ABB 1SDA056001R1 E2S1600 PR121/P-LSI is a 1600 A three-pole withdrawable SACE Emax air circuit breaker moving part with an R1600 LSI electronic overcurrent release and 85 kA breaking capacity at 415 V AC for demanding low-voltage power distribution systems.
£9,632.77
The ABB E2S1600 PR121/P-LSI, order code 1SDA056001R1, is a high-performance three-pole withdrawable air circuit breaker moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax series, this E2S circuit breaker combines a rated current of 1600 A with the PR121/P electronic overcurrent release for dependable protection in industrial, commercial and infrastructure power networks.
This configuration is supplied as the withdrawable moving part (W MP) for use with a compatible SACE Emax withdrawable fixed part. The fitted PR121/P-LSI R1600 electronic overcurrent release provides long-time, short-time and instantaneous protection functions, helping protect electrical systems against sustained overloads and short-circuit faults while supporting selective protection coordination.
The E2S performance level provides an ultimate and service short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC, together with a short-time withstand current of 65 kA for 1 s. The breaker is fitted with four auxiliary contacts and open/closed position indication, supporting status signalling and integration into maintainable high-current switchboards.
Air circuit breakers such as the ABB SACE Emax E2S1600 provide switching, isolation and protection for high-current low-voltage distribution circuits. The E2S performance class combines high short-circuit interruption capability with robust short-time withstand performance, while the withdrawable architecture enables the moving circuit-breaker assembly to be removed from its compatible fixed part for inspection, servicing or replacement.
The PR121/P electronic overcurrent release provides LSI protection for demanding electrical networks. Long-time protection responds to sustained overload conditions, short-time protection supports selective coordination during fault events, and instantaneous protection rapidly interrupts severe short-circuit currents to help safeguard conductors, switchgear and connected electrical equipment.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA056001R1 |
| EAN | 8015644573416 |
| Product type | Air circuit breaker moving part |
| Frame / performance level | E2S |
| Short-circuit performance level | S |
| Rated current (In) | 1600 A |
| Rated operational current (Ie) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 3 |
| Current type | AC |
| Installation version | Withdrawable |
| Configuration | Moving part (MP) |
| Trip unit | PR121/P |
| Overcurrent release rating | R1600 |
| Release type | Electronic |
| Protection functions | LSI |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 400 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 500 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 65 kA |
| Short-time withstand current (Icw) for 1 s | 65 kA |
| Short-time withstand current (Icw) for 3 s | 50 kA |
| Terminal connection type | Withdrawable circuit breaker |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 215 W |
| Mechanical durability | 25,000 cycles |
| Electrical durability at ≤440 V | 12,000 cycles |
| Electrical durability at 500–690 V | 10,000 cycles |
| Dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Net weight | 49 kg |
| Standard | IEC |
| HS code | 85362090 |
| ABB product group | 310513-New Emax |
The ABB 1SDA056001R1 is a 1600 A three-pole withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems.
The PR121/P-LSI electronic overcurrent release provides long-time, short-time and instantaneous protection, commonly abbreviated as LSI, for protection against overload and short-circuit conditions.
The E2S1600 circuit breaker and its R1600 overcurrent release are rated at 1600 A.
The ABB 1SDA056001R1 is the withdrawable moving part of the E2S1600 circuit breaker and is designed for use with the corresponding SACE Emax withdrawable fixed part.
The E2S1600 provides an ultimate and service short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC, with a short-time withstand current of 65 kA for 1 s.
ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining high-current switching capability, electronic protection and maintainable withdrawable configurations for industrial, commercial and infrastructure electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.