1SDA056074R1 ABB E2L 1250 PR121/P-LSIG 1250 A 4-Pole Withdrawable Air Circuit Breaker

1SDA056074R1 ABB E2L 1250 PR121/P-LSIG 1250 A 4-Pole Withdrawable Air Circuit Breaker

ABB 1SDA056074R1 is a SACE Emax E2L 1250 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LSIG R1250 electronic overcurrent release providing comprehensive long-time, short-time, instantaneous and earth-fault protection.

SKU: 1SDA056074R1MPN: 1SDA056074R1
Price
List Price £16,034.83 ex VAT
Your Price (ex VAT) Save 25%
£12,026.12 25% OFF
You save £4,008.71 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £12,026.12
Trade pricing is personalised to your account

Manufacturer Lead Time

£12,026.12

Why Choose the ABB E2L 1250 PR121/P-LSIG 1SDA056074R1 Air Circuit Breaker?

The ABB 1SDA056074R1 is a high-performance SACE Emax E2L 1250 air circuit breaker moving part designed for switching and comprehensive protection in demanding low-voltage electrical distribution systems. This four-pole withdrawable circuit breaker moving part is equipped with the PR121/P-LSIG R1250 electronic overcurrent release, combining a 1250 A continuous-current rating with advanced electronic fault protection.

The E2L performance level is designed for installations with particularly high prospective short-circuit currents. The breaker is rated for operation up to 690 V AC and provides an ultimate short-circuit breaking capacity of 130 kA at 220–415 V AC, 110 kA at 440 V AC and 85 kA at 500–690 V AC. Its PR121/P-LSIG release provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.

This version is supplied as a four-pole withdrawable moving part (W MP) for use with a compatible SACE Emax fixed part. It is fitted with four auxiliary contacts and circuit-breaker open/closed position indication, combining high fault-clearing performance with convenient servicing and maintenance for critical electrical distribution systems.

Key Advantages

  • High-performance 1250 A air circuit breaker moving part for demanding low-voltage distribution.
  • Four-pole configuration suitable for systems requiring phase and neutral switching.
  • Exceptional 130 kA Icu at 220–415 V AC.
  • Advanced PR121/P-LSIG R1250 electronic overcurrent release.
  • Comprehensive LSIG protection against overload, short-time, instantaneous and earth-fault conditions.
  • Withdrawable moving-part construction supports convenient inspection, servicing and replacement.
  • Part of the high-breaking-capacity ABB SACE Emax E2L air circuit breaker range.

Key Features

  • ABB SACE Emax E2L 1250 series.
  • 1250 A rated uninterrupted current.
  • Four-pole configuration.
  • Withdrawable moving-part execution.
  • PR121/P-LSIG R1250 electronic trip unit.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • Integrated earth-fault protection.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Four auxiliary contacts with open/closed circuit-breaker position indication.

High-Breaking-Capacity LSIG Protection for Power Distribution

ABB SACE Emax E2L air circuit breakers are engineered for low-voltage installations where high prospective short-circuit currents require substantial interruption capability. The E2L 1250 combines a 1250 A continuous-current rating with up to 130 kA ultimate breaking capacity, making it particularly suitable for demanding main distribution, industrial and infrastructure switchgear applications.

The PR121/P-LSIG electronic trip unit provides four principal protection functions: long-time overload protection, short-time delayed short-circuit protection, instantaneous short-circuit protection and earth-fault protection. Combined with its withdrawable construction, the 1SDA056074R1 provides comprehensive fault protection while allowing the moving part to be withdrawn from its compatible fixed portion for inspection, maintenance or replacement.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems with high prospective fault currents.
  • Transformer secondary protection and distribution.
  • Generator and utility distribution systems.
  • Manufacturing and process plant switchgear.
  • Commercial and infrastructure electrical distribution.
  • Four-pole installations requiring withdrawable construction and earth-fault protection.

Technical Specifications

Product family SACE Emax
Series E2L
ABB order code 1SDA056074R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Rated uninterrupted current (Iu) 1250 A
Rated operational current (Ie) 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Current type AC
Number of poles 4
Execution Withdrawable moving part (W MP)
Trip unit PR121/P-LSIG R1250
Release type Electronic overcurrent release
Protection functions LSIG – long-time overload, short-time delayed, instantaneous short-circuit and earth-fault protection
Short-circuit performance level L
Rated ultimate short-circuit breaking capacity (Icu) at 220–415 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 110 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 220–415 V AC 130 kA
Rated service short-circuit breaking capacity (Ics) at 440 V AC 110 kA
Rated service short-circuit breaking capacity (Ics) at 500–690 V AC 65 kA
Rated short-time withstand current (Icw), 1 s 10 kA
Power loss 165 W
Electrical durability at ≤440 V 4000 cycles
Electrical durability at 500–690 V 3000 cycles
Mechanical durability 20000 cycles
Auxiliary contacts 4
Position indication Open / closed
Dimensions (W × H × D) 414 × 461 × 396.5 mm
Net weight 61 kg
EAN 8015644574147

Frequently Asked Questions

What is the ABB 1SDA056074R1 used for?

The ABB 1SDA056074R1 is a 1250 A four-pole withdrawable air circuit breaker moving part designed for switching and comprehensive electronic protection in demanding low-voltage electrical distribution systems, particularly where high short-circuit interruption capability is required.

What is the current rating of the ABB E2L 1250 1SDA056074R1?

The ABB 1SDA056074R1 has a rated uninterrupted current of 1250 A and a rated operational voltage of up to 690 V AC.

What protection does the PR121/P-LSIG trip unit provide?

The PR121/P-LSIG electronic trip unit provides LSIG protection consisting of long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection.

What is the short-circuit breaking capacity of the ABB E2L 1250?

The E2L 1250 provides a rated ultimate short-circuit breaking capacity of 130 kA at 220–415 V AC, 110 kA at 440 V AC and 85 kA at 500–690 V AC.

Is the ABB 1SDA056074R1 fixed or withdrawable?

The ABB 1SDA056074R1 is a four-pole withdrawable moving part (W MP) designed for use with a compatible SACE Emax withdrawable fixed part.

Trusted for High-Performance Industrial Power Distribution

ABB SACE Emax air circuit breakers are engineered to provide dependable switching and advanced electronic protection in demanding low-voltage power distribution systems, with the E2L range providing particularly high short-circuit breaking performance for critical industrial, commercial and infrastructure installations.