Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
ABB 1SDA055835R1 SACE Emax E2B 2000 is a 2000 A four-pole fixed air circuit breaker with a PR122/P-LI electronic release, rear horizontal terminals and 42 kA short-circuit breaking capacity at 415 V AC.
£12,878.09
The ABB 1SDA055835R1 is a SACE Emax E2B 2000 air circuit breaker designed for high-current switching and overcurrent protection in low-voltage AC power distribution systems. This four-pole fixed circuit breaker has a rated current of 2000 A and is equipped with an electronic PR122/P-LI R2000 overcurrent release providing long-time overload and instantaneous short-circuit protection.
Part of the proven ABB SACE Emax range, the E2B 2000 combines substantial current-carrying capability with electronic circuit protection for industrial switchboards and power distribution assemblies. Its B short-circuit performance level provides rated ultimate and service short-circuit breaking capacities of 42 kA at 415 V AC, together with a rated short-time withstand current of 42 kA.
The 1SDA055835R1 is a four-pole fixed (F) circuit breaker fitted with rear horizontal (HR) terminals. It has a rated operational voltage of 690 V AC, rated insulation voltage of 1000 V and rated impulse withstand voltage of 12 kV. Four auxiliary contacts and circuit-breaker open/closed position indication support integration with switchboard signalling and monitoring systems.
Air circuit breakers such as the ABB SACE Emax E2B 2000 provide switching and overcurrent protection for high-current low-voltage distribution circuits. The PR122/P-LI electronic release provides long-time protection against sustained overloads together with instantaneous protection against severe short-circuit currents, helping protect conductors, switchgear and connected equipment.
The combination of 2000 A current capacity, four-pole switching, fixed construction and 42 kA short-circuit performance at 415 V AC makes the 1SDA055835R1 suitable for main incoming and high-current feeder applications. Rear horizontal terminals simplify integration with suitable switchboard busbar arrangements, while auxiliary contacts provide useful circuit-breaker status information for control and monitoring systems.
| Series | SACE Emax |
|---|---|
| ABB order code | 1SDA055835R1 |
| Product type | Air circuit breaker |
| Frame / sub-type | E2 |
| Short-circuit performance level | B |
| Rated current (In) | 2000 A |
| Rated uninterrupted current (Iu) | 2000 A |
| Rated operational current (Ie) | 2000 A |
| Number of poles | 4 |
| Current type | AC |
| Rated operational voltage | 690 V AC |
| Rated insulation voltage (Ui) | 1000 V |
| Rated impulse withstand voltage (Uimp) | 12 kV |
| Rated ultimate short-circuit breaking capacity (Icu) at 415 V AC | 42 kA |
| Rated service short-circuit breaking capacity (Ics) at 415 V AC | 42 kA |
| Rated short-time withstand current (Icw) | 42 kA for 1 s |
| Release | PR122/P-LI R2000 |
| Release type | Electronic |
| Protection functions | LI – long-time and instantaneous |
| Long-time protection (L) | Overload protection |
| Instantaneous protection (I) | Instantaneous short-circuit protection |
| Installation | Fixed |
| Terminal connection | Rear horizontal |
| Auxiliary contacts | 4 |
| Position indication | Circuit breaker open / closed |
| Power loss | 180 W |
| Mechanical durability | 25,000 cycles |
| Mechanical operating frequency | 60 cycles per hour |
| Electrical durability at ≤440 V | 10,000 cycles |
| Electrical durability at 500–690 V | 8,000 cycles |
| Electrical operating frequency | 30 cycles per hour |
| Standard | IEC |
| Weight | 68 kg |
| EAN | 8015644571757 |
The ABB 1SDA055835R1 is a 2000 A four-pole air circuit breaker designed for switching and overcurrent protection in high-current low-voltage industrial, commercial and infrastructure power distribution systems.
The breaker is fitted with a PR122/P-LI R2000 electronic release providing long-time overload and instantaneous short-circuit protection.
LI denotes long-time and instantaneous protection. Long-time protection responds to sustained overload conditions, while instantaneous protection provides rapid operation during severe short-circuit faults.
The 1SDA055835R1 is a fixed four-pole circuit breaker fitted with rear horizontal terminals for permanent installation within a compatible low-voltage switchboard.
The E2B 2000 has rated ultimate and service short-circuit breaking capacities of 42 kA at 415 V AC and a rated short-time withstand current of 42 kA for both 1 s and 3 s.
ABB SACE Emax air circuit breakers provide robust switching and electronic protection for low-voltage power distribution, combining high current capability, dependable fault interruption and flexible switchboard integration for demanding industrial and infrastructure applications.
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.