1SDA056060R1 ABB E2L 1250 PR122/P-LSI 1250 A 4-Pole Fixed Air Circuit Breaker

1SDA056060R1 ABB E2L 1250 PR122/P-LSI 1250 A 4-Pole Fixed Air Circuit Breaker

ABB 1SDA056060R1 is a SACE Emax E2L 1250 A four-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LSI R1250 electronic overcurrent release providing long-time overload, short-time delayed and instantaneous short-circuit protection.

SKU: 1SDA056060R1MPN: 1SDA056060R1
Price
List Price £14,792.28 ex VAT
Your Price (ex VAT) Save 25%
£11,094.21 25% OFF
You save £3,698.07 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,094.21
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,094.21

Why Choose the ABB E2L 1250 PR122/P-LSI 1SDA056060R1 Air Circuit Breaker?

The ABB 1SDA056060R1 is a high-performance SACE Emax E2L 1250 air circuit breaker (ACB) designed for reliable switching, isolation and overcurrent protection in demanding low-voltage electrical distribution systems. This four-pole fixed circuit breaker is equipped with the PR122/P-LSI R1250 electronic overcurrent release, combining a 1250 A continuous-current rating with advanced electronic protection.

The E2L performance level is engineered for installations requiring particularly high short-circuit interruption capability. At 400–415 V AC, the breaker provides a rated ultimate short-circuit breaking capacity of 130 kA, while its rated operational voltage extends to 690 V AC. The PR122/P-LSI release provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.

This version is supplied as a four-pole fixed circuit breaker with rear horizontal terminals, making it suitable for permanent installation in compatible switchboards. Four auxiliary contacts and open/closed position indication support monitoring and integration into industrial, commercial and infrastructure power distribution systems.

Key Advantages

  • High-performance 1250 A air circuit breaker for demanding low-voltage distribution.
  • Four-pole configuration suitable for systems requiring phase and neutral switching.
  • Exceptional 130 kA Icu at 400–415 V AC.
  • Advanced PR122/P-LSI R1250 electronic overcurrent release.
  • LSI protection provides long-time overload, short-time delayed and instantaneous short-circuit protection.
  • Fixed construction with rear horizontal terminals for permanent switchboard installation.
  • Part of the high-breaking-capacity ABB SACE Emax E2L air circuit breaker range.

Key Features

  • ABB SACE Emax E2L 1250 series.
  • 1250 A rated uninterrupted current.
  • Four-pole configuration.
  • Fixed execution.
  • Rear horizontal terminals (HR).
  • PR122/P-LSI R1250 electronic trip unit.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • 130 kA Icu at 400–415 V AC.
  • 1000 V rated insulation voltage and 12 kV impulse withstand voltage.
  • Four auxiliary contacts with open/closed position indication.

High-Breaking-Capacity LSI Protection for Power Distribution

ABB SACE Emax E2L air circuit breakers are designed for low-voltage installations where very high prospective short-circuit currents require substantial interruption capability. The E2L 1250 combines a 1250 A continuous-current rating with up to 130 kA ultimate breaking capacity at common low-voltage distribution voltages, making it suitable for demanding main distribution and industrial switchgear applications.

The PR122/P-LSI electronic trip unit provides three principal protection functions: long-time overload protection, short-time delayed short-circuit protection and instantaneous short-circuit protection. This combination allows the 1SDA056060R1 to provide comprehensive overcurrent protection while supporting coordination and selectivity requirements within appropriately engineered electrical distribution systems.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems with high prospective fault currents.
  • Transformer secondary protection and distribution.
  • Generator and utility distribution systems.
  • Manufacturing and process plant switchgear.
  • Commercial and infrastructure electrical distribution.
  • Four-pole installations requiring phase and neutral switching with LSI protection.

Technical Specifications

Product family SACE Emax
Series E2L
ABB order code 1SDA056060R1
Product group 310513-New Emax
Product type Air circuit breaker
Rated uninterrupted current (Iu) 1250 A
Rated operational current (Ie) 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Current type AC
Number of poles 4
Execution Fixed
Terminal arrangement Rear horizontal terminals (HR)
Trip unit PR122/P-LSI R1250
Release type Electronic overcurrent release
Protection functions LSI – long-time overload, short-time delayed and instantaneous short-circuit protection
Short-circuit performance level L
Rated ultimate short-circuit breaking capacity (Icu) at 220–415 V AC 130 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 110 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 220–415 V AC 130 kA
Rated service short-circuit breaking capacity (Ics) at 440 V AC 110 kA
Rated service short-circuit breaking capacity (Ics) at 500–690 V AC 65 kA
Rated short-time withstand current (Icw), 1 s 10 kA
Overload release adjustment range 500–1250 A
Short-time delayed short-circuit adjustment range 1250–12500 A
Instantaneous short-circuit adjustment range 1875–18750 A
Power loss 105 W
Electrical durability at ≤440 V 4000 cycles
Electrical durability at 500–690 V 3000 cycles
Mechanical durability 20000 cycles
Auxiliary contacts 4
Position indication Open / closed
Dimensions (W × H × D) 386 × 418 × 302 mm
Net weight 68 kg
EAN 8015644574000

Frequently Asked Questions

What is the ABB 1SDA056060R1 used for?

The ABB 1SDA056060R1 is a 1250 A four-pole fixed air circuit breaker designed for switching, isolation and electronic overcurrent protection in demanding low-voltage electrical distribution systems, particularly where high short-circuit interruption capability is required.

What is the current rating of the ABB E2L 1250 1SDA056060R1?

The ABB 1SDA056060R1 has a rated uninterrupted current of 1250 A and a rated operational voltage of up to 690 V AC.

What protection does the PR122/P-LSI trip unit provide?

The PR122/P-LSI electronic trip unit provides LSI protection consisting of long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.

What is the short-circuit breaking capacity of the ABB E2L 1250?

The E2L 1250 provides a rated ultimate short-circuit breaking capacity of 130 kA at 220–415 V AC, 110 kA at 440 V AC and 85 kA at 500–690 V AC.

Is the ABB 1SDA056060R1 fixed or withdrawable?

The ABB 1SDA056060R1 is a four-pole fixed air circuit breaker with rear horizontal terminals for permanent installation within compatible low-voltage switchgear.

Trusted for High-Performance Industrial Power Distribution

ABB SACE Emax air circuit breakers are engineered to provide dependable switching, isolation and advanced electronic protection in demanding low-voltage power distribution systems, with the E2L range providing particularly high short-circuit breaking performance for critical industrial, commercial and infrastructure installations.