ABB 1SDA056011R1 is a SACE Emax E2S 1600 A four-pole withdrawable air circuit breaker moving part with a PR122/P-LI R1600 electronic overcurrent release providing long-time overload and instantaneous short-circuit protection.
£12,709.46
The ABB 1SDA056011R1 is a high-performance SACE Emax E2S 1600 air circuit breaker moving part designed for reliable switching and overcurrent protection in demanding low-voltage electrical distribution systems. Part of the ABB SACE Emax E2 series, this four-pole withdrawable circuit breaker moving part is equipped with a PR122/P-LI R1600 electronic overcurrent release.
With a rated uninterrupted current of 1600 A and a rated operational voltage of up to 690 V AC, the E2S 1600 is suitable for industrial switchboards, commercial distribution systems, transformer protection and other high-current applications. The PR122/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection for dependable protection of electrical distribution circuits.
The E2S performance level provides a rated ultimate short-circuit breaking capacity of 85 kA at 220–440 V AC and 65 kA at 500–690 V AC. This version is supplied as a four-pole withdrawable moving part (W MP) with four auxiliary contacts and open/closed position indication, supporting convenient maintenance and integration into compatible SACE Emax withdrawable switchgear.
Air circuit breakers such as the ABB SACE Emax E2S provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. The E2S 1600 combines substantial continuous-current capability with high short-circuit interruption performance, making it suitable for main switchboards and industrial distribution systems where dependable fault clearance and serviceability are important.
The PR122/P-LI electronic trip unit provides long-time overload and instantaneous short-circuit protection. Combined with the four-pole withdrawable SACE Emax construction, the 1SDA056011R1 provides dependable electronic protection while allowing the circuit breaker moving part to be withdrawn from its compatible fixed portion for inspection, servicing or replacement.
| Product family | SACE Emax |
|---|---|
| Series | E2S |
| ABB order code | 1SDA056011R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Rated uninterrupted current (Iu) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Execution | Withdrawable moving part (W MP) |
| Trip unit | PR122/P-LI R1600 |
| Release type | Electronic overcurrent release |
| Protection functions | LI – long-time overload and instantaneous short-circuit protection |
| Short-circuit performance level | S |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 85 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 85 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 65 kA |
| Rated short-time withstand current (Icw), 3 s | 50 kA |
| Power loss | 215 W |
| Electrical durability at ≤440 V | 12000 cycles |
| Electrical durability at 500–690 V | 10000 cycles |
| Mechanical durability | 25000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Net weight | 61 kg |
| EAN | 8015644573515 |
The ABB 1SDA056011R1 is a 1600 A four-pole air circuit breaker moving part designed for switching and electronic overcurrent protection in demanding low-voltage electrical distribution systems.
The ABB 1SDA056011R1 has a rated uninterrupted current of 1600 A and a rated operational voltage of up to 690 V AC.
The PR122/P-LI electronic trip unit provides LI protection functions consisting of long-time overload protection and instantaneous short-circuit protection.
The E2S 1600 provides a rated ultimate short-circuit breaking capacity of 85 kA at 220–440 V AC and 65 kA at 500–690 V AC, with a rated short-time withstand current of 65 kA for 1 s.
The ABB 1SDA056011R1 is a four-pole withdrawable moving part (W MP) designed for use with a compatible SACE Emax withdrawable fixed part.
ABB SACE Emax air circuit breakers are engineered to provide dependable switching, isolation and advanced electronic protection in demanding low-voltage power distribution systems, making the E2S 1600 a robust solution for industrial, commercial and infrastructure installations.