1SDA055901R1 ABB E2N1600 PR122/P-LSIG 1600 A 4-Pole Fixed Air Circuit Breaker

1SDA055901R1 ABB E2N1600 PR122/P-LSIG 1600 A 4-Pole Fixed Air Circuit Breaker

ABB 1SDA055901R1 is a SACE New Emax E2N1600 four-pole 1600 A fixed air circuit breaker with rear horizontal terminals and a PR122/P-LSIG R1600 electronic release providing long-time, short-time, instantaneous and earth-fault protection.

SKU: 1SDA055901R1MPN: 1SDA055901R1
Price
List Price £15,828.79 ex VAT
Your Price (ex VAT) Save 25%
£11,871.59 25% OFF
You save £3,957.20 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £11,871.59
Trade pricing is personalised to your account

Manufacturer Lead Time

£11,871.59

Why Choose the ABB E2N1600 1SDA055901R1 Air Circuit Breaker?

The ABB E2N1600 1SDA055901R1 is a high-performance SACE Emax air circuit breaker (ACB) designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the established ABB New Emax series, this E2N 1600 configuration features a four-pole fixed design, a rated current of 1600 A and a PR122/P-LSIG electronic overcurrent release.

Designed for industrial, commercial and infrastructure power distribution applications, the E2N1600 combines dependable high-current circuit protection with configurable electronic trip functionality. The PR122/P-LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection, delivering comprehensive protection for critical electrical distribution circuits.

This version is a fixed four-pole circuit breaker with rear horizontal terminals and combines a 1600 A rated current with a rated operational voltage of up to 690 V AC. The E2N performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC, while four auxiliary contacts and open/closed position indication support integration into switchgear control and signalling systems.

Key Advantages

  • High-performance ABB SACE Emax air circuit breaker for demanding low-voltage power distribution.
  • 1600 A rated current for substantial industrial and commercial electrical loads.
  • Four-pole fixed configuration suitable for four-conductor distribution systems.
  • PR122/P-LSIG electronic trip unit provides long-time, short-time, instantaneous and earth-fault protection.
  • 65 kA breaking capacity at 400 V AC and 55 kA at 690 V AC.
  • Rear horizontal terminals provide a practical connection arrangement for compatible low-voltage switchboards.

Key Features

  • ABB SACE New Emax E2N 1600 circuit breaker platform.
  • 1600 A rated current.
  • Four-pole construction.
  • Fixed circuit breaker configuration.
  • Rear horizontal terminals.
  • PR122/P-LSIG electronic overcurrent release.
  • R1600 / 1600 A release rating.
  • Long-time, short-time, instantaneous and earth-fault protection functions.
  • 690 V AC rated operational voltage.
  • Four auxiliary contacts and circuit breaker open/closed position indication.

Advanced LSIG Protection for High-Current Power Distribution

Air circuit breakers such as the ABB SACE Emax E2N1600 provide switching and protection for high-current low-voltage distribution circuits. Electronic trip technology enables abnormal current conditions to be detected accurately, allowing the breaker to disconnect the protected circuit according to configured protection parameters and helping minimise damage to cables, switchgear and connected equipment.

The PR122/P-LSIG release provides L, S, I and G protection functions, covering long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the fixed SACE Emax architecture, four-pole construction and rear horizontal terminals, this configuration is well suited to switchboards requiring comprehensive high-current protection, selective coordination and dependable system integration.

Typical Applications

  • Low-voltage main distribution switchboards.
  • Industrial power distribution systems.
  • Commercial and infrastructure electrical distribution.
  • Manufacturing and process plant switchgear.
  • Incoming and outgoing high-current feeder protection.
  • Four-pole distribution systems requiring integrated earth-fault protection.

Technical Specifications

Series SACE New Emax
ABB order code 1SDA055901R1
Product group 310513-New Emax
Product type Air circuit breaker
Frame E2N 1600
Rated current 1600 A
Rated uninterrupted current 1600 A
Rated operational current 1600 A
Rated operational voltage 690 V AC
Rated insulation voltage 1000 V
Rated impulse withstand voltage 12 kV
Current type AC
Number of poles 4
Execution Fixed
Terminal connection Rear horizontal
Trip unit PR122/P-LSIG
Release type Electronic
Release rating R1600 / 1600 A
Protection functions L (long-time), S (short-time), I (instantaneous) and G (earth fault)
Rated ultimate short-circuit breaking capacity 65 kA at 220–440 V AC; 55 kA at 500–690 V AC
Rated service short-circuit breaking capacity 65 kA at 220–440 V AC; 55 kA at 500–690 V AC
Rated short-time withstand current 55 kA for 1 s; 42 kA for 3 s
Integrated earth-fault protection Yes
Short-circuit performance level N
Power loss 115 W
Electrical durability 12,000 cycles at ≤440 V; 10,000 cycles at 500–690 V
Mechanical durability 25,000 cycles
Auxiliary contacts 4
Position indication Open / closed
Standard IEC
Dimensions (W × H × D) 386 × 418 × 302 mm
Net weight 56 kg
EAN 8015644572419

Frequently Asked Questions

What is the ABB E2N1600 1SDA055901R1 used for?

The ABB 1SDA055901R1 is a SACE Emax E2N 1600 air circuit breaker designed for switching and comprehensive overcurrent protection in high-current low-voltage electrical distribution systems.

What is the rated current of the ABB E2N1600 1SDA055901R1?

The 1SDA055901R1 has a rated current of 1600 A and uses an R1600 release with its PR122/P electronic trip unit.

Which trip unit is fitted to the ABB 1SDA055901R1?

The breaker is fitted with an ABB PR122/P-LSIG R1600 electronic overcurrent release, providing long-time, short-time, instantaneous and earth-fault protection.

What is the breaking capacity of the ABB E2N1600 1SDA055901R1?

The breaker has rated ultimate and service short-circuit breaking capacities of 65 kA at 220–440 V AC and 55 kA at 500–690 V AC.

Is the ABB 1SDA055901R1 fixed or withdrawable?

The 1SDA055901R1 is a fixed four-pole E2N 1600 circuit breaker equipped with rear horizontal terminals for integration into compatible low-voltage switchgear.

Trusted Protection from ABB

ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution installations, combining advanced electronic protection technology with robust switchgear integration.