Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055906R1 E2N1600 PR121/P-LSIG is a 1600 A three-pole withdrawable SACE Emax air circuit breaker moving part with LSIG electronic protection and 65 kA breaking capacity at 415 V AC for low-voltage power distribution systems.
£10,264.19
The ABB E2N1600 PR121/P-LSIG, order code 1SDA055906R1, is a high-performance three-pole withdrawable air circuit breaker moving part designed for protection and switching in low-voltage electrical distribution systems. As part of the proven ABB SACE Emax series, this E2N circuit breaker combines a 1600 A rated current with the PR121/P electronic overcurrent release for dependable protection in industrial, commercial and infrastructure power installations.
This configuration is the withdrawable moving part (W MP) of the circuit breaker, enabling removal from its compatible fixed cradle for inspection, servicing and replacement. The integrated PR121/P-LSIG electronic overcurrent release provides long-time, short-time, instantaneous and ground-fault protection functions, helping protect electrical networks against overloads, short circuits and earth faults.
With a rated uninterrupted current of 1600 A and an ultimate short-circuit breaking capacity of 65 kA at 415 V AC, the E2N1600 is suited to demanding high-current distribution applications. Its withdrawable architecture, four auxiliary contacts and circuit-breaker open/closed position indication support maintainable and flexible integration into low-voltage switchboards.
Air circuit breakers such as the ABB SACE Emax E2N1600 provide switching, isolation and protection for high-current low-voltage distribution circuits. Withdrawable circuit breakers are particularly useful in installations where maintainability and continuity are important because the moving circuit-breaker assembly can be withdrawn from its compatible fixed cradle for servicing or replacement.
The PR121/P electronic overcurrent release provides LSIG protection for demanding electrical networks. Long-time protection responds to sustained overload conditions, short-time and instantaneous functions protect against short-circuit currents, and ground-fault protection provides additional protection against earth-fault currents within the electrical distribution system.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA055906R1 |
| EAN | 8015644572464 |
| Product type | Air circuit breaker moving part |
| Frame / performance level | E2N |
| Rated current | 1600 A |
| Rated operational current | 1600 A |
| Number of poles | 3 |
| Current type | AC |
| Installation version | Withdrawable |
| Configuration | Moving part (MP) |
| Trip unit | PR121/P |
| Overcurrent release rating | R1600 |
| Protection functions | LSIG |
| Long-time protection | L |
| Short-time protection | S |
| Instantaneous protection | I |
| Ground-fault protection | G |
| Overload release adjustment range | 640–1600 A |
| Short-time delayed short-circuit adjustment range | 1600–16000 A |
| Instantaneous short-circuit adjustment range | 2400–24000 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Ultimate short-circuit breaking capacity (Icu) at 415 V AC | 65 kA |
| Service short-circuit breaking capacity (Ics) at 415 V AC | 65 kA |
| Ultimate short-circuit breaking capacity (Icu) at 690 V AC | 55 kA |
| Short-time withstand current (Icw) for 1 s | 55 kA |
| Short-time withstand current (Icw) for 3 s | 42 kA |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Circuit breaker open / closed |
| Mechanical durability | 25,000 cycles |
| Dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Net weight | 49 kg |
| ABB product group | 310513-New Emax |
The ABB 1SDA055906R1 is a 1600 A three-pole withdrawable air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution systems.
The PR121/P-LSIG electronic overcurrent release provides long-time, short-time, instantaneous and ground-fault protection, commonly abbreviated as LSIG.
The E2N1600 PR121/P-LSIG has a rated current of 1600 A.
This model is the withdrawable moving part (W MP) of the E2N1600 circuit breaker and is intended for use with the corresponding withdrawable circuit-breaker installation system.
The ABB E2N1600 provides an ultimate short-circuit breaking capacity of 65 kA at 415 V AC and a short-time withstand current of 55 kA for 1 s.
ABB SACE Emax air circuit breakers are engineered for dependable low-voltage power distribution, combining high-current switching capability, advanced electronic protection and maintainable withdrawable configurations for industrial, commercial and infrastructure electrical systems.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.