1SDA055875R1 ABB E2N 1250 PR122/P-LI 1250 A 3-Pole Withdrawable Air Circuit Breaker Moving Part

1SDA055875R1 ABB E2N 1250 PR122/P-LI 1250 A 3-Pole Withdrawable Air Circuit Breaker Moving Part

ABB 1SDA055875R1 SACE Emax E2N 1250 is a 1250 A three-pole withdrawable air circuit breaker moving part with a PR122/P-LI electronic release and 65 kA short-circuit breaking capacity at 415 V AC.

SKU: 1SDA055875R1MPN: 1SDA055875R1
Price
List Price £10,701.79 ex VAT
Your Price (ex VAT) Save 25%
£8,026.34 25% OFF
You save £2,675.45 per unit
Manufacturer Lead Time Estimated Delivery 6 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,026.34
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,026.34

Why Choose the ABB 1SDA055875R1 E2N 1250 Air Circuit Breaker Moving Part?

The ABB 1SDA055875R1 is a SACE Emax E2N 1250 moving part for a withdrawable air circuit breaker, designed for switching and overcurrent protection in demanding low-voltage AC power distribution systems. This three-pole unit has a rated current of 1250 A and is equipped with an electronic PR122/P-LI R1250 overcurrent release providing long-time overload and instantaneous short-circuit protection.

Part of the established ABB SACE Emax range, the E2N 1250 combines substantial current-carrying capability with strong short-circuit performance and the serviceability of a withdrawable circuit-breaker arrangement. The N performance level provides rated ultimate and service short-circuit breaking capacities of 65 kA at 415 V AC, making this breaker suitable for industrial, commercial and infrastructure distribution systems with significant prospective fault currents.

The 1SDA055875R1 is a three-pole withdrawable (W) moving portion intended for use with a compatible SACE Emax fixed part. It is rated for operation up to 690 V AC, with a rated insulation voltage of 1000 V and rated impulse withstand voltage of 12 kV. Four auxiliary contacts and circuit-breaker open/closed position indication support integration with switchboard signalling, monitoring and control systems.

Key Advantages

  • High-current 1250 A E2N air circuit breaker moving part for low-voltage distribution.
  • PR122/P-LI R1250 electronic release provides long-time overload and instantaneous short-circuit protection.
  • 65 kA rated ultimate and service short-circuit breaking capacity at 415 V AC.
  • Three-pole configuration is suited to three-phase power distribution systems.
  • Withdrawable construction supports inspection, servicing and replacement within compatible Emax switchgear.
  • 55 kA short-time withstand current for 1 s provides robust fault-current performance.
  • Maintains 55 kA breaking capacity at 690 V AC for demanding higher-voltage low-voltage systems.
  • Four auxiliary contacts and open/closed position indication support circuit-breaker status monitoring.

Key Features

  • ABB SACE Emax E2N 1250 air circuit breaker moving part.
  • 1250 A rated current.
  • 3-pole configuration.
  • PR122/P-LI R1250 electronic overcurrent release.
  • LI functions provide long-time overload and instantaneous short-circuit protection.
  • Withdrawable (W) circuit-breaker configuration.
  • Moving portion for installation with a compatible SACE Emax fixed part.
  • 690 V AC rated operational voltage.
  • 65 kA Icu and Ics at 415 V AC.
  • 55 kA Icu and Ics at 690 V AC.
  • 55 kA rated short-time withstand current for 1 s.
  • 42 kA rated short-time withstand current for 3 s.
  • Four auxiliary contacts with circuit-breaker open/closed position indication.

Reliable LI Protection for High-Current Distribution

The ABB SACE Emax E2N 1250 provides switching and electronic overcurrent protection for high-current low-voltage distribution circuits. Its PR122/P-LI electronic release combines long-time protection against sustained overload conditions with instantaneous protection against severe short-circuit currents, helping protect conductors, switchgear and connected equipment.

The withdrawable construction allows the circuit-breaker moving portion to be removed from its compatible fixed part, supporting inspection, maintenance and replacement strategies in critical switchboards. Combined with a 1250 A rating, three-pole configuration and 65 kA short-circuit breaking capacity at 415 V AC, the 1SDA055875R1 is well suited to main incoming and high-current feeder duties requiring strong fault interruption and serviceable switchgear construction.

Typical Applications

  • Industrial low-voltage distribution switchboards.
  • Main incoming circuit protection.
  • Three-phase power distribution systems.
  • High-current feeder protection.
  • Withdrawable switchgear assemblies.
  • Manufacturing and process plants.
  • Commercial and infrastructure electrical distribution.
  • Distribution systems with high prospective short-circuit currents.

Technical Specifications

Series SACE Emax
ABB order code 1SDA055875R1
Product type Air circuit breaker moving part
Frame / sub-type E2
Short-circuit performance level N
Rated current (In) 1250 A
Rated uninterrupted current (Iu) 1250 A
Rated operational current (Ie) 1250 A
Number of poles 3
Current type AC
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Rated ultimate short-circuit breaking capacity (Icu) at 400/415 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 400/415 V AC 65 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 500 V AC 55 kA
Rated ultimate short-circuit breaking capacity (Icu) at 690 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 690 V AC 55 kA
Rated short-time withstand current (Icw) 55 kA for 1 s
Release PR122/P-LI R1250
Release type Electronic
Protection functions LI – long-time and instantaneous
Long-time protection (L) Overload protection
Instantaneous protection (I) Instantaneous short-circuit protection
Version Withdrawable
Configuration Moving portion
Terminal connection type Withdrawable circuit breaker
Auxiliary contacts 4
Position indication Circuit breaker open / closed
Power loss 130 W
Mechanical durability 25,000 cycles
Mechanical operating frequency 60 cycles per hour
Electrical durability at ≤440 V 15,000 cycles
Electrical durability at 500–690 V 15,000 cycles
Electrical operating frequency 30 cycles per hour
Product dimensions (W × H × D) 324 × 461 × 396.5 mm
Net weight 49 kg
Standard IEC
EAN 8015644572150

Frequently Asked Questions

What is the ABB 1SDA055875R1?

The ABB 1SDA055875R1 is the moving portion of a three-pole SACE Emax E2N 1250 withdrawable air circuit breaker, rated at 1250 A and fitted with a PR122/P-LI R1250 electronic overcurrent release.

What protection release is fitted to the ABB 1SDA055875R1?

The breaker is fitted with a PR122/P-LI R1250 electronic release, providing long-time overload and instantaneous short-circuit protection.

What does LI protection mean?

LI denotes long-time and instantaneous protection. Long-time protection responds to sustained overload conditions, while instantaneous protection provides rapid operation during severe short-circuit faults.

Is the ABB 1SDA055875R1 fixed or withdrawable?

The 1SDA055875R1 is a withdrawable circuit-breaker moving part designed for installation with the corresponding compatible ABB SACE Emax fixed part.

What is the short-circuit breaking capacity of the ABB E2N 1250?

The E2N 1250 has rated ultimate and service short-circuit breaking capacities of 65 kA at 415 V AC. At 690 V AC, both Icu and Ics are 55 kA.

Trusted ABB Protection for Critical Distribution Systems

ABB SACE Emax air circuit breakers provide robust switching and electronic protection for low-voltage power distribution, combining high short-circuit performance, dependable overcurrent protection and serviceable withdrawable construction for demanding industrial and infrastructure applications.