1SDA056012R1 ABB E2S1600 PR122/P-LSI 1600 A 4P Withdrawable Air Circuit Breaker Moving Part

1SDA056012R1 ABB E2S1600 PR122/P-LSI 1600 A 4P Withdrawable Air Circuit Breaker Moving Part

ABB 1SDA056012R1 E2S1600 four-pole withdrawable air circuit breaker moving part rated at 1600 A with a PR122/P-LSI electronic release providing long-time, short-time and instantaneous overcurrent protection.

SKU: 1SDA056012R1MPN: 1SDA056012R1
Price
List Price £17,714.51 ex VAT
Your Price (ex VAT) Save 25%
£13,285.88 25% OFF
You save £4,428.63 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £13,285.88
Trade pricing is personalised to your account

Manufacturer Lead Time

£13,285.88

Why Choose the ABB E2S1600 PR122/P-LSI Air Circuit Breaker Moving Part?

The ABB E2S1600 PR122/P-LSI, order code 1SDA056012R1, is a high-performance four-pole withdrawable air circuit breaker moving part designed for switching and protection in demanding low-voltage power distribution systems. As part of the ABB SACE Emax E2 series, it combines a rated current of 1600 A with the advanced PR122/P-LSI electronic overcurrent release.

The PR122/P-LSI trip unit provides long-time, short-time and instantaneous protection, helping safeguard conductors, switchgear and connected equipment against overloads and short-circuit conditions. Its adjustable electronic protection functions support effective coordination within industrial, commercial and infrastructure power-distribution networks.

This version is supplied as the moving part of a withdrawable E2S1600 circuit breaker and is intended for use with the corresponding ABB Emax fixed part. Its four-pole construction, 1600 A current rating, 690 V AC rated operational voltage and high short-circuit performance make it suitable for critical switchboards and high-current distribution applications.

Key Advantages

  • High-performance ABB SACE Emax E2S air circuit breaker moving part.
  • 1600 A rated uninterrupted current for high-current distribution systems.
  • Four-pole configuration for comprehensive switching and isolation.
  • Advanced PR122/P-LSI electronic overcurrent release.
  • Long-time, short-time and instantaneous protection against overload and short-circuit conditions.
  • Withdrawable construction supports convenient isolation, servicing and maintenance.
  • 85 kA ultimate short-circuit breaking capacity at 400/415 V AC.
  • Four auxiliary change-over contacts support circuit-breaker status signalling and control integration.

Key Features

  • ABB SACE Emax E2S series.
  • 1600 A rated current.
  • Four-pole withdrawable moving part.
  • PR122/P-LSI R1600 electronic overcurrent release.
  • LSI protection functions: Long-time, Short-time and Instantaneous.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 85 kA Icu and Ics at 400/415 V AC.
  • 65 kA Icu and Ics at 690 V AC.
  • Four auxiliary change-over contacts.
  • Circuit-breaker open/closed position indication.

Reliable LSI Protection for High-Current Distribution

Air circuit breakers such as the ABB SACE Emax E2S1600 provide switching, isolation and fault protection for high-current low-voltage distribution systems. The E2S performance level offers substantial short-circuit interruption capability, making this breaker suitable for main switchboards and industrial installations where high prospective fault currents may occur.

The PR122/P-LSI electronic release provides long-time protection against sustained overloads, short-time protection for selective short-circuit coordination and instantaneous protection against severe fault currents. Combined with withdrawable construction and auxiliary status contacts, the E2S1600 moving part provides dependable protection together with practical serviceability in suitable Emax switchgear.

Typical Applications

  • Main low-voltage electrical distribution switchboards.
  • Industrial power distribution systems.
  • Manufacturing and process plant switchgear.
  • Commercial and infrastructure electrical distribution.
  • Transformer secondary distribution systems.
  • Generator and standby power installations.
  • High-current incoming and feeder protection.
  • Withdrawable switchgear requiring adjustable LSI protection.

Technical Specifications

Series SACE Emax E2
ABB order code 1SDA056012R1
Product type Air circuit breaker moving part
Frame / performance level E2S
Number of poles 4
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational current (Ie) 1600 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Trip unit PR122/P-LSI R1600
Release type Electronic
Protection functions LSI – Long-time, Short-time and Instantaneous
Overload release adjustment range 640–1600 A
Instantaneous short-circuit release adjustment range 2400–24000 A
Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 400/415 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 65 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 65 kA
Rated short-time withstand current (Icw), 1 s 65 kA
Rated short-time withstand current (Icw), 3 s 50 kA
Installation Withdrawable
Component Moving part
Auxiliary contacts 4 change-over contacts
Position indication Circuit breaker open / closed
Integrated earth-fault protection No
Motor operating mechanism Optional
Power loss 215 W
Mechanical durability 25,000 cycles
Standard IEC
EAN 8015644573522

Frequently Asked Questions

What is the ABB 1SDA056012R1?

The ABB 1SDA056012R1 is the moving part of a four-pole SACE Emax E2S1600 withdrawable air circuit breaker, rated at 1600 A and fitted with a PR122/P-LSI R1600 electronic overcurrent release.

What protection functions does the PR122/P-LSI provide?

The PR122/P-LSI provides long-time overload, short-time short-circuit and instantaneous short-circuit protection.

What is the rated current of ABB 1SDA056012R1?

The E2S1600 moving part has a rated uninterrupted current of 1600 A and uses a four-pole configuration.

Is ABB 1SDA056012R1 fixed or withdrawable?

ABB 1SDA056012R1 is the moving part of a withdrawable air circuit breaker and is designed for use with the corresponding ABB SACE Emax fixed part.

What is the breaking capacity of the E2S1600?

This E2S1600 configuration provides an ultimate short-circuit breaking capacity of 85 kA at 400/415 V AC and 65 kA at 690 V AC.

Trusted Protection for Critical Power Systems

ABB SACE Emax air circuit breakers combine high short-circuit performance, advanced electronic protection and serviceable withdrawable construction to provide dependable switching and protection for demanding low-voltage power distribution systems.