides L, S, I and G protection functions, supporting selective coordination while helping protect conductors, busbars and connected equipment against sustained overloads, short circuits and earth faults.
This model is a three-pole withdrawable moving part rated for operation up to 690 V AC. The E2L performance level provides a rated ultimate short-circuit breaking capacity of 130 kA at 415 V AC, while its withdrawable construction supports convenient inspection, servicing and replacement when installed with the corresponding SACE Emax E2 fixed part.
The ABB E2L1600 is engineered for low-voltage installations where exceptionally high prospective short-circuit currents require substantial interruption capability. With an ultimate breaking capacity of 130 kA at 415 V AC, this E2L configuration is well suited to main switchboards, transformer-fed distribution systems and industrial networks located close to high-capacity power sources.
The PR121/P-LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the withdrawable SACE Emax platform, this configuration provides comprehensive high-current protection while allowing the breaker moving part to be withdrawn from its compatible fixed part for inspection, servicing or replacement.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA056098R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Number of poles | 3 |
| Execution | Withdrawable moving part |
| Trip unit | PR121/P-LSIG electronic overcurrent release |
| Protection functions | L, S, I, G |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate breaking capacity (Icu) at 400 V AC | 130 kA |
| Rated service breaking capacity (Ics) at 400 V AC | 130 kA |
| Rated ultimate breaking capacity (Icu) at 415 V AC | 130 kA |
| Rated service breaking capacity (Ics) at 415 V AC | 130 kA |
| Rated ultimate breaking capacity (Icu) at 440 V AC | 110 kA |
| Rated service breaking capacity (Ics) at 440 V AC | 110 kA |
| Rated ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Rated service breaking capacity (Ics) at 500 V AC | 65 kA |
| Rated ultimate breaking capacity (Icu) at 690 V AC | 85 kA |
| Rated service breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 10 kA |
| Short-circuit performance level | L |
| Current type | AC |
| Power loss | 265 W |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Product net weight | 59 kg |
| EAN | 8015644574383 |
| Customs tariff / HS code | 85362090 |
| Standard | IEC |
It is a 1600 A air circuit breaker moving part designed for switching and comprehensive protection of demanding high-current low-voltage electrical distribution systems.
This circuit breaker is equipped with an ABB PR121/P-LSIG electronic overcurrent release.
The LSIG configuration provides long-time overload, short-time, instantaneous short-circuit and earth-fault protection.
The E2L1600 provides a rated ultimate short-circuit breaking capacity of 130 kA at 415 V AC and 85 kA at 690 V AC.
This model is a three-pole withdrawable moving part designed for use with the corresponding SACE Emax E2 fixed part.
ABB SACE Emax air circuit breakers are engineered for dependable protection and control of low-voltage power distribution systems, combining exceptionally high breaking performance, comprehensive electronic protection and maintainable withdrawable construction for demanding industrial, commercial and infrastructure installations.