Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056075R1 is a SACE Emax E2L 1250 A four-pole withdrawable air circuit breaker moving part with a PR122/P-LI R1250 electronic overcurrent release providing long-time overload and instantaneous short-circuit protection.
£10,660.96
The ABB 1SDA056075R1 is a high-performance SACE Emax E2L 1250 air circuit breaker moving part designed for reliable switching and electronic overcurrent protection in demanding low-voltage electrical distribution systems. This four-pole withdrawable circuit breaker moving part is equipped with the PR122/P-LI R1250 electronic overcurrent release and has a rated uninterrupted current of 1250 A.
The E2L performance level is engineered for installations with high prospective short-circuit currents. The breaker is rated for operation up to 690 V AC and provides an ultimate short-circuit breaking capacity of 130 kA at 220–415 V AC, 110 kA at 440 V AC and 85 kA at 500–690 V AC. The PR122/P-LI release provides long-time overload and instantaneous short-circuit protection.
This version is supplied as a four-pole withdrawable moving part (W MP) for use with a compatible SACE Emax fixed part. It incorporates four auxiliary contacts and open/closed circuit-breaker position indication, combining high fault-clearing performance with a withdrawable design that supports inspection, servicing and replacement within compatible switchgear.
ABB SACE Emax E2L air circuit breakers are designed for low-voltage installations where high prospective short-circuit currents require substantial interruption capability. The E2L 1250 combines a 1250 A continuous-current rating with up to 130 kA ultimate breaking capacity, making it suitable for demanding main distribution, industrial and infrastructure switchgear applications.
The PR122/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. Combined with the four-pole withdrawable construction, the 1SDA056075R1 provides dependable electronic overcurrent protection while allowing the circuit breaker moving part to be withdrawn from its compatible fixed portion for inspection, maintenance or replacement.
| Product family | SACE Emax |
|---|---|
| Series | E2L |
| ABB order code | 1SDA056075R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 4 |
| Execution | Withdrawable moving part (W MP) |
| Trip unit | PR122/P-LI R1250 |
| Release type | Electronic overcurrent release |
| Protection functions | LI – long-time overload and instantaneous short-circuit protection |
| Short-circuit performance level | L |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–415 V AC | 130 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 110 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–415 V AC | 130 kA |
| Rated service short-circuit breaking capacity (Ics) at 440 V AC | 110 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 10 kA |
| Power loss | 165 W |
| Electrical durability at ≤440 V | 4000 cycles |
| Electrical durability at 500–690 V | 3000 cycles |
| Mechanical durability | 20000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Net weight | 61 kg |
| EAN | 8015644574154 |
The ABB 1SDA056075R1 is a 1250 A four-pole withdrawable air circuit breaker moving part designed for switching and electronic overcurrent protection in demanding low-voltage electrical distribution systems, particularly where high short-circuit interruption capability is required.
The ABB 1SDA056075R1 has a rated uninterrupted current of 1250 A and a rated operational voltage of up to 690 V AC.
The PR122/P-LI electronic trip unit provides LI protection consisting of long-time overload protection and instantaneous short-circuit protection.
The E2L 1250 provides a rated ultimate short-circuit breaking capacity of 130 kA at 220–415 V AC, 110 kA at 440 V AC and 85 kA at 500–690 V AC.
The ABB 1SDA056075R1 is a four-pole withdrawable moving part (W MP) designed for use with a compatible SACE Emax withdrawable fixed part.
ABB SACE Emax air circuit breakers are engineered to provide dependable switching and advanced electronic protection in demanding low-voltage power distribution systems, with the E2L range providing particularly high short-circuit breaking performance for critical industrial, commercial and infrastructure installations.
We use cookies