ABB 1SDA055939R1 is a SACE Emax E2N 2000 A three-pole withdrawable air circuit breaker moving part with a PR122/P-LI electronic overcurrent release for high-current low-voltage power distribution protection.
£11,794.17
The ABB 1SDA055939R1 is a SACE Emax E2N 2000 withdrawable air circuit breaker moving part designed for dependable switching and protection in high-current low-voltage power distribution systems. This three-pole unit combines a 2000 A rated current with ABB's PR122/P-LI electronic overcurrent release, providing long-time overload and instantaneous short-circuit protection for demanding industrial, commercial and infrastructure installations.
As part of the ABB SACE Emax range, the E2N 2000 is engineered for protection of switchboards, transformers, generators and high-current distribution feeders. The PR122/P-LI release provides electronic LI protection, with an overload setting range of 800–2000 A and an instantaneous short-circuit release adjustment range of 3000–30000 A.
This model is supplied as the moving part of a three-pole withdrawable circuit breaker. It has a rated operational voltage of 690 V AC, an ultimate short-circuit breaking capacity of 65 kA at 400 V AC and a short-time withstand current of 55 kA for 1 s, providing robust performance for high-current switchgear applications.
Air circuit breakers such as the ABB SACE Emax E2N provide switching, isolation and automatic overcurrent protection for high-current low-voltage distribution circuits. The electronic trip unit monitors circuit current and initiates breaker operation when configured protection thresholds are exceeded, helping protect switchgear, conductors and connected electrical equipment against damaging overload and short-circuit currents.
The PR122/P-LI release gives this E2N 2000 long-time overload and instantaneous short-circuit protection. Combined with its 2000 A rating, three-pole arrangement, withdrawable construction and high short-circuit performance, the ABB 1SDA055939R1 is well suited to demanding high-current switchboard installations where maintainability and dependable circuit protection are essential.
| Series | SACE Emax |
|---|---|
| ABB order code / MPN | 1SDA055939R1 |
| ABB product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame | E2N 2000 |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Number of poles | 3 |
| Version | Withdrawable (W) moving part |
| Trip unit | PR122/P-LI |
| Release type | Electronic |
| Protection functions | Long-time and instantaneous (LI) |
| Overload release setting range | 800–2000 A |
| Instantaneous short-circuit release setting range | 3000–30000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 400/415 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 55 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 55 kA |
| Short-time withstand current (Icw), 1 s | 55 kA |
| Short-time withstand current (Icw), 3 s | 42 kA |
| Short-circuit performance level | N |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Integrated earth-fault protection | No |
| Motor drive integrated | No |
| Motor drive optional | Yes |
| Mechanical durability | 25,000 cycles |
| Electrical durability at ≤440 V | 10,000 cycles |
| Electrical durability at 500–690 V | 8,000 cycles |
| Power loss | 330 W |
| Standard | IEC |
| Product net dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Product net weight | 49 kg |
| EAN | 8015644572792 |
The ABB 1SDA055939R1 is the moving part of a SACE Emax E2N 2000 three-pole withdrawable air circuit breaker, rated at 2000 A and equipped with a PR122/P-LI electronic overcurrent release.
The PR122/P-LI provides long-time overload and instantaneous short-circuit protection, collectively identified as LI protection.
The ABB 1SDA055939R1 is a withdrawable (W) version supplied as the moving part of the E2N 2000 circuit breaker system.
The circuit breaker moving part has a rated uninterrupted current of 2000 A and a rated operational voltage of 690 V AC.
The E2N 2000 provides an ultimate short-circuit breaking capacity of 65 kA at 400/415 V AC and 55 kA at 690 V AC.
No. This model uses the PR122/P-LI release for long-time and instantaneous protection. Earth-fault protection is not integrated into this LI configuration.
ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, supporting industrial, commercial and infrastructure installations where reliable high-current circuit protection is essential.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.