Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055937R1 E2N2000 PR121/P-LSI is a 2000 A three-pole withdrawable SACE Emax air circuit breaker moving part with LSI electronic protection and 65 kA breaking capacity at 415 V AC for high-current low-voltage power distribution systems.
£11,791.56
The ABB E2N2000 PR121/P-LSI, order code 1SDA055937R1, is a high-performance three-pole withdrawable air circuit breaker moving part designed for protection and switching in low-voltage electrical distribution systems. As part of the proven ABB SACE Emax series, this E2N circuit breaker combines a 2000 A rated current with the PR121/P electronic overcurrent release for dependable protection in demanding industrial, commercial and infrastructure power installations.
This configuration is supplied as the withdrawable moving part (W MP) of the circuit breaker, allowing the breaker assembly to be withdrawn from its compatible fixed cradle for inspection, servicing and replacement. The integrated PR121/P-LSI electronic overcurrent release provides long-time, short-time and instantaneous protection functions, helping protect electrical networks against sustained overloads and short-circuit faults.
With a rated uninterrupted current of 2000 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 65 kA at 415 V AC, the E2N2000 is suited to demanding high-current distribution applications. Its withdrawable architecture, four auxiliary contacts and circuit-breaker open/closed position indication support maintainable integration into low-voltage switchboards and power distribution assemblies.
Air circuit breakers such as the ABB SACE Emax E2N2000 provide switching, isolation and protection for high-current low-voltage distribution circuits. Withdrawable configurations are particularly useful in installations where maintainability and service continuity are important because the moving circuit-breaker assembly can be withdrawn from its compatible fixed cradle for inspection, servicing or replacement.
The PR121/P electronic overcurrent release provides LSI protection for demanding electrical networks. Long-time protection responds to sustained overload conditions, while short-time and instantaneous functions provide protection against short-circuit currents, helping coordinate protection and safeguard conductors, switchgear and connected electrical equipment.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA055937R1 |
| EAN | 8015644572778 |
| Product type | Air circuit breaker moving part |
| Frame / performance level | E2N |
| Short-circuit performance level | N |
| Rated current | 2000 A |
| Rated operational current | 2000 A |
| Rated uninterrupted current | 2000 A |
| Number of poles | 3 |
| Current type | AC |
| Installation version | Withdrawable |
| Configuration | Moving part (MP) |
| Trip unit | PR121/P |
| Overcurrent release rating | R2000 |
| Release type | Electronic |
| Protection functions | LSI |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Overload adjustment range | 800–2000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 55 kA |
| Service short-circuit breaking capacity (Ics) at 690 V AC | 55 kA |
| Short-time withstand current (Icw) for 1 s | 55 kA |
| Short-time withstand current (Icw) for 3 s | 42 kA |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 330 W |
| Mechanical durability | 25,000 cycles |
| Electrical durability at ≤440 V | 10,000 cycles |
| Electrical durability at 500–690 V | 8,000 cycles |
| Dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Net weight | 49 kg |
| Standard | IEC |
| ABB product group | 310513-New Emax |
The ABB 1SDA055937R1 is a 2000 A three-pole withdrawable air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution systems.
The PR121/P-LSI electronic overcurrent release provides long-time, short-time and instantaneous protection, commonly abbreviated as LSI.
The E2N2000 PR121/P-LSI has a rated current of 2000 A.
This model is the withdrawable moving part (W MP) of the E2N2000 circuit breaker and is intended for use with the corresponding withdrawable installation system.
The ABB E2N2000 provides an ultimate short-circuit breaking capacity of 65 kA at 415 V AC and 55 kA at 690 V AC.
ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining high-current switching capability, electronic protection and maintainable withdrawable configurations for industrial, commercial and infrastructure electrical systems.
We use cookies