1SDA055937R1 ABB E2N2000 PR121/P-LSI 2000A 3-Pole Withdrawable Air Circuit Breaker

1SDA055937R1 ABB E2N2000 PR121/P-LSI 2000A 3-Pole Withdrawable Air Circuit Breaker

ABB 1SDA055937R1 E2N2000 PR121/P-LSI is a 2000 A three-pole withdrawable SACE Emax air circuit breaker moving part with LSI electronic protection and 65 kA breaking capacity at 415 V AC for high-current low-voltage power distribution systems.

SKU: 1SDA055937R1Alt SKU: E2N2000AMPN: 1SDA055937R1
Price
List Price £15,722.08 ex VAT
Your Price (ex VAT) Save 25%
£11,791.56 25% OFF
You save £3,930.52 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,791.56
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,791.56

Why Choose the ABB E2N2000 PR121/P-LSI 2000A Air Circuit Breaker?

The ABB E2N2000 PR121/P-LSI, order code 1SDA055937R1, is a high-performance three-pole withdrawable air circuit breaker moving part designed for protection and switching in low-voltage electrical distribution systems. As part of the proven ABB SACE Emax series, this E2N circuit breaker combines a 2000 A rated current with the PR121/P electronic overcurrent release for dependable protection in demanding industrial, commercial and infrastructure power installations.

This configuration is supplied as the withdrawable moving part (W MP) of the circuit breaker, allowing the breaker assembly to be withdrawn from its compatible fixed cradle for inspection, servicing and replacement. The integrated PR121/P-LSI electronic overcurrent release provides long-time, short-time and instantaneous protection functions, helping protect electrical networks against sustained overloads and short-circuit faults.

With a rated uninterrupted current of 2000 A, a rated operational voltage of 690 V AC and an ultimate short-circuit breaking capacity of 65 kA at 415 V AC, the E2N2000 is suited to demanding high-current distribution applications. Its withdrawable architecture, four auxiliary contacts and circuit-breaker open/closed position indication support maintainable integration into low-voltage switchboards and power distribution assemblies.

Key Advantages

  • High-performance ABB SACE Emax air circuit breaker moving part for low-voltage power distribution.
  • 2000 A rated current for demanding high-current installations.
  • Three-pole withdrawable configuration for three-phase electrical distribution systems.
  • PR121/P-LSI electronic overcurrent release for comprehensive overcurrent protection.
  • Long-time, short-time and instantaneous protection against overload and short-circuit conditions.
  • 65 kA ultimate short-circuit breaking capacity at 415 V AC.
  • 55 kA short-time withstand current for 1 s for robust fault-current performance.
  • Withdrawable moving-part design supports efficient inspection, maintenance and replacement.

Key Features

  • ABB SACE Emax E2N series.
  • 2000 A rated current.
  • Three-pole construction.
  • Withdrawable moving part (W MP).
  • PR121/P-LSI R2000 electronic overcurrent release.
  • LSI protection: long-time, short-time and instantaneous.
  • 690 V AC rated operational voltage.
  • 65 kA ultimate and service short-circuit breaking capacity at 415 V AC.
  • 55 kA ultimate and service short-circuit breaking capacity at 690 V AC.
  • 55 kA short-time withstand current for 1 s.
  • Four auxiliary contacts for circuit-breaker status signalling.
  • Open/closed circuit-breaker position indication.

Advanced Protection for Low-Voltage Power Distribution

Air circuit breakers such as the ABB SACE Emax E2N2000 provide switching, isolation and protection for high-current low-voltage distribution circuits. Withdrawable configurations are particularly useful in installations where maintainability and service continuity are important because the moving circuit-breaker assembly can be withdrawn from its compatible fixed cradle for inspection, servicing or replacement.

The PR121/P electronic overcurrent release provides LSI protection for demanding electrical networks. Long-time protection responds to sustained overload conditions, while short-time and instantaneous functions provide protection against short-circuit currents, helping coordinate protection and safeguard conductors, switchgear and connected electrical equipment.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Main incomer and high-current feeder protection.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical systems.
  • Motor control centres and power distribution assemblies.
  • Transformer secondary and generator distribution circuits.
  • Switchgear requiring withdrawable circuit-breaker architecture for maintenance flexibility.

Technical Specifications

Series SACE Emax
ABB order code 1SDA055937R1
EAN 8015644572778
Product type Air circuit breaker moving part
Frame / performance level E2N
Short-circuit performance level N
Rated current 2000 A
Rated operational current 2000 A
Rated uninterrupted current 2000 A
Number of poles 3
Current type AC
Installation version Withdrawable
Configuration Moving part (MP)
Trip unit PR121/P
Overcurrent release rating R2000
Release type Electronic
Protection functions LSI
Long-time protection L
Short-time protection S
Instantaneous protection I
Overload adjustment range 800–2000 A
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Ultimate short-circuit breaking capacity (Icu) at 415 V AC 65 kA
Service short-circuit breaking capacity (Ics) at 415 V AC 65 kA
Ultimate short-circuit breaking capacity (Icu) at 690 V AC 55 kA
Service short-circuit breaking capacity (Ics) at 690 V AC 55 kA
Short-time withstand current (Icw) for 1 s 55 kA
Short-time withstand current (Icw) for 3 s 42 kA
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Power loss 330 W
Mechanical durability 25,000 cycles
Electrical durability at ≤440 V 10,000 cycles
Electrical durability at 500–690 V 8,000 cycles
Dimensions (W × H × D) 324 × 461 × 396.5 mm
Net weight 49 kg
Standard IEC
ABB product group 310513-New Emax

Frequently Asked Questions

What is the ABB 1SDA055937R1 used for?

The ABB 1SDA055937R1 is a 2000 A three-pole withdrawable air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution systems.

What protection functions does the PR121/P-LSI trip unit provide?

The PR121/P-LSI electronic overcurrent release provides long-time, short-time and instantaneous protection, commonly abbreviated as LSI.

What is the rated current of this circuit breaker?

The E2N2000 PR121/P-LSI has a rated current of 2000 A.

Is the ABB 1SDA055937R1 fixed or withdrawable?

This model is the withdrawable moving part (W MP) of the E2N2000 circuit breaker and is intended for use with the corresponding withdrawable installation system.

What is the breaking capacity of the E2N2000 circuit breaker?

The ABB E2N2000 provides an ultimate short-circuit breaking capacity of 65 kA at 415 V AC and 55 kA at 690 V AC.

Trusted Protection for Critical Power Systems

ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining high-current switching capability, electronic protection and maintainable withdrawable configurations for industrial, commercial and infrastructure electrical systems.