Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055881R1 E2N1250 is a 1250 A four-pole withdrawable SACE Emax air circuit breaker moving part with PR121/P-LSI electronic protection, 690 V AC operational voltage and 65 kA breaking capacity at 400 V AC.
£10,522.50
The ABB 1SDA055881R1 is a SACE Emax E2N air circuit breaker (ACB) moving part designed for switching and protection in demanding low-voltage electrical distribution systems. Rated at 1250 A, this four-pole withdrawable circuit breaker moving part is equipped with the PR121/P-LSI R1250 electronic overcurrent release for comprehensive overload and short-circuit protection.
As part of the ABB SACE Emax / New Emax range, the E2N1250 combines high short-circuit performance with electronic protection for industrial and commercial power distribution. The PR121/P-LSI release provides long-time, short-time and instantaneous protection functions, helping protect cables, busbars, transformers and connected electrical equipment against overloads and short-circuit faults.
The E2N1250 PR121/P-LSI is a four-pole withdrawable moving part with a rated uninterrupted current of 1250 A and a rated operational voltage of 690 V AC. Its N performance level provides a rated ultimate and service short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC, while the withdrawable construction supports servicing and replacement within compatible SACE Emax switchgear assemblies.
Air circuit breakers such as the ABB E2N1250 provide switching, isolation and protection for high-current low-voltage distribution circuits. The four-pole configuration is well suited to three-phase four-wire systems, while the withdrawable architecture allows the circuit breaker moving part to be disconnected from its corresponding fixed part for inspection, servicing or replacement within appropriately designed switchgear.
The PR121/P-LSI electronic release provides long-time protection against sustained overloads, short-time protection for selective short-circuit coordination and instantaneous protection against severe fault currents. Combined with the E2N's high short-circuit interruption capability, this makes the 1SDA055881R1 suitable for demanding industrial and commercial power distribution systems.
| Series | SACE Emax / New Emax |
|---|---|
| ABB order code | 1SDA055881R1 |
| Product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Number of poles | 4 |
| Current type | AC |
| Installation | Withdrawable |
| Configuration | Moving part (MP) |
| Trip unit | PR121/P-LSI R1250 |
| Release type | Electronic |
| Protection functions | Long-time, short-time and instantaneous (LSI) |
| Short-circuit performance level | N |
| Rated ultimate short-circuit breaking capacity (Icu) at 400 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 400 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 440 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 440 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 500 V AC | 55 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 55 kA |
| Rated short-time withstand current (Icw) | 55 kA for 1 s; 42 kA for 3 s |
| Power loss | 130 W |
| Electrical durability | 15,000 cycles at ≤440 V AC; 15,000 cycles at 500–690 V AC |
| Mechanical durability | 25,000 cycles |
| Auxiliary contacts | 4 |
| Position indication | Open / closed |
| Standards | IEC |
| Dimensions (W × H × D) | 414 × 461 × 396.5 mm |
| Net weight | 61 kg |
| Package gross weight | 73 kg |
| EAN | 8015644572211 |
The ABB 1SDA055881R1 is a 1250 A four-pole withdrawable SACE Emax air circuit breaker moving part used for switching and protecting high-current low-voltage electrical distribution circuits.
The circuit breaker moving part has a rated uninterrupted current of 1250 A.
The breaker is fitted with an ABB PR121/P-LSI R1250 electronic overcurrent release, providing long-time, short-time and instantaneous protection.
The E2N1250 provides an ultimate and service short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC.
The 1SDA055881R1 is a four-pole withdrawable moving part designed for connection through the corresponding ABB SACE Emax fixed part in a compatible switchgear assembly.
ABB SACE Emax air circuit breakers are designed for dependable switching and protection in demanding low-voltage power distribution systems, combining high short-circuit performance, electronic LSI protection and flexible withdrawable switchgear integration.
We use cookies