ABB E2S2000 1SDA056045R1 is a 2000 A four-pole withdrawable SACE Emax air circuit breaker moving part with a PR122/P-LSIG electronic trip unit for overload, short-circuit and earth-fault protection.
£17,259.01
The ABB E2S2000 1SDA056045R1 is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for protection and switching in high-current low-voltage electrical distribution systems. Part of the proven ABB SACE Emax E2 series, this four-pole withdrawable breaker combines a 2000 A rated current with the advanced PR122/P-LSIG electronic trip unit for comprehensive overload, short-time, instantaneous and earth-fault protection.
Designed for demanding industrial and commercial power distribution applications, the E2S2000 provides reliable circuit protection while its withdrawable construction supports convenient inspection, servicing and replacement when installed with the appropriate Emax fixed part. The PR122/P-LSIG electronic overcurrent release provides L, S, I and G protection functions, supporting selective coordination and protection against sustained overloads, short circuits and earth faults.
This model is a four-pole withdrawable moving part rated at 2000 A with an operational voltage up to 690 V AC. Its E2S performance class provides a rated ultimate short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC, making it suitable for substantial distribution systems requiring high fault-current interruption capability.
Air circuit breakers such as the ABB E2S2000 provide switching and protection at the main and distribution levels of low-voltage electrical installations. Their high current capability, substantial short-circuit interruption performance and electronic protection technology make them particularly suitable for switchboards supplying industrial machinery, infrastructure, commercial facilities and other substantial electrical loads.
The PR122/P-LSIG electronic trip unit provides long-time overload, short-time delayed short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the withdrawable SACE Emax platform, this configuration delivers comprehensive electrical protection while allowing the breaker moving part to be withdrawn from its compatible fixed part for servicing or replacement.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA056045R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Number of poles | 4 |
| Execution | Withdrawable moving part |
| Trip unit | PR122/P-LSIG electronic release |
| Protection functions | L, S, I, G |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate breaking capacity (Icu) at 415 V AC | 85 kA |
| Rated service breaking capacity (Ics) at 415 V AC | 85 kA |
| Rated ultimate breaking capacity (Icu) at 690 V AC | 65 kA |
| Rated service breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Short-circuit performance level | S |
| Current type | AC |
| Power loss | 330 W |
| Electrical durability at ≤440 V | 10,000 cycles |
| Electrical durability at 500–690 V | 8,000 cycles |
| Mechanical durability | 25,000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Product dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Product net weight | 61 kg |
| EAN | 8015644573850 |
| Standard | IEC |
It is a 2000 A air circuit breaker moving part designed for switching and protection of high-current low-voltage electrical distribution systems.
This circuit breaker is equipped with an ABB PR122/P-LSIG electronic overcurrent release.
The LSIG configuration provides long-time overload, short-time, instantaneous short-circuit and earth-fault protection.
The E2S2000 has a rated ultimate short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC.
This model is a four-pole withdrawable moving part designed for use with the corresponding SACE Emax E2 fixed part.
ABB SACE Emax air circuit breakers are engineered for dependable protection and control of low-voltage power distribution systems, combining high breaking performance, comprehensive electronic protection and maintainable withdrawable construction for demanding industrial and commercial installations.