ABB 1SDA055988R1 is a SACE Emax E2S 1600 A three-pole fixed air circuit breaker with rear horizontal terminals and a PR122/P-LSI electronic overcurrent release for high-current low-voltage power distribution protection.
£8,762.24
The ABB 1SDA055988R1 is a SACE Emax E2S 1600 air circuit breaker designed for dependable switching and overcurrent protection in demanding low-voltage power distribution systems. This three-pole fixed circuit breaker combines a 1600 A rated uninterrupted current with ABB's PR122/P-LSI electronic overcurrent release, providing long-time, short-time and instantaneous protection.
As part of the ABB SACE Emax range, the E2S 1600 offers high short-circuit performance for industrial and infrastructure distribution systems. Its PR122/P-LSI release provides an overload setting range of 640–1600 A, a short-time delayed short-circuit setting range of 960–16000 A and an instantaneous short-circuit setting range of 2400–24000 A.
This model is supplied in a three-pole fixed configuration with rear horizontal terminals and has an ultimate short-circuit breaking capacity of 85 kA at 400 V AC, 50 Hz. Its combination of a 1600 A current rating, E2S short-circuit performance and adjustable LSI protection makes it suitable for high-current switchboards, incoming supplies and major distribution feeders.
Air circuit breakers such as the ABB SACE Emax E2S provide switching, isolation and automatic overcurrent protection for high-current low-voltage distribution circuits. The electronic trip unit monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded, helping protect conductors, switchgear and connected equipment against damaging overload and short-circuit currents.
The PR122/P-LSI release gives this E2S 1600 long-time overload, short-time short-circuit and instantaneous short-circuit protection. The adjustable short-time function supports protection coordination and selectivity within distribution networks, while the 1600 A rating and 85 kA breaking capacity at 400 V AC make the ABB 1SDA055988R1 suitable for demanding high-current switchboard applications.
| Series | SACE Emax |
|---|---|
| ABB order code / MPN | 1SDA055988R1 |
| ABB product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Frame | E2S 1600 |
| Rated current (In) | 1600 A |
| Rated uninterrupted current (Iu) | 1600 A |
| Number of poles | 3 |
| Version | Fixed (F) |
| Main circuit connection | Rear horizontal terminals (HR) |
| Trip unit | PR122/P-LSI R1600 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Overload release setting range | 640–1600 A |
| Short-time delayed short-circuit setting range | 960–16000 A |
| Instantaneous short-circuit setting range | 2400–24000 A |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz | 85 kA |
| Short-circuit performance level | S |
| Integrated earth-fault protection | No |
| Degree of protection | IP2X |
| Motor drive | Optional |
| Auxiliary contacts | 2 NO + 2 NC |
| Trip indication | Yes |
| Product net weight | 55 kg |
| EAN | 8015644573287 |
The ABB 1SDA055988R1 is a SACE Emax E2S 1600 three-pole fixed air circuit breaker rated at 1600 A, with rear horizontal terminals and a PR122/P-LSI electronic overcurrent release.
The PR122/P-LSI provides long-time, short-time and instantaneous protection, collectively identified as LSI protection.
The ABB E2S 1600 has an ultimate short-circuit breaking capacity of 85 kA at 400 V AC, 50 Hz.
The ABB 1SDA055988R1 is a fixed (F) air circuit breaker with rear horizontal terminals for permanent installation within compatible low-voltage switchgear.
No. The PR122/P-LSI configuration provides long-time, short-time and instantaneous overcurrent protection. Integrated earth-fault protection is associated with LSIG configurations rather than this LSI version.
The overload release setting range is 640–1600 A, the short-time delayed short-circuit setting range is 960–16000 A, and the instantaneous short-circuit setting range is 2400–24000 A.
ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, supporting industrial, commercial and infrastructure installations where reliable high-current circuit protection is essential.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.