1SDA055981R1 ABB E2S1250 PR122/P-LSIG 1250 A 4-Pole Withdrawable Air Circuit Breaker

1SDA055981R1 ABB E2S1250 PR122/P-LSIG 1250 A 4-Pole Withdrawable Air Circuit Breaker

ABB 1SDA055981R1 is a SACE New Emax E2S1250 four-pole 1250 A withdrawable air circuit breaker moving part with a PR122/P-LSIG R1250 electronic release providing long-time, short-time, instantaneous and earth-fault protection.

SKU: 1SDA055981R1MPN: 1SDA055981R1
Price
List Price £15,829.84 ex VAT
Your Price (ex VAT) Save 25%
£11,872.38 25% OFF
You save £3,957.46 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,872.38
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,872.38

Why Choose the ABB E2S1250 1SDA055981R1 Air Circuit Breaker?

The ABB E2S1250 1SDA055981R1 is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the established ABB New Emax series, this E2S 1250 configuration features a four-pole withdrawable design, a rated current of 1250 A and a PR122/P-LSIG electronic overcurrent release.

Designed for industrial, commercial and infrastructure power distribution applications, the E2S1250 combines high short-circuit performance with the serviceability of a withdrawable breaker arrangement. The PR122/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection, supporting selective and comprehensive protection of critical electrical distribution circuits.

This version is supplied as the moving part for an E2S 1250 withdrawable circuit breaker and combines a 1250 A rated current with four-pole construction. The E2S performance level provides high fault-handling capability for demanding installations, while four auxiliary contacts and circuit breaker open/closed position indication support integration into switchgear control and signalling systems.

Key Advantages

  • High-performance ABB SACE Emax E2S air circuit breaker moving part for demanding low-voltage power distribution.
  • 1250 A rated current for substantial industrial, commercial and infrastructure electrical loads.
  • Four-pole withdrawable configuration supports flexible installation, servicing and maintenance.
  • PR122/P-LSIG electronic trip unit provides long-time, short-time, instantaneous and earth-fault protection.
  • E2S performance level provides high short-circuit capability for installations with substantial prospective fault currents.
  • Withdrawable construction enables convenient inspection and replacement within compatible ABB SACE Emax switchgear.

Key Features

  • ABB SACE New Emax E2S 1250 circuit breaker platform.
  • 1250 A rated current.
  • Four-pole construction.
  • Withdrawable moving-part configuration.
  • PR122/P-LSIG electronic overcurrent release.
  • R1250 / 1250 A release rating.
  • Long-time, short-time, instantaneous and earth-fault protection functions.
  • Four auxiliary contacts for switchgear signalling and control integration.
  • Circuit breaker open/closed position indication.
  • 25,000-cycle mechanical durability for demanding switchgear applications.

High-Performance LSIG Protection for Power Distribution

Air circuit breakers such as the ABB SACE Emax E2S1250 provide switching and protection for high-current low-voltage distribution circuits where substantial fault levels may be present. The E2S performance class combines high breaking capability with electronic trip technology, helping safeguard cables, busbars, switchgear and connected equipment against potentially damaging electrical faults.

The PR122/P-LSIG release provides L, S, I and G protection functions, covering long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the withdrawable four-pole SACE Emax architecture, this configuration is well suited to switchboards requiring comprehensive protection, selective coordination, high fault-handling capability and convenient maintenance.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical distribution.
  • Manufacturing and process plant switchgear.
  • Incoming and outgoing high-current feeder protection.
  • Four-pole distribution systems requiring withdrawable air circuit breakers with earth-fault protection.

Technical Specifications

Series SACE New Emax
ABB order code 1SDA055981R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Frame E2S 1250
Rated current 1250 A
Current type AC
Number of poles 4
Execution Withdrawable moving part
Trip unit PR122/P-LSIG
Release type Electronic
Release rating R1250 / 1250 A
Protection functions L (long-time), S (short-time), I (instantaneous) and G (earth fault)
Integrated earth-fault protection Yes
Short-circuit performance level S
Electrical durability 15,000 cycles at up to 690 V AC
Mechanical durability 25,000 cycles
Auxiliary contacts 4
Position indication Open / closed
Configuration Moving portion for withdrawable installation
Product dimensions 414 × 461 × 396.5 mm
Net weight 61 kg
EAN 8015644573218

Frequently Asked Questions

What is the ABB E2S1250 1SDA055981R1 used for?

The ABB 1SDA055981R1 is a SACE Emax E2S 1250 air circuit breaker moving part designed for switching and comprehensive overcurrent protection in demanding high-current low-voltage electrical distribution systems.

What is the rated current of the ABB E2S1250 1SDA055981R1?

The 1SDA055981R1 has a rated current of 1250 A and is equipped with an R1250 PR122/P-LSIG electronic overcurrent release.

Which trip unit is fitted to the ABB 1SDA055981R1?

The breaker is fitted with an ABB PR122/P-LSIG R1250 electronic overcurrent release, providing long-time, short-time, instantaneous and earth-fault protection.

What does LSIG protection mean on the ABB PR122/P trip unit?

LSIG denotes long-time overload protection, short-time short-circuit protection, instantaneous short-circuit protection and earth-fault protection, providing comprehensive protection for the connected low-voltage distribution system.

Is the ABB 1SDA055981R1 fixed or withdrawable?

The 1SDA055981R1 is the four-pole moving part of a withdrawable E2S 1250 circuit breaker and is intended for use with the appropriate compatible fixed part in an ABB SACE Emax installation.

Trusted Protection from ABB

ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution installations, combining advanced electronic protection technology with high short-circuit performance and serviceable switchgear integration.