ABB 1SDA056034R1 SACE Emax E2S2000 three-pole withdrawable air circuit breaker moving part with a 2000 A rating, PR121/P-LSIG electronic protection and 85 kA breaking capacity at 415 V AC for low-voltage power distribution.
£13,510.74
The ABB 1SDA056034R1 is a high-performance SACE Emax E2S air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product group, this three-pole withdrawable circuit breaker combines a 2000 A rated current with the advanced PR121/P-LSIG electronic overcurrent release for comprehensive protection of industrial and commercial power networks.
The E2S2000 provides long-time, short-time, instantaneous and earth-fault protection through its LSIG trip functionality. These protection functions help safeguard electrical equipment and conductors against overloads, short circuits and earth faults while supporting effective coordination and selectivity throughout complex low-voltage distribution systems.
With a rated uninterrupted current of 2000 A, a 690 V AC rated operational voltage and an ultimate short-circuit breaking capacity of 85 kA at 415 V AC, the E2S2000 is suitable for high-current switchboards, main incomers and distribution feeders. This version is a three-pole withdrawable moving part, allowing removal from a compatible Emax fixed part for inspection, testing, maintenance or replacement.
Air circuit breakers such as the ABB Emax E2S2000 provide switching, isolation and comprehensive overcurrent protection at critical points within high-current low-voltage distribution systems. Their high short-circuit performance makes them particularly suitable for main incomers, distribution feeders and other applications where dependable interruption of high fault currents is essential.
The PR121/P-LSIG electronic trip unit provides long-time overload, short-time overcurrent, instantaneous short-circuit and earth-fault protection. Combined with the withdrawable Emax design, this provides comprehensive electrical protection while allowing the circuit-breaker moving part to be removed from compatible switchgear for inspection, testing, servicing or replacement.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB order code | 1SDA056034R1 |
| Product type | Air circuit breaker moving part |
| Frame / size | E2 |
| Performance level | S |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Current type | AC |
| Number of poles | 3 |
| Version | Withdrawable (W) |
| Trip unit | PR121/P-LSIG |
| Release type | Electronic |
| Protection functions | Long-time, short-time, instantaneous and earth fault (LSIG) |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability at ≤440 V | 10,000 operating cycles |
| Electrical durability at 500–690 V | 8,000 operating cycles |
| Standard | IEC |
The ABB 1SDA056034R1 is an E2S2000 withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems against overloads, short circuits and earth faults.
This circuit breaker has a rated uninterrupted current of 2000 A, making it suitable for high-current industrial and commercial power distribution applications.
The PR121/P-LSIG electronic overcurrent release provides long-time overload, short-time overcurrent, instantaneous short-circuit and earth-fault protection.
The E2S2000 has a rated ultimate short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC.
The 1SDA056034R1 is a three-pole withdrawable circuit breaker moving part designed for use with a compatible Emax fixed part, allowing removal for inspection, testing, servicing or replacement.
ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high short-circuit performance, advanced electronic protection and service-friendly withdrawable configurations for industrial, commercial and infrastructure applications.
We use cookies