Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055873R1 SACE New Emax E2N1250 three-pole withdrawable air circuit breaker moving part with 1250 A rated current, PR121/P-LSI R1250 electronic protection and 65 kA Icu at 400 V AC.
£8,168.78
The ABB 1SDA055873R1 is a SACE New Emax E2N1250 air circuit breaker (ACB) moving part designed for dependable switching and protection in demanding low-voltage electrical distribution systems. This three-pole withdrawable breaker moving part has a rated uninterrupted current of 1250 A and is equipped with the ABB PR121/P-LSI R1250 electronic overcurrent release.
The PR121/P-LSI trip unit provides long-time (L), short-time (S) and instantaneous (I) protection. This combination protects against overload and short-circuit conditions while the short-time protection function supports selective coordination between upstream and downstream protective devices in industrial, commercial and infrastructure power distribution networks.
The E2N1250 performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC. The 1SDA055873R1 is specifically a three-pole withdrawable moving part, enabling integration with the appropriate ABB E2 fixed part while facilitating isolation, inspection, maintenance and replacement within compatible switchgear assemblies.
Air circuit breakers such as the ABB SACE New Emax E2N1250 provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. With a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, the E2N performance level is suited to installations where substantial prospective fault currents must be safely interrupted.
The PR121/P-LSI release combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. The short-time function supports selective coordination within multi-level distribution systems, while the withdrawable moving-part construction makes the 1SDA055873R1 particularly suitable for switchgear where straightforward isolation, maintenance and breaker replacement are important.
| Series | SACE New Emax E2N |
|---|---|
| Extended product type | E2N1250PR121/P-LSIIn=1250A3pWMP |
| Order code / MPN | 1SDA055873R1 |
| ABB product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Breaker frame | E2N1250 |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 3 |
| Trip unit | PR121/P-LSI R1250 |
| Release technology | Electronic |
| Protection functions | L (long-time), S (short-time) and I (instantaneous) |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 55 kA |
| Rated short-time withstand current (Icw) | 55 kA for 1 s; 42 kA for 3 s |
| Short-circuit performance level | N |
| Construction | Withdrawable |
| Component type | Moving part |
| Auxiliary contacts | 4 |
| Open/closed position indication | Yes |
| Power loss | 130 W |
| Mechanical durability | 25,000 cycles |
| Electrical durability at ≤440 V | 15,000 cycles |
| Electrical durability at 500–690 V | 15,000 cycles |
| Dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Net weight | 49 kg |
| Standard | IEC |
| EAN | 8015644572136 |
| Customs tariff number | 85362090 |
The ABB 1SDA055873R1 is a 1250 A three-pole withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems.
The fitted PR121/P-LSI R1250 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.
The E2N1250 provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC.
The 1SDA055873R1 is a withdrawable three-pole circuit breaker moving part designed for use with the appropriate ABB E2 fixed part in a compatible switchgear assembly.
LSI identifies the three overcurrent protection functions: L for long-time overload protection, S for short-time delayed short-circuit protection and I for instantaneous short-circuit protection.
ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining high-current capability, electronic protection and flexible withdrawable switchgear integration.