Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB E2L1250 1SDA056068R1 is a 1250 A three-pole withdrawable SACE Emax air circuit breaker moving part with a PR122/P-LSI electronic trip unit for overload and short-circuit protection.
£9,086.68
The ABB E2L1250 1SDA056068R1 is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for protection and switching in demanding high-current low-voltage electrical distribution systems. Part of the proven ABB SACE Emax E2 series, this three-pole withdrawable breaker combines a 1250 A rated current with the advanced PR122/P-LSI electronic trip unit for dependable overload, short-time and instantaneous short-circuit protection.
Designed for industrial, infrastructure and commercial power distribution applications, the E2L1250 provides exceptionally high short-circuit interruption performance. The PR122/P-LSI electronic overcurrent release provides L, S and I protection functions, supporting selective coordination while helping protect conductors, busbars and connected equipment against sustained overloads and short-circuit currents.
This model is a three-pole withdrawable moving part rated for operation up to 690 V AC. The E2L performance level provides a rated ultimate short-circuit breaking capacity of 130 kA at 415 V AC, while its withdrawable construction supports convenient inspection, servicing and replacement when used with the corresponding SACE Emax E2 fixed part.
The ABB E2L1250 is engineered for low-voltage installations where exceptionally high prospective short-circuit currents require substantial interruption capability. With an ultimate breaking capacity of 130 kA at 415 V AC, this E2L configuration is well suited to main switchboards, transformer-fed distribution systems and industrial networks located close to high-capacity power sources.
The PR122/P-LSI electronic trip unit provides long-time protection against sustained overloads, short-time delayed protection for selective short-circuit coordination and instantaneous protection against severe fault currents. Combined with the withdrawable SACE Emax platform, this configuration provides dependable high-current protection while allowing the breaker moving part to be withdrawn from its compatible fixed part for servicing or replacement.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA056068R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Number of poles | 3 |
| Execution | Withdrawable moving part |
| Trip unit | PR122/P-LSI electronic release |
| Protection functions | L, S, I |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate breaking capacity (Icu) at 415 V AC | 130 kA |
| Rated service breaking capacity (Ics) at 415 V AC | 130 kA |
| Rated ultimate breaking capacity (Icu) at 440 V AC | 110 kA |
| Rated service breaking capacity (Ics) at 440 V AC | 110 kA |
| Rated ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Rated service breaking capacity (Ics) at 500 V AC | 65 kA |
| Rated ultimate breaking capacity (Icu) at 690 V AC | 85 kA |
| Rated service breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 10 kA |
| Short-circuit performance level | L |
| Current type | AC |
| Power loss | 165 W |
| Electrical durability at ≤440 V | 4,000 cycles |
| Electrical durability at 500–690 V | 3,000 cycles |
| Mechanical durability | 20,000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Product dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Product net weight | 49 kg |
| EAN | 8015644574086 |
| Customs tariff number | 85362090 |
| Standard | IEC |
It is a 1250 A air circuit breaker moving part designed for switching and protection of demanding low-voltage electrical distribution systems.
This circuit breaker is equipped with an ABB PR122/P-LSI electronic overcurrent release.
The LSI configuration provides long-time overload, short-time and instantaneous short-circuit protection.
The E2L1250 provides a rated ultimate short-circuit breaking capacity of 130 kA at 415 V AC.
This model is a three-pole withdrawable moving part designed for use with the corresponding SACE Emax E2 fixed part.
ABB SACE Emax air circuit breakers are engineered for dependable protection and control of low-voltage power distribution systems, combining exceptionally high breaking performance, advanced electronic protection and maintainable withdrawable construction for demanding industrial, commercial and infrastructure installations.