ABB 1SDA055971R1 E2S1250 PR122/P-LI is a 1250 A three-pole withdrawable SACE Emax air circuit breaker moving part with an R1250 LI electronic overcurrent release, 85 kA breaking capacity at 415 V AC and four auxiliary contacts for demanding low-voltage power distribution systems.
£8,264.84
The ABB E2S1250 PR122/P-LI, order code 1SDA055971R1, is a high-performance three-pole withdrawable air circuit breaker moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax series, this E2S circuit breaker combines a rated current of 1250 A with the PR122/P electronic overcurrent release for dependable protection in industrial, commercial and infrastructure power networks.
This configuration is supplied as the withdrawable moving part (W MP) for a compatible SACE Emax withdrawable fixed part, allowing the breaker assembly to be withdrawn for inspection, servicing or replacement. The fitted PR122/P-LI R1250 electronic overcurrent release provides long-time and instantaneous protection functions, helping protect electrical systems against sustained overloads and severe short-circuit faults.
The E2S performance level provides an ultimate and service short-circuit breaking capacity of 85 kA at 415 V AC, together with a short-time withstand current of 65 kA for 1 s. Four auxiliary contacts and open/closed circuit-breaker position indication support status signalling and integration into low-voltage switchboards requiring maintainable withdrawable protection.
Air circuit breakers such as the ABB SACE Emax E2S1250 provide switching, isolation and protection for high-current low-voltage distribution circuits. The E2S performance class offers strong short-circuit interruption capability, while the withdrawable architecture is particularly useful where maintainability and service continuity are important because the moving circuit-breaker assembly can be withdrawn from its compatible fixed part.
The PR122/P electronic overcurrent release provides precise electronic protection for demanding electrical networks. In this LI configuration, long-time protection responds to sustained overload conditions while instantaneous protection rapidly responds to severe short-circuit currents, helping safeguard conductors, switchgear and connected electrical equipment.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA055971R1 |
| EAN | 8015644573119 |
| Product type | Air circuit breaker moving part |
| Frame / performance level | E2S |
| Short-circuit performance level | S |
| Rated current (In) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Number of poles | 3 |
| Current type | AC |
| Installation version | Withdrawable |
| Configuration | Moving part (MP) |
| Trip unit | PR122/P |
| Overcurrent release rating | R1250 |
| Release type | Electronic |
| Protection functions | LI |
| Long-time protection | L |
| Instantaneous protection | I |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 85 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 85 kA |
| Ultimate short-circuit breaking capacity (Icu) at 500 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 65 kA |
| Short-time withstand current (Icw) for 1 s | 65 kA |
| Short-time withstand current (Icw) for 3 s | 50 kA |
| Terminal connection type | Withdrawable circuit breaker |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 130 W |
| Mechanical durability | 25,000 cycles |
| Electrical durability at ≤440 V | 15,000 cycles |
| Electrical durability at 500–690 V | 15,000 cycles |
| Dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Net weight | 49 kg |
| Standard | IEC |
| HS code | 85362090 |
| ABB product group | 310513-New Emax |
The ABB 1SDA055971R1 is a 1250 A three-pole withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems.
The PR122/P-LI electronic overcurrent release provides long-time and instantaneous protection, commonly abbreviated as LI, for protection against overload and short-circuit conditions.
The E2S1250 circuit breaker and its R1250 overcurrent release are rated at 1250 A.
The ABB 1SDA055971R1 is the withdrawable moving part of the E2S1250 circuit breaker and is designed for use with the corresponding SACE Emax withdrawable fixed part.
The E2S1250 provides an ultimate and service short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC, with a short-time withstand current of 65 kA for 1 s.
ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining high-current switching capability, electronic protection and maintainable withdrawable configurations for industrial, commercial and infrastructure electrical systems.
We use cookies