1SDA055971R1 ABB E2S1250 PR122/P-LI 1250A 3-Pole Withdrawable Air Circuit Breaker

1SDA055971R1 ABB E2S1250 PR122/P-LI 1250A 3-Pole Withdrawable Air Circuit Breaker

ABB 1SDA055971R1 E2S1250 PR122/P-LI is a 1250 A three-pole withdrawable SACE Emax air circuit breaker moving part with an R1250 LI electronic overcurrent release, 85 kA breaking capacity at 415 V AC and four auxiliary contacts for demanding low-voltage power distribution systems.

SKU: 1SDA055971R1MPN: 1SDA055971R1
Price
List Price £11,019.79 ex VAT
Your Price (ex VAT) Save 25%
£8,264.84 25% OFF
You save £2,754.95 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,264.84
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,264.84

Why Choose the ABB E2S1250 PR122/P-LI 1250A Air Circuit Breaker?

The ABB E2S1250 PR122/P-LI, order code 1SDA055971R1, is a high-performance three-pole withdrawable air circuit breaker moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Part of the established ABB SACE Emax series, this E2S circuit breaker combines a rated current of 1250 A with the PR122/P electronic overcurrent release for dependable protection in industrial, commercial and infrastructure power networks.

This configuration is supplied as the withdrawable moving part (W MP) for a compatible SACE Emax withdrawable fixed part, allowing the breaker assembly to be withdrawn for inspection, servicing or replacement. The fitted PR122/P-LI R1250 electronic overcurrent release provides long-time and instantaneous protection functions, helping protect electrical systems against sustained overloads and severe short-circuit faults.

The E2S performance level provides an ultimate and service short-circuit breaking capacity of 85 kA at 415 V AC, together with a short-time withstand current of 65 kA for 1 s. Four auxiliary contacts and open/closed circuit-breaker position indication support status signalling and integration into low-voltage switchboards requiring maintainable withdrawable protection.

Key Advantages

  • High-performance ABB SACE Emax E2S air circuit breaker moving part for low-voltage power distribution.
  • 1250 A rated current for demanding industrial and commercial distribution applications.
  • Three-pole withdrawable configuration for three-phase electrical systems.
  • PR122/P-LI electronic overcurrent release for accurate circuit protection.
  • Long-time and instantaneous protection against overload and short-circuit conditions.
  • 85 kA ultimate and service short-circuit breaking capacity at 415 V AC.
  • 65 kA short-time withstand current for 1 s for robust fault-current performance.
  • Withdrawable moving-part design supports efficient inspection, maintenance and replacement.

Key Features

  • ABB SACE Emax E2S series.
  • 1250 A rated uninterrupted current.
  • Three-pole construction.
  • Withdrawable moving part (W MP).
  • PR122/P electronic overcurrent release.
  • R1250 release rating.
  • LI protection: long-time and instantaneous.
  • 690 V AC rated operational voltage.
  • 85 kA breaking capacity at 415 V AC.
  • 65 kA breaking capacity at 690 V AC.
  • Four auxiliary contacts for status signalling.
  • Open/closed circuit-breaker position indication.

Advanced Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E2S1250 provide switching, isolation and protection for high-current low-voltage distribution circuits. The E2S performance class offers strong short-circuit interruption capability, while the withdrawable architecture is particularly useful where maintainability and service continuity are important because the moving circuit-breaker assembly can be withdrawn from its compatible fixed part.

The PR122/P electronic overcurrent release provides precise electronic protection for demanding electrical networks. In this LI configuration, long-time protection responds to sustained overload conditions while instantaneous protection rapidly responds to severe short-circuit currents, helping safeguard conductors, switchgear and connected electrical equipment.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Main incomer and feeder circuit protection.
  • Manufacturing and process plants.
  • Commercial buildings and infrastructure installations.
  • Motor control centres and power distribution assemblies.
  • Transformer secondary and generator distribution circuits.
  • Switchgear requiring withdrawable circuit-breaker architecture for maintenance flexibility.

Technical Specifications

Series SACE Emax
ABB order code 1SDA055971R1
EAN 8015644573119
Product type Air circuit breaker moving part
Frame / performance level E2S
Short-circuit performance level S
Rated current (In) 1250 A
Rated operational current (Ie) 1250 A
Rated uninterrupted current (Iu) 1250 A
Number of poles 3
Current type AC
Installation version Withdrawable
Configuration Moving part (MP)
Trip unit PR122/P
Overcurrent release rating R1250
Release type Electronic
Protection functions LI
Long-time protection L
Instantaneous protection I
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Ultimate short-circuit breaking capacity (Icu) at 400 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 85 kA
Service short-circuit breaking capacity (Ics) at 415 V AC 85 kA
Ultimate short-circuit breaking capacity (Icu) at 500 V AC 65 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 65 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 65 kA
Short-time withstand current (Icw) for 1 s 65 kA
Short-time withstand current (Icw) for 3 s 50 kA
Terminal connection type Withdrawable circuit breaker
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Power loss 130 W
Mechanical durability 25,000 cycles
Electrical durability at ≤440 V 15,000 cycles
Electrical durability at 500–690 V 15,000 cycles
Dimensions (W × H × D) 324 × 461 × 396.5 mm
Net weight 49 kg
Standard IEC
HS code 85362090
ABB product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA055971R1 used for?

The ABB 1SDA055971R1 is a 1250 A three-pole withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems.

What protection functions does the PR122/P-LI trip unit provide?

The PR122/P-LI electronic overcurrent release provides long-time and instantaneous protection, commonly abbreviated as LI, for protection against overload and short-circuit conditions.

What is the rated current of the ABB E2S1250 PR122/P-LI?

The E2S1250 circuit breaker and its R1250 overcurrent release are rated at 1250 A.

Is the ABB 1SDA055971R1 fixed or withdrawable?

The ABB 1SDA055971R1 is the withdrawable moving part of the E2S1250 circuit breaker and is designed for use with the corresponding SACE Emax withdrawable fixed part.

What is the breaking capacity of the ABB E2S1250?

The E2S1250 provides an ultimate and service short-circuit breaking capacity of 85 kA at 415 V AC and 65 kA at 690 V AC, with a short-time withstand current of 65 kA for 1 s.

Trusted Protection for Critical Power Systems

ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining high-current switching capability, electronic protection and maintainable withdrawable configurations for industrial, commercial and infrastructure electrical systems.