ABB 1SDA056032R1 E2S2000 three-pole withdrawable air circuit breaker moving part rated at 2000 A with a PR121/P-LI R2000 electronic release providing long-time overload and instantaneous short-circuit protection.
£12,067.16
The ABB E2S2000 PR121/P-LI, order code 1SDA056032R1, is a high-performance three-pole withdrawable air circuit breaker moving part designed for switching and protection in demanding low-voltage power distribution systems. As part of the ABB SACE Emax E2 series, it combines a rated current of 2000 A with the electronic PR121/P-LI R2000 overcurrent release.
The PR121/P-LI release provides long-time and instantaneous overcurrent protection, helping protect conductors, switchgear and connected equipment against sustained overloads and severe short-circuit conditions. Its electronic protection architecture provides dependable fault response for industrial, commercial and infrastructure distribution networks.
This version is supplied as the moving part of a withdrawable E2S2000 circuit breaker and is intended for use with the appropriate ABB SACE Emax fixed part. Its three-pole construction, 2000 A current rating, rated operational voltage of 690 V AC and high short-circuit performance make it suitable for critical high-current switchboard applications.
Air circuit breakers such as the ABB SACE Emax E2S2000 provide switching, isolation and fault protection for high-current low-voltage distribution systems. The E2S performance level provides substantial short-circuit interruption capability, making this breaker suitable for main switchboards and industrial installations where high prospective fault currents can occur.
The PR121/P-LI electronic release provides long-time protection against sustained overloads together with instantaneous protection against severe short circuits. Combined with withdrawable construction, auxiliary signalling contacts and circuit-breaker position indication, the E2S2000 moving part provides dependable electrical protection together with practical serviceability in suitable ABB Emax switchgear.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA056032R1 |
| Product type | Air circuit breaker moving part |
| Frame / performance level | E2S |
| Number of poles | 3 |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Trip unit | PR121/P-LI R2000 |
| Release type | Electronic |
| Protection functions | LI – Long-time and Instantaneous |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 400/415 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Installation | Withdrawable |
| Component | Moving part |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Electrical durability at ≤440 V | 10,000 cycles |
| Electrical durability at 500–690 V | 8,000 cycles |
| Mechanical durability | 25,000 cycles |
| Power loss | 330 W |
| Weight | 59 kg |
| EAN | 8015644573720 |
The ABB 1SDA056032R1 is the moving part of a three-pole SACE Emax E2S2000 withdrawable air circuit breaker rated at 2000 A and fitted with a PR121/P-LI R2000 electronic overcurrent release.
The PR121/P-LI provides long-time overload protection and instantaneous short-circuit protection.
The E2S2000 moving part has a rated uninterrupted current of 2000 A and uses a three-pole configuration.
ABB 1SDA056032R1 is the moving part of a withdrawable air circuit breaker and is designed for use with the appropriate ABB SACE Emax fixed part.
The E2S2000 provides an ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC and 65 kA at 690 V AC.
ABB SACE Emax air circuit breakers combine high short-circuit performance, electronic overcurrent protection and serviceable withdrawable construction to provide dependable switching and protection for demanding low-voltage power distribution systems.