1SDA055911R1 ABB E2N 1600 PR123/P-LSIG 1600 A 3-Pole Withdrawable Air Circuit Breaker Moving Part

1SDA055911R1 ABB E2N 1600 PR123/P-LSIG 1600 A 3-Pole Withdrawable Air Circuit Breaker Moving Part

ABB 1SDA055911R1 SACE Emax E2N 1600 is a 1600 A three-pole withdrawable air circuit breaker moving part with a PR123/P-LSIG electronic release, comprehensive LSIG protection and 65 kA short-circuit breaking capacity at 400/415 V AC.

SKU: 1SDA055911R1MPN: 1SDA055911R1
Price
List Price £20,895.15 ex VAT
Your Price (ex VAT) Save 25%
£15,671.36 25% OFF
You save £5,223.79 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £15,671.36
Trade pricing is personalised to your account

Manufacturer Lead Time

£15,671.36

Why Choose the ABB 1SDA055911R1 E2N 1600 Air Circuit Breaker Moving Part?

The ABB 1SDA055911R1 is a SACE Emax E2N 1600 moving part for a withdrawable air circuit breaker, designed for high-current switching and comprehensive electronic protection in demanding low-voltage AC power distribution systems. This three-pole unit has a rated current of 1600 A and is equipped with an advanced PR123/P-LSIG R1600 electronic overcurrent release.

The PR123/P-LSIG release provides long-time, short-time, instantaneous and earth-fault protection, supporting coordinated protection against overloads, short circuits and earth-fault conditions. The E2N performance level provides strong short-circuit capability, including 65 kA at 400/415 V AC, making the breaker suitable for industrial and infrastructure distribution systems with significant prospective fault currents.

The 1SDA055911R1 is a three-pole withdrawable (W) moving portion intended for use with a compatible ABB SACE Emax fixed part. Its withdrawable construction facilitates inspection, servicing and replacement within suitable switchgear, while four auxiliary contacts and circuit-breaker open/closed position indication provide useful status signalling for control and monitoring systems.

Key Advantages

  • High-current 1600 A E2N air circuit breaker moving part for demanding low-voltage distribution.
  • PR123/P-LSIG R1600 electronic release provides comprehensive overload, short-circuit and earth-fault protection.
  • 65 kA short-circuit breaking capacity at 400/415 V AC.
  • Three-pole configuration is suited to three-phase power distribution systems.
  • Withdrawable construction supports inspection, maintenance and replacement within compatible SACE Emax switchgear.
  • Integrated earth-fault protection adds protection against faults involving earth or protective conductors.
  • Advanced PR123/P protection supports demanding power-distribution and system-monitoring applications.
  • Four auxiliary contacts and open/closed position indication support circuit-breaker status signalling.

Key Features

  • ABB SACE Emax E2N 1600 air circuit breaker moving part.
  • 1600 A rated current.
  • 3-pole configuration.
  • PR123/P-LSIG R1600 electronic overcurrent release.
  • LSIG functions provide long-time, short-time, instantaneous and earth-fault protection.
  • Withdrawable (W) circuit-breaker configuration.
  • Moving portion for installation with a compatible SACE Emax fixed part.
  • 690 V AC rated operational voltage.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • 65 kA short-circuit breaking capacity at 400/415 V AC.
  • 55 kA short-circuit capability at 500–690 V AC.
  • 55 kA rated short-time withstand current for 1 s.
  • 42 kA rated short-time withstand current for 3 s.
  • Four auxiliary contacts with open/closed circuit-breaker position indication.

Advanced PR123/P-LSIG Protection for 1600 A Distribution

The ABB SACE Emax E2N 1600 provides switching and advanced electronic protection for high-current low-voltage distribution circuits. Its PR123/P-LSIG release combines long-time protection against sustained overloads, short-time protection for selective fault coordination, instantaneous protection against severe short circuits and earth-fault protection for faults involving earth or protective conductors.

The withdrawable construction allows the circuit-breaker moving portion to be removed from its compatible fixed part, supporting inspection, maintenance and replacement strategies in critical switchboards. Combined with a 1600 A rating, three-pole configuration and 65 kA short-circuit capability at 400/415 V AC, the 1SDA055911R1 is well suited to main incoming and high-current feeder duties requiring advanced protection, selectivity and serviceable switchgear construction.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main incoming circuit protection.
  • Three-phase power distribution systems.
  • High-current feeder protection.
  • Withdrawable switchgear assemblies.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical distribution.
  • Distribution systems requiring advanced overload, short-circuit and earth-fault protection.

Technical Specifications

Series SACE Emax
ABB order code 1SDA055911R1
Product type Air circuit breaker moving part
Frame / sub-type E2
Short-circuit performance level N
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Number of poles 3
Current type AC
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 400/415 V AC 65 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 55 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 55 kA
Rated short-time withstand current (Icw) 55 kA for 1 s
Release PR123/P-LSIG R1600
Release type Electronic
Protection functions LSIG – long-time, short-time, instantaneous and earth-fault
Long-time protection (L) Overload protection
Short-time protection (S) Selective short-circuit protection
Instantaneous protection (I) Instantaneous short-circuit protection
Earth-fault protection (G) Ground / earth-fault protection
Version Withdrawable
Configuration Moving portion
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Net weight 59 kg
HS code 85362090
EAN 8015644572518

Frequently Asked Questions

What is the ABB 1SDA055911R1?

The ABB 1SDA055911R1 is the moving portion of a three-pole SACE Emax E2N 1600 withdrawable air circuit breaker, rated at 1600 A and fitted with a PR123/P-LSIG R1600 electronic overcurrent release.

What protection release is fitted to the ABB 1SDA055911R1?

The breaker is fitted with an advanced PR123/P-LSIG R1600 electronic release, providing long-time, short-time, instantaneous and earth-fault protection.

What does LSIG protection mean?

LSIG denotes long-time, short-time, instantaneous and earth-fault protection. Together these functions protect against sustained overloads, selective and severe short-circuit faults, and earth-fault conditions.

Is the ABB 1SDA055911R1 fixed or withdrawable?

The 1SDA055911R1 is a withdrawable circuit-breaker moving part designed for installation with a compatible ABB SACE Emax fixed part.

What is the short-circuit breaking capacity of the ABB E2N 1600?

The E2N 1600 provides 65 kA short-circuit breaking capacity at 400/415 V AC, with 55 kA capability at 500–690 V AC.

Trusted ABB Protection for Critical Distribution Systems

ABB SACE Emax air circuit breakers provide robust switching and advanced electronic protection for low-voltage power distribution, combining high short-circuit performance, comprehensive PR123/P-LSIG protection and serviceable withdrawable construction for demanding industrial and infrastructure applications.