ABB 1SDA055917R1 E2N1600 is a 1600 A four-pole withdrawable SACE Emax air circuit breaker moving part with PR122/P-LSIG electronic protection, integrated ground-fault protection, 690 V AC operational voltage and 65 kA breaking capacity at 400 V AC.

SKU: 1SDA055917R1Alt SKU: E2N1600PR122/P-LSIMPN: 1SDA055917R1
Price
List Price £18,481.39 ex VAT
Your Price (ex VAT) Save 25%
£13,861.04 25% OFF
You save £4,620.35 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £13,861.04
Trade pricing is personalised to your account

Manufacturer Lead Time

£13,861.04

Why Choose the ABB E2N1600 PR122/P-LSIG 1600A 4-Pole Withdrawable Air Circuit Breaker?

The ABB 1SDA055917R1 is a high-performance SACE Emax E2N air circuit breaker (ACB) moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Rated at 1600 A, this four-pole withdrawable circuit breaker moving part is equipped with the PR122/P-LSIG R1600 electronic overcurrent release for comprehensive protection of industrial and commercial power networks.

As part of the ABB SACE Emax / New Emax range, the E2N1600 combines high short-circuit performance with advanced electronic protection. The PR122/P-LSIG release provides long-time, short-time, instantaneous and ground-fault protection functions, helping protect cables, busbars, transformers and connected electrical equipment against overloads, short circuits and earth faults.

The E2N1600 PR122/P-LSIG is a four-pole withdrawable moving part with a rated uninterrupted current of 1600 A and a rated operational voltage of 690 V AC. Its N performance level provides an ultimate and service short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC, making it suitable for high-fault-level three-phase four-wire distribution systems.

Key Advantages

  • High-capacity 1600 A SACE Emax air circuit breaker moving part.
  • Four-pole configuration suitable for three-phase four-wire electrical distribution systems.
  • Advanced PR122/P-LSIG R1600 electronic overcurrent release.
  • LSIG protection provides long-time, short-time, instantaneous and ground-fault protection.
  • 65 kA ultimate and service short-circuit breaking capacity at 400 V AC.
  • 55 kA ultimate and service short-circuit breaking capacity at 690 V AC.
  • Withdrawable moving-part construction supports maintainable switchboard installations.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Key Features

  • ABB SACE Emax E2N1600 air circuit breaker moving part.
  • 1600 A rated uninterrupted current.
  • Four-pole configuration.
  • Withdrawable moving-part construction.
  • PR122/P-LSIG R1600 electronic overcurrent release.
  • Long-time, short-time, instantaneous and ground-fault LSIG protection functions.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 65 kA Icu/Ics at 400 V AC.
  • 55 kA Icu/Ics at 690 V AC.
  • 55 kA short-time withstand current for 1 s.

Advanced LSIG Protection for High-Fault-Level Power Distribution

Air circuit breakers such as the ABB E2N1600 provide switching, isolation and protection for high-current low-voltage distribution circuits. The four-pole configuration is well suited to three-phase four-wire systems, while the withdrawable architecture allows the circuit breaker moving part to be disconnected from its corresponding fixed part for inspection, servicing or replacement within appropriately designed switchgear.

The PR122/P-LSIG electronic release provides long-time protection against sustained overloads, short-time protection for selective short-circuit coordination, instantaneous protection against severe fault currents and ground-fault protection for earth-fault conditions. Combined with the E2N's high breaking capacity, these functions support comprehensive protection and coordination throughout demanding electrical distribution networks.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Three-phase four-wire electrical distribution systems.
  • Main incoming circuit protection.
  • High-fault-level feeder protection.
  • Withdrawable switchgear assemblies.
  • Busbar and bus-coupler applications.
  • Transformer secondary and generator distribution systems.
  • Manufacturing, commercial and infrastructure installations.

Technical Specifications

Series SACE Emax / New Emax
ABB order code 1SDA055917R1
Product group 310513-New Emax
Product type Air circuit breaker moving part
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational current (Ie) 1600 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Number of poles 4
Current type AC
Installation Withdrawable
Configuration Moving part (MP)
Trip unit PR122/P-LSIG R1600
Release type Electronic
Protection functions Long-time, short-time, instantaneous and ground fault (LSIG)
Overload release adjustment 640–1600 A
Short-time short-circuit release adjustment 960–16000 A
Instantaneous short-circuit release adjustment 2400–24000 A
Ground-fault protection Integrated
Short-circuit performance level N
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 400 V AC 65 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 440 V AC 65 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 55 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 55 kA
Rated short-time withstand current (Icw) 55 kA for 1 s; 42 kA for 3 s
Protection rating IP2X
Power loss 215 W
Mechanical durability 25,000 cycles
Auxiliary contacts 4 (2 normally open and 2 normally closed)
Position indication Open / closed
Trip indication Yes
Motor operating mechanism Optional
Standards IEC
Weight 73 kg
EAN 8015644572570

Frequently Asked Questions

What is the ABB 1SDA055917R1 used for?

The ABB 1SDA055917R1 is a 1600 A four-pole withdrawable SACE Emax air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits.

What current rating does the ABB E2N1600 1SDA055917R1 have?

The circuit breaker moving part has a rated uninterrupted current of 1600 A.

What protection unit is fitted to the ABB 1SDA055917R1?

The breaker is fitted with an ABB PR122/P-LSIG R1600 electronic overcurrent release, providing long-time, short-time, instantaneous and ground-fault protection.

What is the breaking capacity of the ABB E2N1600?

The E2N1600 provides an ultimate and service short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC, with a short-time withstand current of 55 kA for 1 s.

Is the ABB 1SDA055917R1 fixed or withdrawable?

The 1SDA055917R1 is a four-pole withdrawable moving part designed for connection through the corresponding ABB SACE Emax fixed part in a compatible switchgear assembly.

Trusted ABB Power Distribution Technology

ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, advanced electronic LSIG protection and flexible withdrawable switchgear integration.