1SDA055921R1 ABB E2N2000 2000 A 3-Pole Air Circuit Breaker

1SDA055921R1 ABB E2N2000 2000 A 3-Pole Air Circuit Breaker

ABB E2N2000 1SDA055921R1 is a 2000 A three-pole fixed SACE Emax air circuit breaker with a PR121/P-LSI electronic trip unit for high-current low-voltage distribution protection.

SKU: 1SDA055921R1Alt SKU: E2N2000MPN: 1SDA055921R1
Price
List Price £14,498.56 ex VAT
Your Price (ex VAT) Save 25%
£10,873.92 25% OFF
You save £3,624.64 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,873.92
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,873.92

Why Choose the ABB E2N2000 1SDA055921R1 Air Circuit Breaker?

The ABB E2N2000 1SDA055921R1 is a high-performance SACE Emax air circuit breaker (ACB) designed for protection and switching of high-current low-voltage electrical distribution systems. Part of the proven ABB Emax E2 series, this fixed three-pole circuit breaker combines a 2000 A rated current with the electronic PR121/P-LSI trip unit for dependable overload, short-time and instantaneous short-circuit protection.

Designed for demanding industrial and commercial power distribution applications, the E2N2000 provides reliable circuit protection while supporting selective coordination within low-voltage switchboards. Its electronic PR121/P-LSI release provides L, S and I protection functions, allowing the breaker to respond appropriately to overload and short-circuit conditions without integrated earth-fault protection.

This model is a three-pole fixed circuit breaker with horizontal rear terminals and a rated operational voltage of up to 690 V AC. The E2N performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 415 V AC, making it suitable for substantial industrial distribution systems where high fault-current interruption capability is required.

Key Advantages

  • High-current 2000 A air circuit breaker for low-voltage power distribution.
  • PR121/P-LSI electronic trip unit provides overload, short-time and instantaneous protection.
  • 65 kA breaking capacity at 415 V AC for demanding fault conditions.
  • Three-pole fixed configuration for permanent switchboard installation.
  • Rated operational voltage up to 690 V AC.
  • Horizontal rear terminals support practical integration into power distribution assemblies.

Key Features

  • ABB SACE Emax E2N2000 air circuit breaker.
  • 2000 A rated current.
  • 3-pole configuration.
  • PR121/P-LSI electronic release.
  • LSI protection functions: long-time, short-time and instantaneous.
  • Fixed (F) circuit-breaker execution.
  • Horizontal rear (HR) main terminals.
  • 65 kA Icu at 415 V AC.
  • 55 kA Icw for 1 second.
  • Rated insulation voltage of 1000 V.
  • Rated impulse withstand voltage of 12 kV.

Reliable Protection for High-Current Distribution Systems

Air circuit breakers such as the ABB E2N2000 provide switching, isolation and protection at the main and distribution levels of low-voltage electrical installations. Their high current ratings and substantial short-circuit interruption capability make them particularly suitable for switchboards supplying industrial machinery, infrastructure and large commercial loads.

The PR121/P-LSI electronic trip unit continuously supports protection against overload and short-circuit conditions through its long-time, short-time and instantaneous functions. Combined with the Emax platform's robust construction, this provides dependable protection for critical low-voltage distribution equipment.

Typical Applications

  • Main low-voltage switchboards and distribution boards.
  • Industrial power distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical installations.
  • Transformer secondary and feeder protection.
  • High-current machinery and production systems.

Technical Specifications

Series SACE Emax E2
ABB order code 1SDA055921R1
Product type Air circuit breaker
Rated current (In) 2000 A
Rated uninterrupted current (Iu) 2000 A
Number of poles 3
Execution Fixed
Trip unit PR121/P-LSI electronic release
Protection functions L, S, I
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate breaking capacity (Icu) at 415 V AC 65 kA
Rated service breaking capacity (Ics) at 415 V AC 65 kA
Rated short-time withstand current (Icw), 1 s 55 kA
Rated short-time withstand current (Icw), 3 s 42 kA
Main terminal arrangement Horizontal rear terminals
Short-circuit performance level N
Standard IEC

Frequently Asked Questions

What is the ABB E2N2000 1SDA055921R1 used for?

It is a 2000 A air circuit breaker designed for switching and protection of high-current low-voltage electrical distribution systems.

What trip unit is fitted to the ABB 1SDA055921R1?

This circuit breaker is equipped with an ABB PR121/P-LSI electronic trip unit providing long-time, short-time and instantaneous protection functions.

What is the rated current of this circuit breaker?

The ABB E2N2000 1SDA055921R1 has a rated current of 2000 A.

What is the breaking capacity of the E2N2000?

The E2N2000 has a rated ultimate short-circuit breaking capacity of 65 kA at 415 V AC.

Is the ABB 1SDA055921R1 fixed or withdrawable?

This model is a fixed three-pole circuit breaker with horizontal rear main terminals.

Trusted ABB Power Distribution Technology

ABB SACE Emax air circuit breakers are engineered for dependable protection and control of low-voltage power distribution systems, combining high breaking performance with electronic protection technology for demanding industrial and commercial installations.