Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055946R1 SACE Emax E2N 2000 is a 2000 A four-pole withdrawable air circuit breaker moving part with a PR121/P-LSIG electronic release and 65 kA short-circuit breaking capacity at 400/415 V AC.
£16,008.08
The ABB 1SDA055946R1 is a SACE Emax E2N 2000 moving part for a withdrawable air circuit breaker, engineered for high-current switching and comprehensive protection in demanding low-voltage AC power distribution systems. This four-pole unit has a rated current of 2000 A and is equipped with a PR121/P-LSIG R2000 electronic overcurrent release.
The PR121/P-LSIG release provides long-time, short-time, instantaneous and earth-fault protection, helping protect distribution circuits against overloads, delayed and severe short circuits, and earth-fault conditions. The E2N performance level provides rated ultimate and service short-circuit breaking capacities of 65 kA at 400/415 V AC, with substantial fault-interruption capability maintained at higher operating voltages.
The 1SDA055946R1 is a four-pole withdrawable (W) moving part designed for use with the corresponding compatible SACE Emax fixed part. Its withdrawable construction supports efficient inspection, maintenance and replacement within critical switchboards, while four auxiliary contacts and circuit-breaker open/closed position indication facilitate integration with monitoring and control systems.
The ABB SACE Emax E2N 2000 provides dependable switching and electronic protection for high-current low-voltage distribution circuits. Its PR121/P-LSIG electronic release combines long-time protection against sustained overloads, short-time protection for selective fault coordination, instantaneous protection against severe short circuits and earth-fault protection for faults involving earth or protective conductors.
The withdrawable construction allows the circuit-breaker moving part to be removed from its compatible fixed part, supporting inspection, maintenance and replacement strategies in critical switchboards. Combined with a 2000 A rating, four-pole configuration and 65 kA short-circuit breaking capacity at 400/415 V AC, the 1SDA055946R1 is well suited to main incoming and high-current feeder duties requiring comprehensive protection and serviceable switchgear construction.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA055946R1 |
| Extended product type | E2N2000PR121/P-LSIGIn=2000A4pWMP |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E2 |
| Short-circuit performance level | N |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Number of poles | 4 |
| Current type | AC |
| Rated operational voltage (Ue) | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 400/415 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 55 kA |
| Rated short-time withstand current (Icw) | 55 kA for 1 s |
| Release | PR121/P-LSIG R2000 |
| Release type | Electronic |
| Protection functions | LSIG – long-time, short-time, instantaneous and earth-fault |
| Long-time protection (L) | Overload protection |
| Overload release adjustment range | 800–2000 A |
| Short-time protection (S) | Delayed short-circuit protection |
| Short-time short-circuit adjustment range | 2000–20000 A |
| Instantaneous protection (I) | Instantaneous short-circuit protection |
| Instantaneous short-circuit adjustment range | 3000–30000 A |
| Earth-fault protection (G) | Integrated |
| Version | Withdrawable |
| Configuration | Moving part |
| Auxiliary contacts | 4 total, 2 NO + 2 NC |
| Position indication | Circuit breaker open / closed |
| Trip indication | Yes |
| Motor operating mechanism | Optional |
| Degree of protection | IP2X |
| Power loss | 330 W |
| Mechanical durability | 25,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Electrical durability at ≤440 V | 10,000 cycles |
| Electrical durability at 500–690 V | 8,000 cycles |
| Electrical operating frequency | 30 cycles per hour |
| Product dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Net weight | 61 kg |
| Standard | IEC |
| EAN | 8015644572860 |
The ABB 1SDA055946R1 is the moving part of a four-pole SACE Emax E2N 2000 withdrawable air circuit breaker, rated at 2000 A and fitted with a PR121/P-LSIG R2000 electronic overcurrent release.
The breaker is fitted with a PR121/P-LSIG R2000 electronic release, providing long-time, short-time, instantaneous and earth-fault protection.
LSIG denotes long-time, short-time, instantaneous and earth-fault protection. Together these functions protect against sustained overloads, delayed and severe short-circuit faults, and earth-fault conditions.
The 1SDA055946R1 is a withdrawable circuit-breaker moving part designed for installation with the corresponding compatible ABB SACE Emax fixed part.
The E2N 2000 provides rated ultimate and service short-circuit breaking capacities of 65 kA at 400/415 V AC and 55 kA at 500–690 V AC, with a rated short-time withstand current of 55 kA for 1 s.
ABB SACE Emax air circuit breakers provide robust switching and electronic protection for low-voltage power distribution, combining high short-circuit performance, comprehensive LSIG protection and serviceable withdrawable construction for demanding industrial and infrastructure applications.
We use cookies