Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB E2N2000 1SDA055921R1 is a 2000 A three-pole fixed SACE Emax air circuit breaker with a PR121/P-LSI electronic trip unit for high-current low-voltage distribution protection.
£10,873.92
The ABB E2N2000 1SDA055921R1 is a high-performance SACE Emax air circuit breaker (ACB) designed for protection and switching of high-current low-voltage electrical distribution systems. Part of the proven ABB Emax E2 series, this fixed three-pole circuit breaker combines a 2000 A rated current with the electronic PR121/P-LSI trip unit for dependable overload, short-time and instantaneous short-circuit protection.
Designed for demanding industrial and commercial power distribution applications, the E2N2000 provides reliable circuit protection while supporting selective coordination within low-voltage switchboards. Its electronic PR121/P-LSI release provides L, S and I protection functions, allowing the breaker to respond appropriately to overload and short-circuit conditions without integrated earth-fault protection.
This model is a three-pole fixed circuit breaker with horizontal rear terminals and a rated operational voltage of up to 690 V AC. The E2N performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 415 V AC, making it suitable for substantial industrial distribution systems where high fault-current interruption capability is required.
Air circuit breakers such as the ABB E2N2000 provide switching, isolation and protection at the main and distribution levels of low-voltage electrical installations. Their high current ratings and substantial short-circuit interruption capability make them particularly suitable for switchboards supplying industrial machinery, infrastructure and large commercial loads.
The PR121/P-LSI electronic trip unit continuously supports protection against overload and short-circuit conditions through its long-time, short-time and instantaneous functions. Combined with the Emax platform's robust construction, this provides dependable protection for critical low-voltage distribution equipment.
| Series | SACE Emax E2 |
|---|---|
| ABB order code | 1SDA055921R1 |
| Product type | Air circuit breaker |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Number of poles | 3 |
| Execution | Fixed |
| Trip unit | PR121/P-LSI electronic release |
| Protection functions | L, S, I |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate breaking capacity (Icu) at 415 V AC | 65 kA |
| Rated service breaking capacity (Ics) at 415 V AC | 65 kA |
| Rated short-time withstand current (Icw), 1 s | 55 kA |
| Rated short-time withstand current (Icw), 3 s | 42 kA |
| Main terminal arrangement | Horizontal rear terminals |
| Short-circuit performance level | N |
| Standard | IEC |
It is a 2000 A air circuit breaker designed for switching and protection of high-current low-voltage electrical distribution systems.
This circuit breaker is equipped with an ABB PR121/P-LSI electronic trip unit providing long-time, short-time and instantaneous protection functions.
The ABB E2N2000 1SDA055921R1 has a rated current of 2000 A.
The E2N2000 has a rated ultimate short-circuit breaking capacity of 65 kA at 415 V AC.
This model is a fixed three-pole circuit breaker with horizontal rear main terminals.
ABB SACE Emax air circuit breakers are engineered for dependable protection and control of low-voltage power distribution systems, combining high breaking performance with electronic protection technology for demanding industrial and commercial installations.
We use cookies