Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056033R1 SACE Emax E2S2000 three-pole withdrawable air circuit breaker moving part with a 2000 A rating, PR121/P-LSI electronic protection and 85 kA breaking capacity at 415 V AC for low-voltage power distribution.
£12,614.63
The ABB 1SDA056033R1 is a high-performance SACE Emax E2S air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. As part of the ABB New Emax product group, this three-pole withdrawable circuit breaker combines a 2000 A rated current with the PR121/P-LSI electronic overcurrent release for dependable protection of industrial and commercial power networks.
The E2S2000 provides long-time, short-time and instantaneous protection through its LSI trip functionality. The electronic release offers adjustable protection characteristics for effective coordination and selectivity, helping protect conductors and equipment against overload and short-circuit conditions throughout complex low-voltage distribution systems.
With a rated uninterrupted current of 2000 A, a 690 V AC rated operational voltage and an ultimate short-circuit breaking capacity of 85 kA at 415 V AC, the E2S2000 is suitable for high-current switchboards, main incomers and distribution feeders. This version is the three-pole withdrawable moving part, allowing the breaker to be removed from a compatible fixed part for inspection, servicing or replacement.
Air circuit breakers such as the ABB Emax E2S2000 provide switching, isolation and overcurrent protection at critical points within high-current low-voltage distribution systems. Their high short-circuit performance makes them particularly suitable for main incomers, distribution feeders and other applications where dependable interruption of high fault currents is essential.
The PR121/P-LSI electronic trip unit provides long-time overload, short-time overcurrent and instantaneous short-circuit protection. Combined with the withdrawable Emax design, this enables reliable electrical protection while allowing the breaker moving part to be removed from compatible switchgear for maintenance, testing or replacement.
| Series | SACE Emax |
|---|---|
| Product group | 310513-New Emax |
| ABB order code | 1SDA056033R1 |
| EAN | 8015644573737 |
| Product type | Air circuit breaker moving part |
| Frame / size | E2 |
| Performance level | S |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Current type | AC |
| Number of poles | 3 |
| Version | Withdrawable (W) |
| Trip unit | PR121/P-LSI |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload release adjustment range | 800–2000 A |
| Short-time delayed short-circuit release adjustment range | 2000–20000 A |
| Instantaneous short-circuit release adjustment range | 3000–30000 A |
| Integrated earth-fault protection | No |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open/closed |
| Motor drive | Optional |
| Mechanical durability | 25,000 operating cycles |
| Electrical durability at ≤440 V | 10,000 operating cycles |
| Electrical durability at 500–690 V | 8,000 operating cycles |
| Power loss | 330 W |
| Dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Net weight | 49 kg |
| Standard | IEC |
The ABB 1SDA056033R1 is an E2S2000 withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems against overload and short-circuit conditions.
This circuit breaker has a rated uninterrupted current of 2000 A, making it suitable for high-current industrial and commercial power distribution applications.
The PR121/P-LSI electronic overcurrent release provides long-time overload, short-time overcurrent and instantaneous short-circuit protection. This LSI version does not include integrated earth-fault protection.
The E2S2000 has a rated ultimate short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC.
The 1SDA056033R1 is a three-pole withdrawable circuit breaker moving part. It is designed for use with a compatible Emax fixed part, allowing the breaker to be withdrawn for inspection, servicing, testing or replacement.
ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high short-circuit performance, electronic overcurrent protection and service-friendly withdrawable configurations for industrial, commercial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.