Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055876R1 SACE Emax E2N 1250 is a 1250 A three-pole withdrawable air circuit breaker moving part with a PR122/P-LSI electronic release and 65 kA short-circuit breaking capacity at 415 V AC.
£8,602.70
The ABB 1SDA055876R1 is a SACE Emax E2N 1250 moving part for a withdrawable air circuit breaker, designed for high-current switching and overcurrent protection in demanding low-voltage AC power distribution systems. This three-pole unit has a rated current of 1250 A and is equipped with an electronic PR122/P-LSI R1250 overcurrent release providing long-time, short-time and instantaneous protection.
Part of the established ABB SACE Emax range, the E2N 1250 combines substantial current-carrying capability with strong short-circuit performance and the serviceability of a withdrawable circuit-breaker arrangement. The N performance level provides rated ultimate and service short-circuit breaking capacities of 65 kA at 415 V AC, making this breaker suitable for industrial, commercial and infrastructure distribution systems with significant prospective fault currents.
The 1SDA055876R1 is a three-pole withdrawable (W) moving portion intended for installation with a compatible SACE Emax fixed part. It is rated for operation up to 690 V AC, with a rated insulation voltage of 1000 V and rated impulse withstand voltage of 12 kV. Its withdrawable construction supports maintenance and replacement strategies in critical switchboards where service continuity and dependable circuit protection are important.
The ABB SACE Emax E2N 1250 provides switching and electronic overcurrent protection for high-current low-voltage distribution circuits. Its PR122/P-LSI electronic release combines long-time protection against sustained overload conditions, short-time protection for selective fault coordination and instantaneous protection against severe short-circuit currents, helping protect conductors, switchgear and connected equipment.
The withdrawable construction allows the circuit-breaker moving portion to be removed from its compatible fixed part, supporting inspection, maintenance and replacement strategies in critical switchboards. Combined with a 1250 A rating, three-pole configuration and 65 kA short-circuit breaking capacity at 415 V AC, the 1SDA055876R1 is well suited to main incoming and high-current feeder duties requiring strong fault interruption, selectivity and serviceable switchgear construction.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA055876R1 |
| Product type | Air circuit breaker moving part |
| Frame / sub-type | E2 |
| Short-circuit performance level | N |
| Rated current (In) | 1250 A |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Number of poles | 3 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 400/415 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 500 V AC | 55 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 690 V AC | 55 kA |
| Rated short-time withstand current (Icw) | 55 kA for 1 s |
| Release | PR122/P-LSI R1250 |
| Release type | Electronic |
| Protection functions | LSI – long-time, short-time and instantaneous |
| Long-time protection (L) | Overload protection |
| Short-time protection (S) | Selective short-circuit protection |
| Instantaneous protection (I) | Instantaneous short-circuit protection |
| Version | Withdrawable |
| Configuration | Moving portion |
| Terminal connection type | Withdrawable circuit breaker |
| Power loss | 130 W |
| Mechanical durability | 25,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Electrical durability at ≤440 V | 15,000 cycles |
| Electrical durability at 500–690 V | 15,000 cycles |
| Electrical operating frequency | 30 cycles per hour |
| Standard | IEC |
| Package gross weight | 59 kg |
| EAN | 8015644572167 |
The ABB 1SDA055876R1 is the moving portion of a three-pole SACE Emax E2N 1250 withdrawable air circuit breaker, rated at 1250 A and fitted with a PR122/P-LSI R1250 electronic overcurrent release.
The breaker is fitted with a PR122/P-LSI R1250 electronic release, providing long-time, short-time and instantaneous overcurrent protection.
LSI denotes long-time, short-time and instantaneous protection. Long-time protection responds to sustained overloads, short-time protection supports selective coordination during short-circuit conditions, and instantaneous protection provides rapid operation during severe faults.
The 1SDA055876R1 is a withdrawable circuit-breaker moving part designed for installation with a compatible ABB SACE Emax fixed part.
The E2N 1250 has rated ultimate and service short-circuit breaking capacities of 65 kA at 400/415 V AC. At 500–690 V AC, both Icu and Ics are 55 kA.
ABB SACE Emax air circuit breakers provide robust switching and electronic protection for low-voltage power distribution, combining high short-circuit performance, selective LSI protection and serviceable withdrawable construction for demanding industrial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.