1SDA055900R1 ABB E2N1600 PR122/P-LSI 1600A 4-Pole Fixed Air Circuit Breaker

1SDA055900R1 ABB E2N1600 PR122/P-LSI 1600A 4-Pole Fixed Air Circuit Breaker

ABB 1SDA055900R1 E2N1600 is a 1600 A four-pole fixed SACE Emax air circuit breaker with PR122/P-LSI electronic protection, rear horizontal terminals and 65 kA breaking capacity at 400 V AC.

SKU: 1SDA055900R1MPN: 1SDA055900R1
Price
List Price £14,571.34 ex VAT
Your Price (ex VAT) Save 25%
£10,928.51 25% OFF
You save £3,642.84 per unit
Manufacturer Lead Time Estimated Delivery 8 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £10,928.51
Trade pricing is personalised to your account

Manufacturer Lead Time

£10,928.51

Why Choose the ABB E2N1600 PR122/P-LSI 1600A 4-Pole Fixed Air Circuit Breaker?

The ABB 1SDA055900R1 is a high-performance SACE Emax E2N air circuit breaker (ACB) designed for switching and protection in demanding low-voltage electrical distribution systems. Rated at 1600 A, this four-pole fixed circuit breaker is equipped with the PR122/P-LSI R1600 electronic overcurrent release for comprehensive overload and short-circuit protection.

As part of the ABB SACE Emax / New Emax range, the E2N1600 combines high short-circuit performance with electronic protection for industrial and commercial power distribution. The PR122/P-LSI release provides long-time, short-time and instantaneous protection functions, helping protect cables, busbars, transformers and connected equipment against sustained overloads and short-circuit faults.

The E2N1600 PR122/P-LSI is a four-pole fixed circuit breaker with rear flat horizontal terminals, a rated uninterrupted current of 1600 A and a rated operational voltage of 690 V AC. Its N performance level provides an ultimate and service short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC, making it suitable for high-fault-level three-phase four-wire distribution systems.

Key Advantages

  • High-capacity 1600 A SACE Emax air circuit breaker.
  • Four-pole configuration suitable for three-phase four-wire electrical distribution systems.
  • Advanced PR122/P-LSI R1600 electronic overcurrent release.
  • LSI protection provides long-time, short-time and instantaneous overcurrent protection.
  • 65 kA ultimate and service short-circuit breaking capacity at 400 V AC.
  • 55 kA ultimate and service short-circuit breaking capacity at 690 V AC.
  • 55 kA short-time withstand current for 1 s supports selective protection strategies.
  • Fixed construction with rear flat horizontal terminals for robust switchboard integration.

Key Features

  • ABB SACE Emax E2N1600 air circuit breaker.
  • 1600 A rated uninterrupted current.
  • Four-pole configuration.
  • Fixed circuit-breaker construction.
  • Rear flat horizontal terminals.
  • PR122/P-LSI R1600 electronic overcurrent release.
  • Long-time, short-time and instantaneous LSI protection functions.
  • 690 V AC rated operational voltage.
  • 65 kA Icu/Ics at 400 V AC.
  • 55 kA Icu/Ics at 690 V AC.
  • Four auxiliary contacts.
  • Open/closed circuit-breaker position indication.

Advanced Circuit Protection for High-Fault-Level Four-Wire Distribution

Air circuit breakers such as the ABB E2N1600 provide switching, isolation and protection for high-current low-voltage distribution circuits. The four-pole configuration is particularly suitable for three-phase four-wire systems, while the E2N performance level provides substantial short-circuit interruption capability for installations with elevated prospective fault currents.

The PR122/P-LSI electronic release provides long-time protection against sustained overloads, short-time protection to support selective short-circuit coordination and instantaneous protection against severe fault currents. Together with adjustable protection settings and the E2N's high breaking capacity, these functions support dependable protection and coordination throughout demanding electrical distribution networks.

Typical Applications

  • Industrial low-voltage switchboards and distribution panels.
  • Three-phase four-wire electrical distribution systems.
  • Main incoming circuit protection.
  • High-fault-level feeder protection.
  • Busbar and bus-coupler applications.
  • Transformer secondary distribution systems.
  • Manufacturing and process plants.
  • Commercial and infrastructure power distribution.

Technical Specifications

Series SACE Emax / New Emax
ABB order code 1SDA055900R1
Product group 310513-New Emax
Product type Air circuit breaker (ACB)
Rated current (In) 1600 A
Rated uninterrupted current (Iu) 1600 A
Rated operational current (Ie) 1600 A
Rated operational voltage 690 V AC
Number of poles 4
Current type AC
Installation Fixed
Main terminals Rear flat horizontal (HR)
Trip unit PR122/P-LSI R1600
Release type Electronic
Protection functions Long-time, short-time and instantaneous (LSI)
Overload release adjustment 640–1600 A
Short-time short-circuit release adjustment 960–16000 A
Instantaneous short-circuit release adjustment 2400–24000 A
Short-circuit performance level N
Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 400 V AC 65 kA
Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 440 V AC 65 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 55 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 55 kA
Rated short-time withstand current (Icw) 55 kA for 1 s; 42 kA for 3 s
Protection rating IP2X
Auxiliary contacts 4
Position indication Open / closed
Trip indication Yes
Motor operating mechanism Optional
Standards IEC
Weight 68 kg
EAN 8015644572402

Frequently Asked Questions

What is the ABB 1SDA055900R1 used for?

The ABB 1SDA055900R1 is a 1600 A four-pole fixed SACE Emax air circuit breaker used for switching and protecting high-current low-voltage electrical distribution circuits in industrial, commercial and infrastructure installations.

What current rating does the ABB E2N1600 1SDA055900R1 have?

The circuit breaker has a rated uninterrupted current of 1600 A.

What protection unit is fitted to the ABB 1SDA055900R1?

The breaker is fitted with an ABB PR122/P-LSI R1600 electronic overcurrent release, providing long-time, short-time and instantaneous protection.

What is the breaking capacity of the ABB E2N1600?

The E2N1600 provides an ultimate and service short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC, with a short-time withstand current of 55 kA for 1 s.

Is the ABB 1SDA055900R1 fixed or withdrawable?

The 1SDA055900R1 is a four-pole fixed air circuit breaker with rear flat horizontal terminals for permanent integration into compatible low-voltage switchboards.