Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055872R1 SACE New Emax E2N1250 three-pole withdrawable air circuit breaker moving part with 1250 A rated current, PR121/P-LI R1250 electronic protection and 65 kA Icu at 400 V AC.
£7,947.80
The ABB 1SDA055872R1 is a SACE New Emax E2N1250 air circuit breaker (ACB) moving part designed for dependable switching and protection in demanding low-voltage electrical distribution systems. This three-pole withdrawable breaker moving part has a rated uninterrupted current of 1250 A and is equipped with the ABB PR121/P-LI R1250 electronic overcurrent release.
The PR121/P-LI trip unit provides long-time (L) overload and instantaneous (I) short-circuit protection. Its adjustable protection characteristics help safeguard conductors, switchgear and connected equipment against overload and severe short-circuit conditions, making the breaker suitable for industrial, commercial and infrastructure power distribution.
The E2N1250 performance level provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC. The 1SDA055872R1 is specifically the three-pole withdrawable moving part, enabling integration with the appropriate ABB E2 fixed part and supporting convenient isolation, maintenance and replacement within compatible switchgear assemblies.
Air circuit breakers such as the ABB SACE New Emax E2N1250 provide switching, isolation and overcurrent protection for high-current low-voltage distribution circuits. With a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC, the E2N performance level is suited to installations where substantial prospective fault currents must be safely interrupted.
The PR121/P-LI release combines adjustable long-time overload protection with instantaneous short-circuit protection. Together with its 1250 A current rating and withdrawable three-pole construction, the 1SDA055872R1 provides a practical solution for switchgear applications where straightforward isolation, inspection and breaker replacement are important operational requirements.
| Series | SACE New Emax E2N |
|---|---|
| Order code / MPN | 1SDA055872R1 |
| ABB product group | 310513-New Emax |
| Product type | Air circuit breaker moving part |
| Breaker frame | E2N1250 |
| Rated uninterrupted current (Iu) | 1250 A |
| Rated operational current (Ie) | 1250 A |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Current type | AC |
| Number of poles | 3 |
| Trip unit | PR121/P-LI R1250 |
| Release technology | Electronic |
| Protection functions | L (long-time) and I (instantaneous) |
| Overload release setting range | 500–1250 A |
| Instantaneous short-circuit release adjustment range | 1875–18750 A |
| Rated ultimate short-circuit breaking capacity (Icu) at 220–440 V AC | 65 kA |
| Rated ultimate short-circuit breaking capacity (Icu) at 500–690 V AC | 55 kA |
| Rated service short-circuit breaking capacity (Ics) at 220–440 V AC | 65 kA |
| Rated service short-circuit breaking capacity (Ics) at 500–690 V AC | 55 kA |
| Rated short-time withstand current (Icw) | 55 kA for 1 s; 42 kA for 3 s |
| Short-circuit performance level | N |
| Construction | Withdrawable |
| Component type | Moving part |
| Auxiliary contacts | 4 changeover contacts |
| Open/closed position indication | Yes |
| Motor operating mechanism | Optional |
| Power loss | 130 W |
| Mechanical durability | 25,000 cycles |
| Electrical durability | 15,000 cycles |
| Dimensions (W × H × D) | 324 × 461 × 396.5 mm |
| Net weight | 49 kg |
| Standard | IEC |
| EAN | 8015644572129 |
| Customs tariff number | 85362090 |
The ABB 1SDA055872R1 is a 1250 A three-pole withdrawable air circuit breaker moving part designed for switching and protecting high-current low-voltage electrical distribution systems.
The fitted PR121/P-LI R1250 electronic trip unit provides long-time overload and instantaneous short-circuit protection.
The E2N1250 provides a rated ultimate short-circuit breaking capacity of 65 kA at 400 V AC and 55 kA at 690 V AC.
The 1SDA055872R1 is a withdrawable three-pole circuit breaker moving part designed for use with the appropriate ABB E2 fixed part in a compatible switchgear assembly.
The PR121/P-LI configuration provides an overload release setting range of 500–1250 A and an instantaneous short-circuit release adjustment range of 1875–18750 A.
ABB SACE Emax air circuit breakers are engineered for dependable switching and protection in demanding low-voltage power distribution systems, combining high-current capability, electronic overcurrent protection and flexible withdrawable switchgear integration.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.