1SDA056033R1 ABB E2S2000 PR121/P-LSI 2000A 3P Withdrawable Air Circuit Breaker

1SDA056033R1 ABB E2S2000 PR121/P-LSI 2000A 3P Withdrawable Air Circuit Breaker

ABB 1SDA056033R1 SACE Emax E2S2000 three-pole withdrawable air circuit breaker moving part with a 2000 A rating, PR121/P-LSI electronic protection and 85 kA breaking capacity at 415 V AC for low-voltage power distribution.

SKU: 1SDA056033R1Alt SKU: E2S2000MPN: 1SDA056033R1
Price
List Price £16,819.51 ex VAT
Your Price (ex VAT) Save 25%
£12,614.63 25% OFF
You save £4,204.88 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £12,614.63
Trade pricing is personalised to your account

Manufacturer Lead Time

£12,614.63

Why Choose the ABB E2S2000 PR121/P-LSI 2000A 3P Withdrawable Air Circuit Breaker?

The ABB 1SDA056033R1 is a high-performance SACE Emax E2S air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB New Emax product group, this three-pole withdrawable circuit breaker combines a 2000 A rated current with the PR121/P-LSI electronic overcurrent release for dependable protection of industrial and commercial power networks.

The E2S2000 provides long-time, short-time and instantaneous protection through its LSI trip functionality. The electronic release offers adjustable protection characteristics for effective coordination and selectivity, helping protect conductors and equipment against overload and short-circuit conditions throughout complex low-voltage distribution systems.

With a rated uninterrupted current of 2000 A, a 690 V AC rated operational voltage and an ultimate short-circuit breaking capacity of 85 kA at 415 V AC, the E2S2000 is suitable for high-current switchboards, main incomers and distribution feeders. This version is the three-pole withdrawable moving part, allowing the breaker to be removed from a compatible fixed part for inspection, servicing or replacement.

Key Advantages

  • High-performance ABB SACE Emax air circuit breaker moving part for low-voltage power distribution.
  • 2000 A rated uninterrupted current for high-current electrical installations.
  • Three-pole withdrawable configuration for industrial three-phase distribution systems.
  • Advanced PR121/P-LSI electronic overcurrent release.
  • LSI functionality provides long-time, short-time and instantaneous protection.
  • High 85 kA breaking capacity at 415 V AC.
  • 65 kA short-time withstand current for 1 s supports robust system coordination.
  • Withdrawable construction simplifies inspection, maintenance and replacement within compatible switchgear.

Key Features

  • ABB SACE Emax E2S2000 air circuit breaker moving part.
  • 2000 A rated uninterrupted current.
  • Three-pole construction.
  • Withdrawable circuit-breaker configuration.
  • PR121/P-LSI electronic overcurrent release.
  • 690 V AC rated operational voltage.
  • 85 kA Icu at 415 V AC.
  • 65 kA Icu at 690 V AC.
  • 65 kA Icw for 1 s.
  • 50 kA Icw for 3 s.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Four auxiliary change-over contacts.
  • Circuit-breaker open/closed position indication.

Reliable Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB Emax E2S2000 provide switching, isolation and overcurrent protection at critical points within high-current low-voltage distribution systems. Their high short-circuit performance makes them particularly suitable for main incomers, distribution feeders and other applications where dependable interruption of high fault currents is essential.

The PR121/P-LSI electronic trip unit provides long-time overload, short-time overcurrent and instantaneous short-circuit protection. Combined with the withdrawable Emax design, this enables reliable electrical protection while allowing the breaker moving part to be removed from compatible switchgear for maintenance, testing or replacement.

Typical Applications

  • Main incoming circuit breakers in low-voltage switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Manufacturing and process plants.
  • Transformer and generator distribution systems.
  • High-current distribution feeder protection.
  • Withdrawable power distribution and switchgear assemblies.
  • Electrical networks requiring coordinated overload and short-circuit protection.

Technical Specifications

Series SACE Emax
Product group 310513-New Emax
ABB order code 1SDA056033R1
EAN 8015644573737
Product type Air circuit breaker moving part
Frame / size E2
Performance level S
Rated current (In) 2000 A
Rated uninterrupted current (Iu) 2000 A
Rated operational current (Ie) 2000 A
Current type AC
Number of poles 3
Version Withdrawable (W)
Trip unit PR121/P-LSI
Release type Electronic
Protection functions Long-time, short-time and instantaneous (LSI)
Overload release adjustment range 800–2000 A
Short-time delayed short-circuit release adjustment range 2000–20000 A
Instantaneous short-circuit release adjustment range 3000–30000 A
Integrated earth-fault protection No
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 220–440 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 500–690 V AC 65 kA
Rated short-time withstand current (Icw), 1 s 65 kA
Rated short-time withstand current (Icw), 3 s 50 kA
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open/closed
Motor drive Optional
Mechanical durability 25,000 operating cycles
Electrical durability at ≤440 V 10,000 operating cycles
Electrical durability at 500–690 V 8,000 operating cycles
Power loss 330 W
Dimensions (W × H × D) 324 × 461 × 396.5 mm
Net weight 49 kg
Standard IEC

Frequently Asked Questions

What is the ABB 1SDA056033R1 used for?

The ABB 1SDA056033R1 is an E2S2000 withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems against overload and short-circuit conditions.

What is the rated current of the ABB E2S2000 1SDA056033R1?

This circuit breaker has a rated uninterrupted current of 2000 A, making it suitable for high-current industrial and commercial power distribution applications.

What protection does the PR121/P-LSI trip unit provide?

The PR121/P-LSI electronic overcurrent release provides long-time overload, short-time overcurrent and instantaneous short-circuit protection. This LSI version does not include integrated earth-fault protection.

What is the breaking capacity of the ABB E2S2000?

The E2S2000 has a rated ultimate short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC.

Is the ABB 1SDA056033R1 fixed or withdrawable?

The 1SDA056033R1 is a three-pole withdrawable circuit breaker moving part. It is designed for use with a compatible Emax fixed part, allowing the breaker to be withdrawn for inspection, servicing, testing or replacement.

Trusted Protection from ABB

ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high short-circuit performance, electronic overcurrent protection and service-friendly withdrawable configurations for industrial, commercial and infrastructure applications.