ABB E2L1250 1SDA056059R1 is a 1250 A four-pole fixed SACE Emax air circuit breaker with horizontal rear terminals and a PR122/P-LI electronic trip unit for overload and instantaneous short-circuit protection.
£10,517.96
The ABB E2L1250 1SDA056059R1 is a high-performance SACE Emax air circuit breaker (ACB) designed for protection and switching in demanding high-current low-voltage electrical distribution systems. Part of the proven ABB SACE Emax E2 series, this four-pole fixed circuit breaker combines a 1250 A rated current with the advanced PR122/P-LI electronic trip unit for dependable overload and instantaneous short-circuit protection.
Designed for industrial, infrastructure and commercial power distribution applications, the E2L1250 provides exceptionally high short-circuit interruption performance. The PR122/P-LI electronic overcurrent release provides L and I protection functions, helping protect conductors, busbars and connected equipment against sustained overloads and severe short-circuit currents.
This model is a four-pole fixed circuit breaker with horizontal rear terminals for switchboard and busbar integration. The E2L performance level provides a rated ultimate short-circuit breaking capacity of 130 kA at 415 V AC, making it particularly suitable for distribution systems with very high prospective fault currents.
The ABB E2L1250 is engineered for low-voltage installations where exceptionally high prospective short-circuit currents require substantial interruption capability. With an ultimate breaking capacity of 130 kA at 415 V AC, this E2L configuration is well suited to main switchboards, transformer-fed distribution systems and industrial networks located close to high-capacity power sources.
The PR122/P-LI electronic trip unit provides long-time protection against sustained overloads together with instantaneous protection against severe short-circuit currents. Combined with the robust fixed SACE Emax platform, horizontal rear terminals and four-pole construction, this configuration provides dependable protection for critical three-phase and neutral low-voltage distribution circuits.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA056059R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Number of poles | 4 |
| Execution | Fixed |
| Terminal arrangement | Horizontal rear terminals |
| Trip unit | PR122/P-LI electronic release |
| Protection functions | L, I |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate breaking capacity (Icu) at 415 V AC | 130 kA |
| Rated service breaking capacity (Ics) at 415 V AC | 130 kA |
| Rated ultimate breaking capacity (Icu) at 440 V AC | 110 kA |
| Rated service breaking capacity (Ics) at 440 V AC | 110 kA |
| Rated ultimate breaking capacity (Icu) at 500 V AC | 85 kA |
| Rated service breaking capacity (Ics) at 500 V AC | 65 kA |
| Rated ultimate breaking capacity (Icu) at 690 V AC | 85 kA |
| Rated service breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 10 kA |
| Short-circuit performance level | L |
| Current type | AC |
| Power loss | 105 W |
| Electrical durability at ≤440 V | 4,000 cycles |
| Electrical durability at 500–690 V | 3,000 cycles |
| Mechanical durability | 20,000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Product dimensions (W × H × D) | 386 × 418 × 302 mm |
| Product net weight | 56 kg |
| EAN | 8015644573997 |
| Customs tariff number | 85362090 |
| Standard | IEC |
It is a 1250 A air circuit breaker designed for switching and protection of demanding low-voltage electrical distribution systems.
This circuit breaker is equipped with an ABB PR122/P-LI electronic overcurrent release.
The LI configuration provides long-time overload and instantaneous short-circuit protection.
The E2L1250 provides a rated ultimate short-circuit breaking capacity of 130 kA at 415 V AC.
This model is a four-pole fixed air circuit breaker with horizontal rear terminals, a 1250 A rated current and PR122/P-LI electronic protection.
ABB SACE Emax air circuit breakers are engineered for dependable protection and control of low-voltage power distribution systems, combining high breaking performance with electronic protection technology for demanding industrial, commercial and infrastructure installations.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.