1SDA055929R1 ABB E2N 2000 PR121/P-LSI 2000 A 4-Pole Air Circuit Breaker

1SDA055929R1 ABB E2N 2000 PR121/P-LSI 2000 A 4-Pole Air Circuit Breaker

ABB 1SDA055929R1 SACE Emax E2N 2000 is a 2000 A four-pole fixed air circuit breaker with rear horizontal terminals, a PR121/P-LSI electronic release and 65 kA ultimate short-circuit breaking capacity at 400 V AC.

SKU: 1SDA055929R1Alt SKU: E2NMPN: 1SDA055929R1
Price
List Price £18,589.95 ex VAT
Your Price (ex VAT) Save 25%
£13,942.46 25% OFF
You save £4,647.49 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £13,942.46
Trade pricing is personalised to your account

Manufacturer Lead Time

£13,942.46

Why Choose the ABB 1SDA055929R1 E2N 2000 Air Circuit Breaker?

The ABB 1SDA055929R1 is a SACE Emax E2N 2000 air circuit breaker designed for high-current switching and selective overcurrent protection in demanding low-voltage AC power distribution systems. This four-pole fixed circuit breaker has a rated uninterrupted current of 2000 A and is equipped with a PR121/P-LSI R2000 electronic overcurrent release.

The PR121/P-LSI release provides long-time, short-time and instantaneous protection, allowing the breaker to respond to sustained overloads and both delayed and severe short-circuit conditions. The E2N performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, supporting use in industrial and infrastructure distribution systems with substantial prospective fault currents.

The 1SDA055929R1 is a four-pole fixed (F) circuit breaker with rear horizontal (HR) terminals for permanent installation in compatible low-voltage switchboards. It is supplied with four auxiliary contacts and circuit-breaker open/closed position indication, providing useful status information for switchboard signalling, monitoring and control circuits.

Key Advantages

  • High-current 2000 A E2N air circuit breaker for demanding low-voltage power distribution.
  • PR121/P-LSI R2000 electronic release provides long-time, short-time and instantaneous overcurrent protection.
  • 65 kA rated ultimate short-circuit breaking capacity at 400 V AC.
  • Four-pole configuration supports three-phase distribution systems requiring neutral switching.
  • Fixed construction provides robust permanent integration into low-voltage switchboards.
  • Rear horizontal terminals support practical connection to switchboard busbar systems.
  • Short-time protection supports selective coordination between upstream and downstream protective devices.
  • Four auxiliary contacts and open/closed position indication support circuit-breaker monitoring and control.

Key Features

  • ABB SACE Emax E2N 2000 air circuit breaker.
  • 2000 A rated uninterrupted current.
  • 4-pole configuration.
  • PR121/P-LSI R2000 electronic overcurrent release.
  • LSI functions provide long-time, short-time and instantaneous protection.
  • Fixed (F) circuit-breaker version.
  • Rear horizontal (HR) main terminals.
  • 65 kA Icu at 400 V AC, 50 Hz.
  • Adjustable overload release setting from 800–2000 A.
  • Adjustable short-time short-circuit setting from 2000–20000 A.
  • Adjustable instantaneous short-circuit setting from 3000–30000 A.
  • IP2X degree of protection.
  • Four auxiliary contacts configured as 2 NO + 2 NC.
  • Open/closed circuit-breaker position indication.
  • Optional motor operating mechanism capability.

Selective LSI Protection for 2000 A Power Distribution

The ABB SACE Emax E2N 2000 provides dependable switching and electronic overcurrent protection for high-current low-voltage distribution circuits. Its PR121/P-LSI electronic release combines long-time protection against sustained overloads, short-time protection for selective fault coordination and instantaneous protection for rapid interruption of severe short-circuit currents.

With a 2000 A current rating, four-pole fixed construction and 65 kA ultimate short-circuit breaking capacity at 400 V AC, the 1SDA055929R1 is well suited to main incoming and high-current feeder duties. Rear horizontal terminals facilitate integration with suitable switchboard busbars, while its auxiliary contacts and breaker position indication support remote status monitoring and control-system integration.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main incoming circuit protection.
  • Three-phase and neutral power distribution systems.
  • High-current feeder protection.
  • Power distribution centres and fixed switchgear assemblies.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical distribution.
  • Distribution systems requiring selective LSI overcurrent protection.

Technical Specifications

Series SACE Emax
ABB order code 1SDA055929R1
Extended product type E2N2000PR121/P-LSIIn=2000A4pFHR
Product type Air circuit breaker
Frame E2
Performance level N
Rated current (In) 2000 A
Rated uninterrupted current (Iu) 2000 A
Number of poles 4
Current type AC
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC, 50 Hz 65 kA
Release PR121/P-LSI R2000
Release type Electronic overcurrent release
Protection functions LSI – long-time, short-time and instantaneous
Long-time protection (L) Overload protection
Overload release adjustment range 800–2000 A
Short-time protection (S) Delayed short-circuit protection
Short-time short-circuit adjustment range 2000–20000 A
Instantaneous protection (I) Instantaneous short-circuit protection
Instantaneous short-circuit adjustment range 3000–30000 A
Installation Fixed
Main terminal position Rear
Terminal arrangement Rear horizontal
Main circuit connection Busbar connection
Auxiliary contacts 4 total, 2 NO + 2 NC
Position indication Circuit breaker open / closed
Trip indication Yes
Motor operating mechanism Optional
Degree of protection IP2X
Product net width 386 mm
Product net height 418 mm
Product net depth 302 mm
EAN 8015644572693
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA055929R1?

The ABB 1SDA055929R1 is a SACE Emax E2N 2000 four-pole fixed air circuit breaker rated at 2000 A, with rear horizontal terminals and a PR121/P-LSI R2000 electronic overcurrent release.

What protection release is fitted to the ABB 1SDA055929R1?

The breaker is fitted with a PR121/P-LSI R2000 electronic overcurrent release, providing long-time, short-time and instantaneous overcurrent protection.

What does LSI protection mean?

LSI denotes long-time, short-time and instantaneous protection. Long-time protection responds to sustained overloads, short-time protection supports selective coordination during short-circuit conditions, and instantaneous protection provides rapid operation during severe faults.

Is the ABB 1SDA055929R1 fixed or withdrawable?

The 1SDA055929R1 is a fixed four-pole air circuit breaker fitted with rear horizontal terminals for permanent installation within a compatible low-voltage switchboard.

What is the short-circuit breaking capacity of the ABB E2N 2000?

The E2N 2000 has a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, 50 Hz, providing substantial fault-interruption capability for demanding low-voltage distribution systems.

Trusted ABB Protection for Critical Distribution Systems

ABB SACE Emax air circuit breakers provide robust switching and electronic protection for low-voltage power distribution, combining high current capability, selective LSI protection and dependable fixed switchboard integration for demanding industrial and infrastructure applications.