ABB 1SDA055884R1 is a SACE New Emax E2N1250 four-pole 1250 A withdrawable air circuit breaker moving part with a PR122/P-LSI R1250 electronic release providing long-time, short-time and instantaneous overcurrent protection.
£10,629.83
The ABB E2N1250 1SDA055884R1 is a high-performance SACE Emax air circuit breaker (ACB) moving part designed for protection and switching in low-voltage electrical distribution systems. As part of the ABB New Emax series, this E2N 1250 configuration features a four-pole withdrawable design, a rated current of 1250 A and a PR122/P-LSI electronic overcurrent release.
Designed for demanding industrial, commercial and infrastructure power distribution applications, the E2N1250 combines dependable circuit protection with the serviceability of a withdrawable breaker arrangement. The PR122/P-LSI electronic trip unit provides long-time overload, short-time short-circuit and instantaneous short-circuit protection, supporting selective and coordinated protection of high-current electrical distribution circuits.
This version is supplied as the moving part for an E2N 1250 withdrawable circuit breaker and combines a 1250 A rated current with four-pole construction and a rated operational voltage of 690 V AC. The E2N performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, 50 Hz, while four auxiliary change-over contacts and open/closed position indication support switchgear control and status monitoring.
Air circuit breakers such as the ABB SACE Emax E2N1250 provide switching and protection for high-current low-voltage distribution circuits. Electronic trip technology enables accurate detection of abnormal current conditions, allowing the breaker to disconnect the protected circuit when configured protection thresholds are exceeded.
The PR122/P-LSI release provides L, S and I protection functions, covering long-time overload, short-time short-circuit and instantaneous short-circuit protection. Combined with the withdrawable SACE Emax architecture, this configuration is well suited to switchboards requiring dependable high-current protection, selective coordination, maintainability and operational flexibility.
| Series | SACE New Emax |
|---|---|
| ABB order code | 1SDA055884R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Frame | E2N 1250 |
| Rated current | 1250 A |
| Rated uninterrupted current | 1250 A |
| Rated operational current | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage | 1000 V |
| Rated impulse withstand voltage | 12 kV |
| Current type | AC |
| Number of poles | 4 |
| Execution | Withdrawable moving part |
| Trip unit | PR122/P-LSI |
| Release type | Electronic |
| Release rating | R1250 / 1250 A |
| Protection functions | L (long-time), S (short-time) and I (instantaneous) |
| Overload release setting range | 500–1250 A |
| Instantaneous short-circuit release setting range | 1875–18750 A |
| Rated ultimate short-circuit breaking capacity | 65 kA at 400 V AC, 50 Hz |
| Rated ultimate short-circuit breaking capacity at 690 V AC | 55 kA |
| Rated service short-circuit breaking capacity | 65 kA at 400 V AC, 50 Hz |
| Rated service short-circuit breaking capacity at 690 V AC | 55 kA |
| Rated short-time withstand current | 55 kA for 1 s; 42 kA for 3 s |
| Integrated earth-fault protection | No |
| Short-circuit performance level | N |
| Power loss | 130 W |
| Electrical durability | 15,000 cycles |
| Mechanical durability | 25,000 cycles |
| Auxiliary contacts | 4 change-over contacts |
| Position indication | Open / closed |
| Motor drive integrated | No |
| Motor drive | Optional |
| Standard | IEC |
| Dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Net weight | 61 kg |
| EAN | 8015644572242 |
The ABB 1SDA055884R1 is a SACE Emax E2N 1250 air circuit breaker moving part designed for switching and overcurrent protection in high-current low-voltage electrical distribution systems.
This circuit breaker configuration has a rated current of 1250 A, with an overload release setting range of 500–1250 A.
The breaker is fitted with an ABB PR122/P-LSI R1250 electronic overcurrent release, providing long-time, short-time and instantaneous overcurrent protection.
The breaker has a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, 50 Hz and 55 kA at 690 V AC.
The 1SDA055884R1 is the moving part of a withdrawable E2N 1250 circuit breaker for use with the appropriate compatible fixed part in an ABB SACE Emax installation.
ABB SACE Emax air circuit breakers are engineered for dependable protection and switching in demanding low-voltage power distribution installations, combining advanced electronic protection technology with flexible and serviceable switchgear integration.