Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055901R1 is a SACE New Emax E2N1600 four-pole 1600 A fixed air circuit breaker with rear horizontal terminals and a PR122/P-LSIG R1600 electronic release providing long-time, short-time, instantaneous and earth-fault protection.
£11,871.59
The ABB E2N1600 1SDA055901R1 is a high-performance SACE Emax air circuit breaker (ACB) designed for protection and switching in demanding low-voltage electrical distribution systems. Part of the established ABB New Emax series, this E2N 1600 configuration features a four-pole fixed design, a rated current of 1600 A and a PR122/P-LSIG electronic overcurrent release.
Designed for industrial, commercial and infrastructure power distribution applications, the E2N1600 combines dependable high-current circuit protection with configurable electronic trip functionality. The PR122/P-LSIG release provides long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection, delivering comprehensive protection for critical electrical distribution circuits.
This version is a fixed four-pole circuit breaker with rear horizontal terminals and combines a 1600 A rated current with a rated operational voltage of up to 690 V AC. The E2N performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC, while four auxiliary contacts and open/closed position indication support integration into switchgear control and signalling systems.
Air circuit breakers such as the ABB SACE Emax E2N1600 provide switching and protection for high-current low-voltage distribution circuits. Electronic trip technology enables abnormal current conditions to be detected accurately, allowing the breaker to disconnect the protected circuit according to configured protection parameters and helping minimise damage to cables, switchgear and connected equipment.
The PR122/P-LSIG release provides L, S, I and G protection functions, covering long-time overload, short-time short-circuit, instantaneous short-circuit and earth-fault protection. Combined with the fixed SACE Emax architecture, four-pole construction and rear horizontal terminals, this configuration is well suited to switchboards requiring comprehensive high-current protection, selective coordination and dependable system integration.
| Series | SACE New Emax |
|---|---|
| ABB order code | 1SDA055901R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker |
| Frame | E2N 1600 |
| Rated current | 1600 A |
| Rated uninterrupted current | 1600 A |
| Rated operational current | 1600 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Current type | AC |
| Number of poles | 4 |
| Execution | Fixed |
| Terminal connection | Rear horizontal |
| Trip unit | PR122/P-LSIG |
| Release type | Electronic |
| Release rating | R1600 / 1600 A |
| Protection functions | L (long-time), S (short-time), I (instantaneous) and G (earth fault) |
| Rated ultimate short-circuit breaking capacity | 65 kA at 220–440 V AC; 55 kA at 500–690 V AC |
| Rated service short-circuit breaking capacity | 65 kA at 220–440 V AC; 55 kA at 500–690 V AC |
| Rated short-time withstand current | 55 kA for 1 s; 42 kA for 3 s |
| Integrated earth-fault protection | Yes |
| Short-circuit performance level | N |
| Power loss | 115 W |
| Electrical durability | 12,000 cycles at ≤440 V; 10,000 cycles at 500–690 V |
| Mechanical durability | 25,000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Standard | IEC |
| Dimensions (W × H × D) | 386 × 418 × 302 mm |
| Net weight | 56 kg |
| EAN | 8015644572419 |
The ABB 1SDA055901R1 is a SACE Emax E2N 1600 air circuit breaker designed for switching and comprehensive overcurrent protection in high-current low-voltage electrical distribution systems.
The 1SDA055901R1 has a rated current of 1600 A and uses an R1600 release with its PR122/P electronic trip unit.
The breaker is fitted with an ABB PR122/P-LSIG R1600 electronic overcurrent release, providing long-time, short-time, instantaneous and earth-fault protection.
The breaker has rated ultimate and service short-circuit breaking capacities of 65 kA at 220–440 V AC and 55 kA at 500–690 V AC.
The 1SDA055901R1 is a fixed four-pole E2N 1600 circuit breaker equipped with rear horizontal terminals for integration into compatible low-voltage switchgear.
ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution installations, combining advanced electronic protection technology with robust switchgear integration.