Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056092R1 E2L1600 four-pole fixed air circuit breaker rated at 1600 A with rear horizontal terminals and a PR122/P-LSI R1600 electronic release providing long-time, short-time and instantaneous overcurrent protection.
£11,554.11
The ABB E2L1600 PR122/P-LSI, order code 1SDA056092R1, is a high-performance four-pole fixed air circuit breaker (ACB) designed for switching and protection in demanding low-voltage power distribution systems. Part of the ABB SACE Emax E2 series, it combines a rated uninterrupted current of 1600 A with the advanced PR122/P-LSI R1600 electronic overcurrent release.
The PR122/P-LSI release provides long-time, short-time and instantaneous protection, helping safeguard conductors, switchgear and connected equipment against sustained overloads and short-circuit conditions. Its adjustable electronic protection functions support selective coordination in industrial, commercial and infrastructure electrical distribution networks.
This E2L1600 version uses fixed construction with rear flat horizontal terminals and is fitted with four change-over auxiliary contacts plus circuit-breaker open/closed position indication. With a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 130 kA at 400/415 V AC, it is engineered for switchboards with particularly demanding prospective fault levels.
The ABB SACE Emax E2L1600 is designed for low-voltage installations where substantial prospective short-circuit currents require high interruption performance. Its E2L execution provides an ultimate and service short-circuit breaking capacity of 130 kA at 400/415 V AC, making it particularly suitable for main distribution boards, transformer-fed systems and demanding industrial switchgear.
The PR122/P-LSI electronic release combines long-time overload protection, short-time protection for selective fault coordination and instantaneous protection against severe short circuits. Together with fixed rear-horizontal-terminal construction, four auxiliary change-over contacts and open/closed position indication, the E2L1600 provides robust protection and practical integration into suitably designed ABB Emax switchgear.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA056092R1 |
| Product type | Air circuit breaker |
| Frame / performance level | E2L |
| Number of poles | 4 |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | PR122/P-LSI R1600 |
| Release type | Electronic |
| Protection functions | LSI – Long-time, Short-time and Instantaneous |
| Overload release current setting | 640–1600 A |
| Instantaneous short-circuit release adjustment range | 2400–24000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 130 kA |
| Service short-circuit breaking capacity (Ics) at 400/415 V AC | 130 kA |
| Ultimate short-circuit breaking capacity (Icu) at 440 V AC | 110 kA |
| Service short-circuit breaking capacity (Ics) at 440 V AC | 110 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 10 kA |
| Installation | Fixed |
| Terminal arrangement | Rear flat horizontal |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Integrated earth-fault protection | No |
| Motor operating mechanism | Optional |
| Electrical durability at ≤440 V | 3,000 cycles |
| Electrical durability at 500–690 V | 2,000 cycles |
| Mechanical durability | 20,000 cycles |
| Power loss | 170 W |
| Standard | IEC |
| Net weight | 68 kg |
| EAN | 8015644574321 |
The ABB 1SDA056092R1 is a four-pole fixed SACE Emax E2L1600 air circuit breaker rated at 1600 A, equipped with rear horizontal terminals and a PR122/P-LSI R1600 electronic overcurrent release.
The PR122/P-LSI provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.
The E2L1600 has a rated uninterrupted current of 1600 A and uses a four-pole configuration.
ABB 1SDA056092R1 is a fixed air circuit breaker with rear flat horizontal main terminals for integration into suitable low-voltage switchgear.
This E2L1600 configuration provides an ultimate short-circuit breaking capacity of 130 kA at 400/415 V AC, 110 kA at 440 V AC and 85 kA at 690 V AC.
ABB SACE Emax air circuit breakers combine advanced electronic protection, high short-circuit performance and robust switchgear integration to provide dependable switching and protection for demanding low-voltage power distribution systems.
We use cookies