1SDA056018R1 ABB E2S2000 PR121/P-LSIG 2000A 3P Fixed Air Circuit Breaker

1SDA056018R1 ABB E2S2000 PR121/P-LSIG 2000A 3P Fixed Air Circuit Breaker

ABB 1SDA056018R1 SACE Emax E2S2000 three-pole fixed air circuit breaker with a 2000 A rating, PR121/P-LSIG electronic protection and 85 kA breaking capacity at 415 V AC for low-voltage power distribution.

SKU: 1SDA056018R1MPN: 1SDA056018R1
Price
List Price £16,703.64 ex VAT
Your Price (ex VAT) Save 25%
£12,527.73 25% OFF
You save £4,175.91 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £12,527.73
Trade pricing is personalised to your account

Manufacturer Lead Time

£12,527.73

Why Choose the ABB E2S2000 PR121/P-LSIG 2000A 3P Fixed Air Circuit Breaker?

The ABB 1SDA056018R1 is a high-performance SACE Emax E2S air circuit breaker (ACB) designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the ABB New Emax product group, this three-pole fixed circuit breaker combines a 2000 A rated current with the advanced PR121/P-LSIG electronic overcurrent release for comprehensive protection of industrial and commercial power networks.

The E2S2000 provides long-time, short-time, instantaneous and earth-fault protection through its LSIG trip functionality. This combination enables effective protection against overloads, short circuits and earth faults while supporting coordination and selectivity within complex low-voltage distribution systems.

With a rated uninterrupted current of 2000 A, a 690 V AC rated operational voltage and an ultimate short-circuit breaking capacity of 85 kA at 415 V AC, the E2S2000 is suited to high-current switchboards, main incomers and distribution feeders. This version features a three-pole fixed configuration with horizontal rear terminals for integration into electrical switchgear assemblies.

Key Advantages

  • High-performance ABB SACE Emax air circuit breaker for low-voltage power distribution.
  • 2000 A rated uninterrupted current for high-current electrical installations.
  • Three-pole fixed configuration for industrial three-phase distribution systems.
  • Advanced PR121/P-LSIG electronic overcurrent release.
  • LSIG functionality provides long-time, short-time, instantaneous and earth-fault protection.
  • High 85 kA breaking capacity at 415 V AC.
  • 65 kA short-time withstand current for 1 s supports robust system coordination.
  • Horizontal rear terminals facilitate integration into switchboards and power distribution assemblies.

Key Features

  • ABB SACE Emax E2S2000 air circuit breaker.
  • 2000 A rated uninterrupted current.
  • Three-pole construction.
  • Fixed circuit-breaker configuration.
  • PR121/P-LSIG electronic overcurrent release.
  • 690 V AC rated operational voltage.
  • 85 kA Icu at 415 V AC.
  • 65 kA Icu at 690 V AC.
  • 65 kA Icw for 1 s.
  • 50 kA Icw for 3 s.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Horizontal rear terminal arrangement.
  • Four auxiliary contacts with open/closed position indication.

Reliable Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB Emax E2S2000 provide switching, isolation and comprehensive overcurrent protection at critical points within high-current low-voltage distribution systems. Their high short-circuit performance makes them particularly suitable for main incomers, distribution feeders and other applications where dependable interruption of high fault currents is essential.

The PR121/P-LSIG electronic trip unit provides long-time overload, short-time overcurrent, instantaneous short-circuit and earth-fault protection. Its protection functions help engineers coordinate circuit breakers throughout an electrical network, improving selectivity while helping isolate electrical faults and maintain supply to unaffected circuits.

Typical Applications

  • Main incoming circuit breakers in low-voltage switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical installations.
  • Manufacturing and process plants.
  • Transformer and generator distribution systems.
  • High-current distribution feeder protection.
  • Power distribution and switchgear assemblies.
  • Electrical networks requiring overload, short-circuit and earth-fault protection.

Technical Specifications

Series SACE Emax
Product group 310513-New Emax
ABB order code 1SDA056018R1
EAN 8015644573584
Product type Air circuit breaker
Frame / size E2
Performance level S
Rated current (In) 2000 A
Rated uninterrupted current (Iu) 2000 A
Rated operational current (Ie) 2000 A
Current type AC
Number of poles 3
Installation Fixed
Trip unit PR121/P-LSIG
Release type Electronic
Protection functions Long-time, short-time, instantaneous and earth fault (LSIG)
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC 85 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 220–440 V AC 85 kA
Rated service short-circuit breaking capacity (Ics) at 500–690 V AC 65 kA
Rated short-time withstand current (Icw), 1 s 65 kA
Rated short-time withstand current (Icw), 3 s 50 kA
Terminal connection Horizontal rear terminals
Auxiliary contacts 4
Mechanical durability 25,000 operating cycles
Electrical durability at ≤440 V 10,000 operating cycles
Electrical durability at 500–690 V 8,000 operating cycles
Power loss 180 W
Dimensions (W × H × D) 296 × 418 × 302 mm
Net weight 45 kg

Frequently Asked Questions

What is the ABB 1SDA056018R1 used for?

The ABB 1SDA056018R1 is an E2S2000 air circuit breaker designed for switching and protecting high-current low-voltage electrical distribution systems against overloads, short circuits and earth faults.

What is the rated current of the ABB E2S2000 1SDA056018R1?

This circuit breaker has a rated uninterrupted current of 2000 A, making it suitable for high-current industrial and commercial power distribution applications.

What protection does the PR121/P-LSIG trip unit provide?

The PR121/P-LSIG electronic overcurrent release provides long-time overload, short-time overcurrent, instantaneous short-circuit and earth-fault protection.

What is the breaking capacity of the ABB E2S2000?

The E2S2000 has a rated ultimate short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC.

Is the ABB 1SDA056018R1 fixed or withdrawable?

The 1SDA056018R1 is a three-pole fixed circuit breaker with horizontal rear terminals, designed for permanent installation within a suitable low-voltage switchboard or power distribution assembly.

Trusted Protection from ABB

ABB SACE Emax air circuit breakers provide dependable switching and protection for demanding low-voltage power distribution systems, combining high short-circuit performance with advanced electronic protection for industrial, commercial and infrastructure applications.