Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA056027R1 is a SACE Emax E2S 2000 A four-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LI R2000 electronic overcurrent release providing long-time overload and instantaneous short-circuit protection.
£13,875.17
The ABB 1SDA056027R1 is a high-performance SACE Emax E2S 2000 air circuit breaker (ACB) designed for reliable switching, isolation and overcurrent protection in demanding low-voltage electrical distribution systems. This four-pole fixed circuit breaker is equipped with the PR122/P-LI R2000 electronic overcurrent release, combining a high continuous-current rating with advanced electronic protection.
With a rated uninterrupted current of 2000 A and a rated operational voltage of up to 690 V AC, the E2S 2000 is suitable for main distribution switchboards, industrial installations, transformer protection and commercial power infrastructure. The PR122/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection for dependable protection of conductors and connected equipment.
The E2S performance level provides a rated ultimate short-circuit breaking capacity of 85 kA at 220–440 V AC and 65 kA at 500–690 V AC. This version is supplied as a four-pole fixed circuit breaker with rear horizontal terminals and is fitted with four auxiliary contacts plus open/closed position indication for integration into compatible low-voltage switchgear.
Air circuit breakers such as the ABB SACE Emax E2S provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. The E2S 2000 combines substantial continuous-current capability with high short-circuit interruption performance, making it particularly suitable for main switchboards and industrial distribution systems where dependable fault clearance is essential.
The PR122/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. Combined with the four-pole fixed construction and rear horizontal terminals, the 1SDA056027R1 provides dependable electronic protection for permanent switchgear installations requiring a high current rating and robust short-circuit performance.
| Product family | SACE Emax |
|---|---|
| Series | E2S |
| ABB order code | 1SDA056027R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Execution | Fixed |
| Terminal arrangement | Rear horizontal terminals (HR) |
| Trip unit | PR122/P-LI R2000 |
| Release type | Electronic overcurrent release |
| Protection functions | LI – long-time overload and instantaneous short-circuit protection |
| Short-circuit performance level | S |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Power loss | 180 W |
| Electrical durability at ≤440 V | 10000 cycles |
| Electrical durability at 500–690 V | 8000 cycles |
| Mechanical durability | 25000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Dimensions (W × H × D) | 386 × 418 × 302 mm |
| Net weight | 56 kg |
| EAN | 8015644573676 |
The ABB 1SDA056027R1 is a 2000 A four-pole air circuit breaker designed for switching, isolation and electronic overcurrent protection in demanding low-voltage electrical distribution systems.
The ABB 1SDA056027R1 has a rated uninterrupted current of 2000 A and a rated operational voltage of up to 690 V AC.
The PR122/P-LI electronic trip unit provides LI protection functions consisting of long-time overload protection and instantaneous short-circuit protection.
The E2S 2000 provides a rated ultimate short-circuit breaking capacity of 85 kA at 220–440 V AC and 65 kA at 500–690 V AC, with a rated short-time withstand current of 65 kA for 1 s.
The ABB 1SDA056027R1 is a four-pole fixed air circuit breaker with rear horizontal terminals for permanent installation within compatible low-voltage switchgear.
ABB SACE Emax air circuit breakers are engineered to provide dependable switching, isolation and advanced electronic protection in demanding low-voltage power distribution systems, making the E2S 2000 a robust solution for industrial, commercial and infrastructure installations.