1SDA056056R1 ABB E2L1250 PR121/P-LI 1250A 4P Fixed Air Circuit Breaker

1SDA056056R1 ABB E2L1250 PR121/P-LI 1250A 4P Fixed Air Circuit Breaker

ABB 1SDA056056R1 is a SACE Emax E2L 1250 four-pole 1250 A fixed air circuit breaker with rear horizontal terminals and a PR121/P-LI R1250 electronic overcurrent release for high-current low-voltage circuit protection.

SKU: 1SDA056056R1MPN: 1SDA056056R1
Price
List Price £13,919.17 ex VAT
Your Price (ex VAT) Save 25%
£10,439.38 25% OFF
You save £3,479.79 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,439.38
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,439.38

Why Choose the ABB E2L1250 PR121/P-LI 1250A 4P Fixed Air Circuit Breaker?

The ABB E2L1250 PR121/P-LI, order code 1SDA056056R1, is a high-performance SACE Emax air circuit breaker designed for switching and protection in demanding low-voltage power distribution systems. As part of the ABB SACE Emax E2L series, this four-pole fixed circuit breaker is rated at 1250 A and incorporates a PR121/P-LI R1250 electronic overcurrent release.

The PR121/P-LI trip unit provides long-time overload (L) and instantaneous short-circuit (I) protection, helping protect electrical distribution circuits against sustained overcurrents and severe short-circuit faults. The E2L performance level provides high fault-interruption capability for industrial, commercial and infrastructure installations where dependable high-current circuit protection is required.

This E2L1250 configuration features a four-pole fixed execution with rear horizontal flat terminals. It has a rated operational current of 1250 A, a rated operational voltage up to 690 V AC and an ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC, making it suitable for substantial low-voltage distribution and switchboard applications.

Key Advantages

  • High-performance 1250 A SACE Emax air circuit breaker.
  • Advanced PR121/P electronic overcurrent release for dependable circuit protection.
  • LI protection provides long-time overload and instantaneous short-circuit protection.
  • Four-pole configuration suitable for three-phase distribution systems incorporating a neutral conductor.
  • Fixed execution with rear horizontal flat terminals for permanent switchboard installation.
  • High ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC.

Key Features

  • ABB SACE Emax E2L 1250 air circuit breaker.
  • 1250 A rated current.
  • Four-pole configuration.
  • PR121/P-LI R1250 electronic overcurrent release.
  • Long-time overload protection (L).
  • Instantaneous short-circuit protection (I).
  • Fixed circuit breaker execution.
  • Rear horizontal flat terminals.
  • Rated operational voltage up to 690 V AC.
  • Fitted with four auxiliary change-over contacts and circuit breaker open/closed position indication.

High-Performance Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E2L1250 provide switching and protection for high-current low-voltage distribution circuits. The electronic overcurrent release monitors current conditions and initiates breaker operation when configured protection thresholds are exceeded, helping protect cables, busbars, switchgear and connected electrical equipment.

The PR121/P-LI release combines long-time overload and instantaneous short-circuit protection within an electronic trip unit. Together with the E2L frame's high breaking capacity and four-pole fixed construction, this configuration provides dependable protection for main distribution and feeder circuits in demanding industrial, commercial and infrastructure installations.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plant switchgear.
  • Commercial building electrical distribution.
  • Infrastructure and utility installations.
  • Main incomer and high-current feeder protection.
  • Four-pole three-phase distribution systems incorporating neutral switching.

Technical Specifications

Product family SACE Emax
Series / frame E2L 1250
ABB order code 1SDA056056R1
Product type Air circuit breaker
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated operational current (Ie) 1250 A
Number of poles 4
Trip unit PR121/P-LI R1250
Release type Electronic
Protection functions LI
Long-time protection L
Instantaneous protection I
Overload release adjustment range 500–1250 A
Instantaneous short-circuit release adjustment range 1875–18750 A
Rated operational voltage up to 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Ultimate short-circuit breaking capacity (Icu) 130 kA at 400–415 V AC
Service short-circuit breaking capacity (Ics) 130 kA at 400–415 V AC
Ultimate short-circuit breaking capacity at 690 V AC 85 kA
Service short-circuit breaking capacity at 690 V AC 65 kA
Execution Fixed
Terminal configuration Rear horizontal flat terminals
Auxiliary contacts 4 change-over contacts
Position indication Open / closed
Motor drive Optional
Integrated earth-fault protection No
Power loss 105 W
Mechanical durability 20,000 operating cycles
Dimensions (W × H × D) 386 × 418 × 302 mm
Net weight 56 kg
Standard IEC
EAN 8015644573966
Product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA056056R1?

The ABB 1SDA056056R1 is a SACE Emax E2L 1250 four-pole fixed air circuit breaker rated at 1250 A, fitted with rear horizontal terminals and a PR121/P-LI R1250 electronic overcurrent release.

What is the rated current of the ABB E2L1250 PR121/P-LI?

The circuit breaker has a rated current of 1250 A and is designed for high-current low-voltage power distribution applications.

What does LI protection mean on the PR121/P trip unit?

LI denotes long-time overload protection and instantaneous short-circuit protection, providing protection against sustained overcurrents and severe short-circuit faults.

How many poles does ABB 1SDA056056R1 have?

The ABB 1SDA056056R1 is a four-pole circuit breaker, suitable for three-phase distribution systems where the neutral conductor is incorporated into the breaker configuration.

Is the ABB 1SDA056056R1 fixed or withdrawable?

This model is a fixed circuit breaker with rear horizontal flat terminals, intended for permanent installation within a compatible low-voltage switchboard.

What is the breaking capacity of the ABB E2L1250 1SDA056056R1?

The breaker has an ultimate short-circuit breaking capacity of 130 kA at 400–415 V AC and 85 kA at 690 V AC.

Trusted by Electrical Engineers Worldwide

ABB SACE Emax air circuit breakers are widely applied in demanding low-voltage power distribution systems, providing dependable high-current switching and electronic circuit protection for industrial, commercial and infrastructure installations.