ABB 1SDA056040R1 is a SACE Emax E2S 2000 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LI R2000 electronic overcurrent release providing long-time overload and instantaneous short-circuit protection.
£15,661.07
The ABB 1SDA056040R1 is a high-performance SACE Emax E2S 2000 air circuit breaker moving part designed for reliable switching and overcurrent protection in demanding low-voltage electrical distribution systems. This four-pole withdrawable circuit breaker moving part is equipped with the PR121/P-LI R2000 electronic overcurrent release, combining a high continuous-current rating with dependable electronic protection.
With a rated uninterrupted current of 2000 A and a rated operational voltage of up to 690 V AC, the E2S 2000 is suitable for main distribution switchboards, industrial installations, transformer protection and commercial power infrastructure. The PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection for conductors, switchgear and connected equipment.
The E2S performance level provides high short-circuit interruption capability, including a rated ultimate short-circuit breaking capacity of 85 kA at 220 V AC and a rated short-time withstand current of 65 kA for 1 s. This version is supplied as a four-pole withdrawable moving part (W MP) fitted with four auxiliary contacts and open/closed circuit-breaker position indication.
Air circuit breakers such as the ABB SACE Emax E2S provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. The E2S 2000 combines substantial continuous-current capability with high short-circuit performance, making it suitable for main switchboards, industrial distribution systems and other installations where dependable fault interruption is essential.
The PR121/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. Combined with the four-pole withdrawable SACE Emax construction, the 1SDA056040R1 provides dependable electronic protection while allowing the circuit breaker moving part to be withdrawn from its compatible fixed portion for inspection, maintenance or replacement.
| Product family | SACE Emax |
|---|---|
| Series | E2S |
| ABB order code | 1SDA056040R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Rated operational voltage | Up to 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Execution | Withdrawable moving part (W MP) |
| Trip unit | PR121/P-LI R2000 |
| Release type | Electronic overcurrent release |
| Protection functions | LI – long-time overload and instantaneous short-circuit protection |
| Short-circuit performance level | S |
| Rated ultimate short-circuit breaking capacity (Icu) at 220 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 220 V AC | 85 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Product depth | 396.5 mm |
| Net weight | 73 kg |
| EAN | 8015644573805 |
The ABB 1SDA056040R1 is a 2000 A four-pole air circuit breaker moving part designed for switching and electronic overcurrent protection in demanding low-voltage electrical distribution systems.
The ABB 1SDA056040R1 has a rated uninterrupted current of 2000 A, making it suitable for high-current industrial, commercial and infrastructure power distribution applications.
The PR121/P-LI electronic trip unit provides LI protection functions consisting of long-time overload protection and instantaneous short-circuit protection.
The E2S 2000 is an S-performance air circuit breaker. For this configuration, the rated ultimate and service short-circuit breaking capacities are 85 kA at 220 V AC, while the rated short-time withstand current is 65 kA for 1 s.