ABB 1SDA056080R1 is a SACE Emax E2L1600 three-pole fixed air circuit breaker rated at 1600 A with rear flat horizontal terminals and a PR121/P-LI electronic release for long-time overload and instantaneous short-circuit protection.
£8,350.62
The ABB 1SDA056080R1 is a high-performance SACE Emax E2L1600 air circuit breaker designed for reliable switching and protection in demanding low-voltage electrical distribution systems. As part of the ABB New Emax product range, this three-pole fixed circuit breaker has a rated uninterrupted current of 1600 A and incorporates the PR121/P-LI electronic overcurrent release.
The PR121/P-LI trip unit provides long-time overload and instantaneous short-circuit protection, helping safeguard electrical installations, conductors and connected equipment against damaging overcurrents. The E2L performance class provides particularly high short-circuit interruption capability, including an ultimate short-circuit breaking capacity of 130 kA at 220–415 V AC.
With a rated operational voltage of up to 690 V AC, three-pole configuration and fixed construction with rear flat horizontal terminals, the E2L1600 is well suited to high-current switchboards and main distribution panels. Its combination of a 1600 A current rating, electronic LI protection and high fault-interruption performance makes it suitable for demanding industrial, commercial and infrastructure power distribution applications.
Air circuit breakers such as the ABB SACE Emax E2L1600 provide dependable switching and protection for high-current low-voltage distribution circuits. The E2L performance class is engineered for installations with demanding prospective fault levels, providing an ultimate breaking capacity of up to 130 kA at common low-voltage distribution voltages and helping protect switchboards, conductors, transformers and connected electrical equipment.
The PR121/P-LI electronic release combines long-time overload protection with instantaneous short-circuit protection. Together with the fixed three-pole E2L1600 platform and rear flat horizontal terminal arrangement, these functions make the 1SDA056080R1 well suited to main distribution and feeder applications requiring high current capacity, substantial fault-interruption performance and dependable electronic protection.
| Product group | 310513-New Emax |
|---|---|
| Series | SACE Emax |
| Order code / MPN | 1SDA056080R1 |
| Product type | Air circuit breaker |
| Frame / sub-type | E2 |
| Short-circuit performance level | L |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Number of poles | 3 |
| Release | PR121/P-LI |
| Release type | Electronic |
| Protection functions | LI |
| Long-time protection (L) | Overload protection |
| Instantaneous protection (I) | Short-circuit protection |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated voltage (Ur) | 690 V |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–415 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 110 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–415 V AC | 130 kA |
| Rated service short-circuit breaking capacity (Ics) at 440 V AC | 110 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 65 kA |
| Rated short-time withstand current (Icw) | 10 kA for 1 s |
| Version | Fixed |
| Terminal connection | Rear flat horizontal |
| Power loss | 170 W |
| Mechanical durability | 20,000 operating cycles |
| Electrical durability at ≤440 V | 3,000 operating cycles |
| Electrical durability at 500–690 V | 2,000 operating cycles |
| Maximum electrical operating frequency | 20 cycles per hour |
| Maximum mechanical operating frequency | 60 cycles per hour |
| Dimensions (W × H × D) | 296 × 418 × 302 mm |
| Net weight | 45 kg |
| Standard | IEC |
| EAN | 8015644574208 |
| Customs tariff number | 85362090 |
The ABB 1SDA056080R1 is an E2L1600 SACE Emax air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution circuits.
The circuit breaker has a rated uninterrupted current of 1600 A.
The PR121/P-LI electronic release provides long-time overload protection and instantaneous short-circuit protection.
The breaker provides an Icu and Ics of 130 kA at 220–415 V AC and 110 kA at 440 V AC. Its Icu at 500–690 V AC is 85 kA, with an Ics of 65 kA.
The 1SDA056080R1 is a three-pole fixed air circuit breaker with rear flat horizontal terminals for installation in compatible low-voltage switchboard assemblies.
ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, electronic protection and robust construction for industrial electrical installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.