1SDA055949R1 ABB E2N2000 PR122/P-LSIG 2000 A 4-Pole Withdrawable Air Circuit Breaker

1SDA055949R1 ABB E2N2000 PR122/P-LSIG 2000 A 4-Pole Withdrawable Air Circuit Breaker

ABB 1SDA055949R1 is a SACE New Emax E2N2000 four-pole 2000 A withdrawable air circuit breaker moving part with a PR122/P-LSIG R2000 electronic release providing long-time, short-time, instantaneous and earth-fault protection.

SKU: 1SDA055949R1Alt SKU: E2N 2000 4P DRAWOUMPN: 1SDA055949R1
Price
List Price £21,542.08 ex VAT
Your Price (ex VAT) Save 25%
£16,156.56 25% OFF
You save £5,385.52 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £16,156.56
Trade pricing is personalised to your account

Manufacturer Lead Time

£16,156.56

Why Choose the ABB E2N2000 1SDA055949R1 Air Circuit Breaker?

The ABB E2N2000 1SDA055949R1 is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the established ABB New Emax series, this E2N 2000 configuration features a four-pole withdrawable design, a rated current of 2000 A and a PR122/P-LSIG electronic overcurrent release.

Designed for industrial, commercial and infrastructure power distribution applications, the E2N2000 combines dependable high-current circuit protection with the serviceability of a withdrawable breaker arrangement. The PR122/P-LSIG electronic trip unit provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection, delivering comprehensive protection for critical electrical distribution circuits.

This version is supplied as the moving part for an E2N 2000 withdrawable circuit breaker and combines a 2000 A rated current with four-pole construction and a rated voltage of 690 V AC. The E2N performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, 50 Hz, while four change-over auxiliary contacts and open/closed position indication support integration into switchgear control and signalling systems.

Key Advantages

  • High-performance ABB SACE Emax air circuit breaker moving part for demanding low-voltage power distribution.
  • 2000 A rated current for substantial industrial and commercial electrical loads.
  • Four-pole withdrawable configuration supports flexible installation, servicing and maintenance.
  • PR122/P-LSIG electronic trip unit provides long-time, short-time, instantaneous and earth-fault protection.
  • 65 kA rated ultimate short-circuit breaking capacity at 400 V AC, 50 Hz.
  • Withdrawable construction supports convenient inspection and replacement within compatible ABB SACE Emax switchgear.

Key Features

  • ABB SACE New Emax E2N 2000 circuit breaker platform.
  • 2000 A rated current.
  • Four-pole construction.
  • Withdrawable moving-part configuration.
  • PR122/P-LSIG electronic overcurrent release.
  • R2000 / 2000 A release rating.
  • Long-time, short-time, instantaneous and earth-fault protection functions.
  • 690 V AC rated voltage.
  • Four change-over auxiliary contacts and circuit breaker open/closed position indication.
  • Optional motor drive for electrically operated applications.

Reliable Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E2N2000 provide switching and protection for high-current low-voltage distribution circuits. Electronic trip technology enables abnormal current conditions to be detected accurately, allowing the breaker to disconnect the protected circuit according to configured protection parameters and helping safeguard cables, switchgear and connected equipment.

The PR122/P-LSIG release provides L, S, I and G protection functions, covering long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the withdrawable SACE Emax architecture and four-pole construction, this configuration is well suited to switchboards requiring comprehensive high-current protection, selective coordination, maintainability and operational flexibility.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical distribution.
  • Manufacturing and process plant switchgear.
  • Incoming and outgoing high-current feeder protection.
  • Four-pole distribution systems requiring withdrawable air circuit breakers with earth-fault protection.

Technical Specifications

Series SACE New Emax
ABB order code 1SDA055949R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Frame E2N 2000
Rated current 2000 A
Rated permanent current 2000 A
Rated voltage 690 V AC
Number of poles 4
Execution Withdrawable moving part
Trip unit PR122/P-LSIG
Release type Electronic
Release rating R2000 / 2000 A
Protection functions L (long-time), S (short-time), I (instantaneous) and G (earth fault)
Overload release setting range 800–2000 A
Short-time short-circuit protection Adjustable
Instantaneous short-circuit release setting range 3000–30000 A
Rated ultimate short-circuit breaking capacity 65 kA at 400 V AC, 50 Hz
Integrated earth-fault protection Yes
Short-circuit performance level N
Auxiliary contacts 4 change-over contacts
Position indication Open / closed
Motor drive integrated No
Motor drive Optional
Configuration Moving portion for withdrawable installation
Standard IEC
Net weight approx. 73 kg
EAN 8015644572891

Frequently Asked Questions

What is the ABB E2N2000 1SDA055949R1 used for?

The ABB 1SDA055949R1 is a SACE Emax E2N 2000 air circuit breaker moving part designed for switching and comprehensive overcurrent protection in high-current low-voltage electrical distribution systems.

What is the rated current of the ABB E2N2000 1SDA055949R1?

The 1SDA055949R1 has a rated current of 2000 A and is equipped with an R2000 PR122/P-LSIG electronic overcurrent release.

Which trip unit is fitted to the ABB 1SDA055949R1?

The breaker is fitted with an ABB PR122/P-LSIG R2000 electronic overcurrent release, providing long-time, short-time, instantaneous and earth-fault protection.

What is the breaking capacity of the ABB E2N2000 1SDA055949R1?

The E2N2000 has a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, 50 Hz, providing robust short-circuit protection for demanding low-voltage distribution systems.

Is the ABB 1SDA055949R1 fixed or withdrawable?

The 1SDA055949R1 is the four-pole moving part of a withdrawable E2N 2000 circuit breaker and is intended for use with the appropriate compatible fixed part in an ABB SACE Emax installation.

Trusted Protection from ABB

ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution installations, combining advanced electronic protection technology with flexible and serviceable switchgear integration.