1SDA055873R1 ABB E2N1250 PR121/P-LSI 1250 A 3-Pole Withdrawable Air Circuit Breaker Moving Part

1SDA055873R1 ABB E2N1250 PR121/P-LSI 1250 A 3-Pole Withdrawable Air Circuit Breaker Moving Part

ABB 1SDA055873R1 SACE New Emax E2N1250 three-pole withdrawable air circuit breaker moving part with 1250 A rated current, PR121/P-LSI R1250 electronic protection and 65 kA Icu at 400 V AC.

SKU: 1SDA055873R1Alt SKU: E2N12MPN: 1SDA055873R1
Price
List Price £10,891.71 ex VAT
Your Price (ex VAT) Save 25%
£8,168.78 25% OFF
You save £2,722.93 per unit
Manufacturer Lead Time Estimated Delivery 7 weeks
Get the best trade prices Trade exclusive

Create an online account to unlock exclusive pricing, special offers and more.

Create an online account Quick & easy setup
SUBTOTAL (EX VAT) £8,168.78
Trade pricing is personalised to your account

Manufacturer Lead Time

£8,168.78

Why Choose the ABB 1SDA055873R1 E2N1250 Air Circuit Breaker Moving Part?

The ABB 1SDA055873R1 is a SACE New Emax E2N1250 air circuit breaker (ACB) moving part designed for dependable switching and protection in demanding low-voltage electrical distribution systems. This three-pole withdrawable breaker moving part has a rated uninterrupted current of 1250 A and is equipped with the ABB PR121/P-LSI R1250 electronic overcurrent release.

The PR121/P-LSI trip unit provides long-time (L), short-time (S) and instantaneous (I) protection. This combination protects against overload and short-circuit conditions while the short-time protection function supports selective coordination between upstream and downstream protective devices in industrial, commercial and infrastructure power distribution networks.

The E2N1250 performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC. The 1SDA055873R1 is specifically a three-pole withdrawable moving part, enabling integration with the appropriate ABB E2 fixed part while facilitating isolation, inspection, maintenance and replacement within compatible switchgear assemblies.

Key Advantages

  • Genuine ABB SACE New Emax E2N1250 withdrawable circuit breaker moving part.
  • 1250 A rated uninterrupted current for high-current low-voltage distribution.
  • Three-pole configuration for three-phase electrical systems.
  • PR121/P-LSI R1250 electronic overcurrent release.
  • Provides long-time, short-time and instantaneous protection.
  • 65 kA Icu at 400 V AC for demanding prospective fault-current conditions.
  • Withdrawable construction facilitates electrical isolation, inspection, servicing and replacement.

Key Features

  • ABB SACE New Emax E2N1250 series.
  • 1250 A rated uninterrupted current.
  • 690 V AC rated operational voltage.
  • Three-pole withdrawable moving part.
  • PR121/P-LSI R1250 electronic trip unit.
  • Long-time overload protection.
  • Short-time delayed short-circuit protection.
  • Instantaneous short-circuit protection.
  • 65 kA Icu and Ics at 400 V AC.
  • 55 kA Icu and Ics at 690 V AC.
  • 55 kA short-time withstand current for 1 s.
  • 1000 V rated insulation voltage.
  • 12 kV rated impulse withstand voltage.
  • Four auxiliary contacts for circuit-breaker status signalling.
  • Open/closed circuit-breaker position indication.

Selective Withdrawable Protection for Power Distribution

Air circuit breakers such as the ABB SACE New Emax E2N1250 provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. With a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, the E2N performance level is suited to installations where substantial prospective fault currents must be safely interrupted.

The PR121/P-LSI release combines long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection. The short-time function supports selective coordination within multi-level distribution systems, while the withdrawable moving-part construction makes the 1SDA055873R1 particularly suitable for switchgear where straightforward isolation, maintenance and breaker replacement are important.

Typical Applications

  • Industrial low-voltage switchboards and distribution systems.
  • Withdrawable power distribution assemblies.
  • Main incoming circuit protection.
  • High-current feeder protection.
  • Manufacturing and process industry power systems.
  • Commercial building electrical distribution.
  • Infrastructure and utility electrical installations.
  • Distribution systems requiring selective short-circuit protection.

Technical Specifications

Series SACE New Emax E2N
Extended product type E2N1250PR121/P-LSIIn=1250A3pWMP
Order code / MPN 1SDA055873R1
ABB product group 310513-New Emax
Product type Air circuit breaker moving part
Breaker frame E2N1250
Rated uninterrupted current (Iu) 1250 A
Rated operational current (Ie) 1250 A
Rated operational voltage 690 V AC
Rated insulation voltage (Ui) 1000 V
Rated impulse withstand voltage (Uimp) 12 kV
Current type AC
Number of poles 3
Trip unit PR121/P-LSI R1250
Release technology Electronic
Protection functions L (long-time), S (short-time) and I (instantaneous)
Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC 65 kA
Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC 55 kA
Rated service short-circuit breaking capacity (Ics) at 220–440 V AC 65 kA
Rated service short-circuit breaking capacity (Ics) at 500–690 V AC 55 kA
Rated short-time withstand current (Icw) 55 kA for 1 s; 42 kA for 3 s
Short-circuit performance level N
Construction Withdrawable
Component type Moving part
Auxiliary contacts 4
Open/closed position indication Yes
Power loss 130 W
Mechanical durability 25,000 cycles
Electrical durability at ≤440 V 15,000 cycles
Electrical durability at 500–690 V 15,000 cycles
Dimensions (W × H × D) 324 × 461 × 396.5 mm
Net weight 49 kg
Standard IEC
EAN 8015644572136
Customs tariff number 85362090

Frequently Asked Questions

What is the ABB 1SDA055873R1 used for?

The ABB 1SDA055873R1 is a 1250 A three-pole withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems.

What protection functions does the ABB 1SDA055873R1 provide?

The fitted PR121/P-LSI R1250 electronic trip unit provides long-time overload, short-time delayed short-circuit and instantaneous short-circuit protection.

What is the breaking capacity of the ABB 1SDA055873R1?

The E2N1250 provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC.

Is the ABB 1SDA055873R1 fixed or withdrawable?

The 1SDA055873R1 is a withdrawable three-pole circuit breaker moving part designed for use with the appropriate ABB E2 fixed part in a compatible switchgear assembly.

What does LSI mean on the ABB PR121/P trip unit?

LSI identifies the three overcurrent protection functions: L for long-time overload protection, S for short-time delayed short-circuit protection and I for instantaneous short-circuit protection.

Trusted by Electrical Professionals Worldwide

ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining high-current capability, electronic protection and flexible withdrawable switchgear integration.